Brand:

ABB ACS880-01-045A-3 Wall-Mounted Drive 22 kW 45 A

Description

A 22 kW industrial drive on a 400 V supply

ABB’s single drives catalogue lists the ACS880-01-045A-3 as an ACS880-01 drive on the 400 V network. The power stage delivers 45 A (22 kW typical motor power) in frame R4. Use cases include sections of a printing or paper machine and pumping stations. Because the choke and Safe Torque Off are already inside, the drive can be mounted on the wall without extra filter hardware.

Technical specifications

Parameter Specification
Type designation ACS880-01-045A-3
Series ACS880-01, wall-mounted single drive, ACS880 industrial drive platform
Supply voltage 3-phase 380 to 415 V (400 V table)
Nominal rating 22 kW, 45 A
Light-overload rating 43 A = 22 kW
Heavy-duty use 18.5 kW, 38 A
Peak current IMAX 64 A
Frame size R4
IP21 size (H1 x W x D) 576 x 203 x 274 mm; 18.6 kg
IP55 size (H x W x D) 576 x 203 x 344 mm; 19.1 kg
Noise level 64 dB(A)
Power loss for cabinet design 526 W (90% frequency, full current)
Cooling air flow 134 m3/h
Brake chopper availability Built in as standard (frames R1 to R4)
Standard brake resistor SACE15RE13 (13 ohm, 435 kJ, 2 kW continuous)
Minimum brake resistance 13 ohm for 22 kW braking power
Optional sine filter B84143V0050R229, 43 A, 22 kW

Sizing and installing the ACS880-01-045A-3

From the ratings table: nominal 45 A / 22 kW, light overload 43 A / 22 kW, heavy duty 38 A / 18.5 kW, IMAX 64 A. Variable-torque loads normally use the light overload column; constant-torque machinery should be sized from the heavy-duty column. Always size from the motor nameplate current at your voltage and check the ambient temperature and altitude against the hardware manual.

The standard IP21 body of frame R4 measures 576 mm high with the cable entry box (490 mm without it), 203 mm wide and 274 mm deep, and weighs 18.6 kg. IP55 enclosures are larger, 576 x 203 x 344 mm at 19.1 kg. The drive loses about 526 W, needs 134 m3/h of cooling air and runs at 64 dB(A).

Braking, filters and options

A brake chopper is built in as standard (frames R1 to R4). The catalogue pairs it with SACE15RE13 (13 ohm, 435 kJ) for 22 kW braking power; the minimum resistance is 13 ohm. The EMC filter options are +E202 (C2), +E200 (C3) and +E201 (C3 on ungrounded supplies); the base drive is C4. A sine filter, type B84143V0050R229, is listed for 43 A at 22 kW and is useful with long motor cables or submersible pumps.

The ZCU control unit provides 6 digital inputs, 2 digital inputs/outputs, 2 analog inputs, 2 analog outputs, 3 relay outputs, STO and an isolated RS485 port. The control unit has three slots for adapters, I/O extension, feedback and safety modules.

Related ABB products: ABB ACQ580-01-046A-4 Water Drive 22 kW 45 A, ABB ACS580-01-046A-4 AC Drive 22 kW 45 A, ABB ACQ580-01-05A7-4 Water Drive 2.2 kW 5.6 A, ABB ACQ580-01-145A-4 Water Drive 75 kW 145 A, ABB ACS580-01-05A7-4 AC Drive 2.2 kW 5.6 A and ABB ACS580-01-145A-4 AC Drive 75 kW 145 A.

Documentation and ordering

This page follows ABB’s ACS880 single drives catalogue (3AUA0000098111, linked) plus the ABB product page for the ACS880-01-045A-3. Seven Star LLC quotes the ACS880-01-045A-3 from Muscat once it has the motor nameplate, supply voltage and option list. Please confirm the type code, options, motor data and ambient conditions before you order; the catalogue revision may be newer than the linked copy. Other sizes are listed in AC drives, and a smaller general purpose family is on the ABB ACS580 page.

Datasheets & Documents
  • PDF Catalog ABB ACS880 single drives catalog (3AUA0000098111) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

Frequently Asked Questions

What are the duty ratings of the ACS880-01-045A-3?
ABB lists 45 A nominal (22 kW), 43 A (22 kW) for light overload, 38 A (18.5 kW) for heavy duty and 64 A maximum output current.
What size and weight is the ACS880-01-045A-3 in IP21?
It is frame R4: 576 mm high with cable entry box, 203 mm wide, 274 mm deep and 18.6 kg; the IP55 version is 576 x 203 x 344 mm and 19.1 kg.
Does the ACS880-01-045A-3 include a brake chopper?
The brake chopper is built in as standard (frames R1 to R4); the catalogue lists SACE15RE13 (13 ohm) and a minimum resistance of 13 ohm.
How much heat and cooling air does the ACS880-01-045A-3 need?
The catalogue gives 526 W of heat dissipation, 134 m3/h of air flow and 64 dB(A) noise.
Which EMC filter options exist for the ACS880-01-045A-3?
The catalogue lists +E202 for C2, +E200 for C3 and +E201 for ungrounded networks; category C4 is standard on 380 to 500 V ACS880-01 drives.