Brand:

Hydac EDS 44F9-0500-1P-DS-000 Flameproof Pressure Switch 500 psi

Description

Hydac EDS 44F9-0500-1P-DS-000 is a programmable pressure switch for hazardous areas that watches a 500 psi circuit and drives a PNP output without a separate transmitter and relay. The welded stainless cell with thin-film strain gauges sits in a 316L flameproof body, the process port is 1/4-18 NPT female and the cable leaves through a 1/2-14 NPT conduit thread. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

What makes EDS 44F9-0500-1P-DS-000 different from a mechanical switch

A diaphragm switch is set once with a screw and drifts with temperature and wear. EDS 44F9-0500-1P-DS-000 stores its switch point electronically, with an adjustment grid of 1 psi at this range, and holds it to 1 percent of full scale maximum. The switch point may be placed between 5 and 100 percent of range and the hysteresis window between 1 and 96 percent, both set by the HPG 3000 unit in a menu. Once the programmer is disconnected the settings stay, which prevents unintended changes on site.

The 1 psi grid at this range is the finest in the 44F9 group: a 500 psi circuit can therefore be supervised at, for example, 175 psi with a hysteresis of 20 psi. Remember that the accuracy limit of 1 percent means 5 psi at full scale, so the stored set point should leave room for that tolerance when it protects a pump from running dry.

Main features of EDS 44F9-0500-1P-DS-000

  • One PNP transistor output, 1.2 A maximum, with adjustable N/O or N/C direction.
  • Programmable on and off delays from 8 to 2000 ms.
  • Sealed gauge cell for the 500 psi range, protection class IP 69K.
  • Supply 12 to 30 V DC with reverse-polarity, overvoltage and short-circuit protection.
  • Response time 8 ms; more than 100 million switching cycles.
  • Triple approval including mining category I M2.

Specifications of EDS 44F9-0500-1P-DS-000

Parameter Value
Model code EDS 44F9-0500-1P-DS-000
Material number (catalog) 921933
Setting range 0 to 500 psi
Overload pressure 1160 psi
Burst pressure 2900 psi
Cell type Sealed gauge (S)
Process connection 1/4-18 NPT, female
Tightening torque 40 N·m (30 lb-ft)
Switching outputs 1 PNP, programmable
Output load max. 1.2 A
Switch-point increment 1 psi
Switch point / hysteresis window 5 to 100 percent / 1 to 96 percent of range
Switching delay 8 to 2000 ms via HPG 3000 programming unit
Response time 8 ms
Accuracy 1 percent FS maximum (0.5 percent typical)
Repeatability 0.1 percent FS maximum
Supply voltage 12 to 30 V DC, ripple 5 percent or less
Current consumption 25 mA plus switching current, 1.225 A total maximum
Electrical connection 1/2-14 NPT conduit, flying leads
Core assignment red +UB, white switch output 1, black 0 V, green SDA (programming), brown not used
Switching cycles more than 100 million
Compensated temperature T5 / T130: -13 to 176 degF; T6 / T110: -13 to 140 degF
Storage temperature -40 to 212 degF
Protection IP 69K (sealed gauge)
Vibration 20 g, 10 to 500 Hz
Weight 0.661 lb (about 300 g)
Approvals ATEX KEMA 10ATEX100 X; CSA MC 224264; IECEx KEM 10.0053X

Typical applications

Use it as a pump-protection switch on a hydraulic power unit, a low-pressure trip on a lubricating circuit or an accumulator charge monitor in a mine or on a platform. In an Omani gas plant the 500 psi window suits instrument-air compressors and nitrogen seal-gas headers inside classified cabinets, where EDS 44F9-0500-1P-DS-000 closes an interlock to a safety PLC input.

How EDS 44F9-0500-1P-DS-000 differs from other EDS 4400 flameproof versions

Compared with EDS 44F9-3000-1P-DS-000 the range falls from 3000 to 500 psi, overload from 7250 to 1160 psi, burst from 14500 to 2900 psi and the switch-point increment from 5 psi to 1 psi. Compared with EDS 44F9-6000-1P-DS-000 the factors are 12 times lower in range. Against the two-output EDS 4479-3000-2P-DS-000 the port is NPT female instead of SAE 6 male and there is only one output at up to 1.2 A.

Selection notes

Pick a range so that the working point sits in the middle third of the span: for EDS 44F9-0500-1P-DS-000 that means normal operation between roughly 150 and 350 psi. Programming equipment must be ordered separately, and a safe-area power supply of 12 to 30 V DC is needed. If you need a second contact for alarm and trip, use a two-output version.

Installation and programming

Seal the female thread, tighten the hex to 40 N·m and route the cable to a certified enclosure. Red goes to plus, black to zero volts, white to the load and the green programming core is connected to the HPG 3000 only during setup. Program the set point, hysteresis and delay times, then disconnect the programmer and test the switching direction with a hand pump on EDS 44F9-0500-1P-DS-000.

Maintenance

The switch has no moving parts apart from the measuring membrane. Check the set points during the yearly instrument audit, keep a copy of the programmed values with the loop record and replace the unit rather than opening the flameproof enclosure.

Frequently asked questions about EDS 44F9-0500-1P-DS-000

How is EDS 44F9-0500-1P-DS-000 programmed? With the HYDAC HPG 3000 programming unit, ordered separately. It sets switch point, hysteresis, N/O or N/C direction and the switching delays, and the instrument keeps the values when the unit is unplugged.

What does 1P in the code mean? One programmable PNP transistor switching output; 2P would give two outputs.

Which cell does DS stand for? D is the combined CSA, ATEX and IECEx approval and S is a sealed gauge cell, offered from 500 psi upwards.

What is the maximum switching current? 1.2 A on the one-output version; the two-output versions are limited to 1 A each.

How do I request EDS 44F9-0500-1P-DS-000? Send an RFQ with the part number, quantity and delivery location to Seven Star LLC.

Documents and quotation

The datasheet for EDS 44F9-0500-1P-DS-000 is provided with this page. Please send an RFQ giving EDS 44F9-0500-1P-DS-000, the quantity and the delivery site to receive availability and lead time.

Other Models in the EDS 4400 ExD Range

Seven Star LLC supplies models from the EDS 4400 ExD range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Hydac EDS 4479-3000-2P-DS-000 Two-Output Flameproof Pressure SwitchPressure SwitchesView details
Hydac EDS 44F9-6000-1P-DS-000 High-Pressure Ex d Switch 6000 psiPressure SwitchesView details
Hydac EDS 44F9-3000-1P-DS-000 Programmable Ex d Pressure SwitchPressure SwitchesView details
Hydac EDS 44F9-0500-1P-DS-000 Flameproof Pressure Switch 500 psiPressure SwitchesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Hydac EDS 44F9-0500-1P-DS-000 Flameproof Pressure Switch 500 psi Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

HYDAC is the German hydraulics group known for hydraulic filters, accumulators and electronic pressure and temperature sensors. It was founded in 1963 in Sulzbach, Saarland, by Werner Dieter and Otmar Schön. The name comes from "hydraulic accumulator", the first product it made under licence. It is still a family company headquartered in Sulzbach.

Seven Star LLC is an independent supplier in Muscat. We list HYDAC filters, filter elements, accumulators, pressure transmitters and switches, and supply them for hydraulic power units, turbines, compressors and mobile machines in Oman and the GCC.

HYDAC at a glance

Established 1963, Sulzbach, Saarland, Germany
Name From "hydraulic accumulator", the first product line
Ownership Family-owned; around 50 international subsidiaries
Product families Hydraulic and lube oil filters, breathers and dryers, bladder and piston accumulators, electronic pressure, temperature and level sensors and switches, coolers, valves and fluid condition monitoring

HYDAC products we list

Family Models Typical use
Pressure filters DF/DFF, DFN, DFDK change-over, HFM, MDF, MFM, FMND Protect servo and proportional valves downstream of the pump
Low-pressure, return and suction filters LF/LFF, LPF, NF, RFL, RFLD, FLND, RFM, RFN, SF, MF/MFD, MFX Return line, lube oil, turbine oil and suction filtration
Breathers and indicators BF, ELF, BDE dryer, VD clogging indicator Keep dust and moisture out of the tank and show when an element needs changing
Accumulators SB330 bladder accumulator Energy storage, pulsation damping and emergency actuation
Pressure transmitters HDA 4445, HDA 4745, HDA 4844, HDA 4345, HDA 4145, HDA 44Z6, HDA 4746 safety, HDA 4748, HDA 7476, HPT 1448S, HPT 506 DP Pressure measurement in hydraulic and process systems
Pressure, temperature and level switches EDS 3400, EDS 3316, EDS 3146, EDS 34Z6, EDS 4348, EDS 824 IO-Link, EDS 8446, EDS 1791, ETS 1700, ETS 3226, ETS 3866, ENS 3116 Local display plus switching outputs for alarms and interlocks

Most hydraulic failures start with dirty or wet oil. That is why a system has filters at several points: a pressure filter in front of sensitive valves, a return filter that cleans what comes back to the tank, and a breather that stops dust and humidity entering as the oil level moves. The filter element's rating (for example 3, 10 or 25 µm) and its material decide what cleanliness class the oil reaches. On HYDAC sensors, the type code also sets the pressure range, the output and the connector. For example, HDA 4445-A-400-000 is a 4-20 mA transmitter for 0-400 bar.

Where HYDAC products are used

In Oman and the GCC, HYDAC filters, accumulators and sensors are used on turbine and compressor lube oil systems, hydraulic power units, offshore and marine hydraulics, cranes, presses, steel and aluminium plants, and construction and mobile machines.

Ordering HYDAC products: what we need

Send the full HYDAC type code or part number from the label. For filter elements, the element code on the end cap (for example 0160 D 010 BN4HC) gives the size, filter type, micron rating and material. For accumulators, send the volume, pressure rating and connection. For sensors, send the pressure range, output signal and connector.

Facts checked against HYDAC company information, October 2026.

FAQ

Questions about the Hydac EDS 44F9-0500-1P-DS-000 Flameproof Pressure

Answers from our engineering team on installation, compatibility and integration.

01How is EDS 44F9-0500-1P-DS-000 programmed?
With the HYDAC HPG 3000 programming unit, ordered separately. It sets switch point, hysteresis, N/O or N/C direction and the switching delays, and the instrument keeps the values when the unit is unplugged.
02What does 1P in the code mean?
One programmable PNP transistor switching output; 2P would give two outputs.
03Which cell does DS stand for?
D is the combined CSA, ATEX and IECEx approval and S is a sealed gauge cell, offered from 500 psi upwards.
04What is the maximum switching current?
1.2 A on the one-output version; the two-output versions are limited to 1 A each.
05How do I request EDS 44F9-0500-1P-DS-000?
Send an RFQ with the part number, quantity and delivery location to Seven Star LLC.