Brand:

ABB CP-E 24/1.25 Power Supply 24 V DC 1.25 A 30 W

Description

ABB CP-E 24/1.25 24 V DC power supply, 1.25 A / 30 W

The ABB CP-E 24/1.25 is a primary switch mode power supply from the CP-E range with a regulated 24 V DC output, a rated output current of 1.25 A and a rated output power of 30 W. It accepts a wide input of 85 to 264 V AC or 90 to 375 V DC, with a rated input of 100 to 240 V AC, so it can be wired to most single-phase supplies without a selector. The order code is 1SVR427031R0000.

It is a small-footprint unit, 40.5 mm wide, aimed at one controller and a few sensors on a single 24 V circuit. It adds a transistor signalling output for output-voltage-OK, which a PLC can monitor.

The output voltage is adjustable within 24 to 28 V DC, which lets you trim for cable drop in long runs or for loads that need a slightly higher level than the nominal 24 V.

Reading the CP-E 24/1.25 type designation

The CP-E name carries the key electrical data, so the type can be checked against a load list in a moment.

Code group Meaning
CP-E ABB DIN rail switch mode power supply range
24 Nominal output voltage 24 V DC
1.25 Rated output current in amperes (1.25 A)

Within the range, the same 24 V output is offered from 0.75 A up to 20 A so the load list should be totalled and the next higher rating chosen, with some reserve.

CP-E 24/1.25 technical specifications

Parameter Specification
Manufacturer / part number ABB / CP-E 24/1.25
Order code / EAN 1SVR427031R0000 / 4016779656870
Type Primary switch mode power supply, single phase, DIN rail
Rated input voltage 100 to 240 V AC
Input voltage range (AC) 85 to 264 V AC
Input voltage range (DC) 90 to 375 V DC
Rated frequency / limits 50 Hz / 47 to 63 Hz
Rated output voltage 24 V DC
Output voltage adjustment range 24 to 28 V DC
Rated output current 1.25 A
Rated output power 30 W
Output characteristic U/I Characteristic Curve
Rated insulation voltage / impulse 300 V / 4 kV (input circuit to output circuit)
Degree of protection Housing IP20
Ambient air temperature Operation -40 to +70 °C
Maximum operating altitude 5000 m
EMC immunity Immunity – Class B
Surge immunity IEC 61000-4-5 Level 3 Line-to-Line 2 kV
Input / output connecting capacity Flexible with ferrule, 0.2 to 2.5 mm² (input and output)
Mounting TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Minimum mounting distance Electrical Conductive Board, Horizontal 25 mm
Dimensions W x H x D 40.5 mm x 90 mm x 114 mm
Net weight 0.27 kg

Values come from the ABB product page for the CP-E 24/1.25. Confirm the input range against your supply and check the temperature limits against the panel conditions before you specify the unit.

How the CP-E 24/1.25 behaves under load

The output follows a U/I characteristic: the unit supplies constant voltage up to its rated current and then limits the current, with the voltage falling, which allows a stable restart on loads with a higher inrush. The output-voltage-OK transistor signal lets you wire a simple supervision input into the control system.

The input range starts at the lower limit of 85 and reaches 264 V AC, so the unit tolerates both low mains and an over-voltage condition within that window. A DC input of 90 to 375 V DC is also accepted, which allows operation from a battery-backed or generator-fed DC bus where needed.

ABB states that the unit allows parallel operation to enable redundancy, and a redundancy unit is available as an accessory.

Where the CP-E 24/1.25 fits and which parts go with it

The ABB CP-E 24/1.25 is a field-installed supply on a 35 mm DIN rail next to the circuit protection, and the 24 V rail it makes feeds PLCs, relays, sensors and signalling devices. It belongs to the same family as the CP-E 24/0.75, CP-E 24/1.25, CP-E 24/2.5, CP-E 24/5.0, CP-E 24/10.0 and CP-E 24/20.0, so a panel can standardise on one connection style and one set of labelling.

Protection on the input side should be sized to the input current and the inrush of the unit, and the 24 V output circuit can be divided into branches with small circuit breakers so that one faulty branch does not take down the rest. A redundancy unit, described by ABB as an accessory, allows two supplies to feed one 24 V rail.

Panel ventilation matters: leave the minimum mounting distance of the table around the unit, and keep power supplies away from the hottest zone of the enclosure.

Selection checklist for the CP-E 24/1.25

  • Load current: total the 24 V load and compare with 1.25 A, leaving a reserve for later extensions and for temperature derating.
  • Supply: confirm the available supply falls within 85 to 264 V AC or 90 to 375 V DC, including tolerance and sags.
  • Output voltage: the adjustment range of 24 to 28 V DC allows trimming for cable drop; set it with a meter under load.
  • Output characteristic: this unit has a u/i characteristic curve characteristic; verify that the load can start under it, particularly with capacitive inputs.
  • Temperature: the ABB data lists -40 to +70 °C for operation; compare with the real enclosure temperature.
  • Space: allow for 40.5 mm of DIN rail width plus the minimum mounting distance.

Installation, commissioning and maintenance of the CP-E 24/1.25

Install the CP-E 24/1.25 on a 35 mm DIN rail in the mounting position listed in the ABB data and keep the specified minimum distance to neighbouring devices. Input and output terminals accept flexible conductors with ferrules of 0.2 to 2.5 mm²; tighten them to 0.6 N·m.

Before energising, check polarity on the output side and make sure that the input is wired to the correct supply. At commissioning, measure the output voltage under typical load and adjust it inside 24 to 28 V DC. Where the unit has a voltage-OK output, confirm that the signal reaches the control system.

In maintenance, check the terminal tightness, dust on the housing and the ambient temperature of the cabinet. A power supply that runs warm for a long time in a closed cabinet ages faster, so ventilation and spacing are cheap ways to extend service life.

Typical applications of the CP-E 24/1.25 in Oman and the GCC

Typical loads are a small PLC with a handful of input modules, a few proximity sensors and relays, or a signalling lamp bank at a pump skid or a compressor package.

Because it has a voltage-OK signal and a wide input range, it is a good fit for sites where the mains can sag, and where an alarm on loss of 24 V should be sent to the control room.

Power supplies in the region face high cabinet temperatures, dust and, on the coast, salt-laden humidity; the temperature range printed in the table and the IP20 rating of the housing mean that the cabinet itself must provide protection against dust and moisture.

CP-E 24/1.25 and the CP-E range

Type Output power Output current Input range Output characteristic Width
CP-E 24/0.75 18 W 0.75 A 90 to 264 V AC Hiccup-Mode 22.5 mm
CP-E 24/1.25 30 W 1.25 A 85 to 264 V AC U/I Characteristic Curve 40.5 mm
CP-E 24/2.5 60 W 2.5 A 85 to 264 V AC U/I Characteristic Curve 40.5 mm
CP-E 24/5.0 120 W 5 A 90 to 132 V AC U/I Characteristic Curve 63.2 mm
CP-E 24/10.0 240 W 10 A 90 to 132 V AC U/I Characteristic Curve 83 mm
CP-E 24/20.0 480 W 20 A 90 to 264 V AC U/I Characteristic Curve 175 mm

The CP-E 24/1.25 is the 40.5 mm wide, U/I output with OK signal unit of the range. When a load grows past its rating, the next higher type in the table is the natural step, and the same wiring practice carries over.

Information to send with an RFQ for the CP-E 24/1.25

  • Exact type CP-E 24/1.25 (order code 1SVR427031R0000), quantity and required delivery time.
  • Total 24 V load and the reserve required.
  • Supply voltage and whether the input is AC or DC.
  • Need for a redundancy arrangement or output monitoring.
  • Cabinet ambient temperature and altitude.
  • Documents needed with the order, for example datasheets.

Documents and quotation

The official ABB data sheet for the CP-E 24/1.25 power supply (document 2CDC114044D0201, English) is attached on this page as a PDF and applies to the ABB CP-E 24/1.25. It sets out the input voltage range, the adjustable 24 V DC output, efficiency, derating with ambient temperature up to +70 °C, approvals, the wiring diagram and the dimension drawing. Check the rating and the characteristic against your circuit before ordering, then send us the quantity and the delivery location for a quotation.

Seven Star LLC supplies ABB power supplies and control gear in Oman and the GCC. Share your 24 V load list and we will match the unit to your cabinet.

Other Models in the Abb Cp E 24v Power Supply Range

Seven Star LLC supplies models from the Abb Cp E 24v Power Supply range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
ABB CP-E 24/0.75 Power Supply 24 V DC 0.75 A 18 WPower ModulesView details
ABB CP-E 24/1.25 Power Supply 24 V DC 1.25 A 30 WPower ModulesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet ABB CP-E 24/1.25 Power Supply Data Sheet (PDF) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB CP-E 24/1.25 Power Supply 24 V DC 1.25 A 30 W

Answers from our engineering team on installation, compatibility and integration.

01What output does the CP-E 24/1.25 deliver?
The CP-E 24/1.25 delivers a rated 24 V DC at 1.25 A, which is 30 W. The output voltage can be adjusted within 24 to 28 V DC.
02What input supply does the CP-E 24/1.25 accept?
The ABB data lists an AC input range of 85 to 264 V AC and a DC input of 90 to 375 V DC, with a rated input of 100 to 240 V AC. The frequency limits are 47 to 63 Hz.
03What is the output characteristic of the CP-E 24/1.25?
It has a u/i characteristic curve characteristic. The output follows a U/I characteristic: the unit supplies constant voltage up to its rated current and then limits the current, with the voltage falling, which allows a stable restart on loads with a higher inrush.
04Can two CP-E 24/1.25 units be used for redundancy?
ABB states that the unit allows parallel operation to enable redundancy, and a redundancy unit is available as an accessory. Check the ABB documentation for the correct redundancy unit and wiring before you plan a redundant 24 V rail.
05How wide is the CP-E 24/1.25 on the DIN rail?
The ABB data lists a width of 40.5 mm, a height of 90 mm and a depth of 114 mm. Allow the minimum mounting distance around the unit for cooling.