ABB ACH580-01-089A-4 45 kW HVACR Drive

Description

ABB ACH580-01-089A-4 HVACR drive for 45 kW motors

The ABB ACH580-01-089A-4 is a wall-mounted variable frequency drive from the ACH580 series, which ABB built specifically for heating, ventilation, air conditioning and refrigeration (HVACR). It belongs to frame size R4 v2, runs on a 3-phase 380 to 480 V supply and has a nominal output current of 89 A for a typical motor power of 45 kW. Typical duties are large AHU and chiller-plant fans, primary pumps and cooling tower cells, where one drive can replace a star-delta starter and add control, energy savings and a building-automation link.

This page explains how the ACH580-01-089A-4 is specified, what its application software does and which installation data matters, so that you can prepare a precise enquiry. The figures come from the ABB ACH580 HVACR catalog.

Decoding the ACH580-01-089A-4 type designation

The ACH580 type code follows the same structure as other ABB all-compatible drives.

Field Value in ACH580-01-089A-4 Meaning
Product series ACH580 HVACR drive with application software for fans, pumps and compressors
Type and construction 01 Standard six-pulse drive, wall-mounted construction
Rating 089A Current class label used in the ordering code; nominal current in the ratings table is 89 A
Voltage 4 3-phase 400 V class (380 to 480 V)
Options + codes For example +B056 for IP55, +F278 for a main disconnect switch, +J400 for the Hand-Off-Auto panel

ACH580-01-089A-4 technical specifications

Parameter Specification
Manufacturer / part number ABB / ACH580-01-089A-4
Product family ACH580-01 wall-mounted HVACR drive, frame R4 v2
Supply voltage 3-phase 380 to 480 V (+10 % / −15 %), 48 to 63 Hz
Nominal output current / power at 400 V 89 A / 45 kW
Nominal output current / power at 480 V 77 A / 60 hp
Output frequency 0 to 598 Hz
Motor control Scalar and vector control; induction, PM, SynRM and PM-assisted SynRM motors
Heat loss, cooling air, noise 1028 W typical; 159 m³/h (94 ft³/min); 70 dBA at full fan speed
Recommended input fuse 100 A gG (IEC); 110 A Class T (UL)
Degree of protection IP21 (UL Type 1) or IP55 (UL Type 12)
Ambient temperature –15 to +50 °C, with derating from +40 °C; no frost allowed
Altitude Full current 0 to 1000 m; reduced by 1 % per 100 m above 1000 m, up to 4000 m
EMC and efficiency EMC category C2 as standard (C1 as option up to 55 kW); efficiency class IE2
Communication BACnet MS/TP, Modbus RTU and N2 embedded (EIA-485); options include BACnet/IP and Modbus TCP
Control I/O (standard) 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 relay outputs, 24 V DC output up to 250 mA
Functional safety Safe Torque Off, SIL 3 / PL e

What makes the ACH580-01-089A-4 an HVACR drive

The hardware is close to other ABB general purpose drives, but the application software is tuned for building services. Fireman’s override keeps fans running during a fire by ignoring faults and warnings. Soft start and stop ramps reduce stress on belts, ducts and pipework. Flying start catches a free-wheeling fan without wasting time on braking. Air filter monitoring raises an alarm when a filter clogs, and resonance monitoring skips frequencies that excite ducts or pipes. For pumps, intelligent pump control manages up to eight parallel pumps, with dry-run protection, system overpressure protection and sleep/boost to avoid inefficient running at low demand.

Further functions are motor preheating against condensation, frost protection for heating coils, leakage and check-valve monitoring, bearing monitoring and a built-in real-time clock for scheduling. A dedicated cooling compressor package adds short-cycle protection, multi-compressor control and a refrigerant selection feature. The ACH580-01 is also listed as compliant with the IEC/UL 60335-2-40:2022 safety standard for use next to equipment with A2L and A3 refrigerants.

At 1,028 W of heat loss it is already a significant heat source in a closed panel, and the recommended input fuse is 100 A gG (110 A UL Class T).

Where ACH580-01-089A-4 fits in the ACH580 range

The ACH580-01 covers 0.75 to 355 kW on 380 to 480 V, with sibling products for other needs: ACH580-04 drive modules for cabinet builders, ACH580-07 cabinet-built drives, and the ultra-low harmonic ACH580-31 and ACH580-34 versions. In the 400 V wall-mounted list the ACH580-01-089A-4 sits between ACH580-01-073A-4 and ACH580-01-106A-4. For machinery, pumps and conveyors outside building services, the ACS580 general purpose family is the closer match, because it shares hardware but not the HVACR application macros.

Frame sizes and ratings related to ACH580-01-089A-4

Type designation Frame Nominal power (kW) Nominal current at 400 V (A) Current at 480 V (A) Power at 480 V (hp)
ACH580-01-062A-4 R4 or R4 v2 30 62 52 40
ACH580-01-073A-4 R4 or R4 v2 37 73 65 50
ACH580-01-089A-4 R4 v2 45 89 77 60

Selection and ordering checklist

  • Confirm the application: the ACH580-01-089A-4 carries HVACR macros for fans, pumps and compressors; for other machinery consider the ACS580.
  • Match the motor current to the 89 A nominal output at 400 V (77 A at 480 V).
  • Decide the enclosure: IP21 (UL Type 1) or IP55 (UL Type 12, code +B056). The IP55 version is designed for dust, moisture and vibration.
  • For IP55 frames R1 to R5, an integrated main disconnect switch (+F278) and the combined switch with EMC C1 filter (+F316) are available.
  • Choose the fieldbus: BACnet MS/TP, Modbus RTU and N2 are built in; BACnet/IP, Modbus TCP, PROFINET IO and EtherNet/IP are plug-in options.
  • Select the control panel: the Hand-Off-Auto assistant panel (+J400) is included as standard and can be replaced by another +Jxxx option.
  • Confirm plus codes and current class against the ABB ordering table before placing the order.

Installing and commissioning ACH580-01-089A-4

The standard R4 v2 enclosure is 203 mm wide. The IP55 version is 8 mm deeper and 1 kg heavier than the IP21 version. For a drive with a factory-fitted disconnect or EMC filter option, use the drawing for the full order code.

Enclosure Front height H3 (mm) Back height H4 (mm) Width (mm) Depth (mm) Weight (kg)
IP21 601 636 203 257 22
IP55 601 636 203 265 23

Source: ABB ACH580-01 hardware manual, R4 v2 row for IP21 (page 333) and IP55 (page 334).

Allow 159 m³/h of cooling air and 1028 W of dissipated heat in the panel or plant-room design. The recommended input protection is 100 A gG or 110 A UL Class T. During commissioning, the first start assistant sets the primary HVACR parameters; the default I/O wires a damper output, a run output and a fault output on the three relays, with a start interlock input. Store the parameters in the panel afterwards, because a backup can be restored to another drive. Keep the nameplate type code on file when ordering spares.

Typical applications of ACH580-01-089A-4 in Oman and the GCC

Drives of this size usually control a single large machine: a main cooling-water or boiler feed pump, a cooling tower fan, a process blower or a compressor in a power, desalination, oil and gas or petrochemical facility. Replacing a direct-on-line or star-delta starter with a drive cuts mechanical stress on couplings and pipework, reduces inrush current and allows the speed to follow the process. In the Gulf climate the thermal design of the electrical room is the main practical issue, so the heat loss and air flow data in this page are worth checking against the room cooling capacity. Air-handling units, chillers, cooling towers, chilled and condenser water pumps are the natural fit for the ACH580 in hotels, hospitals, airports, malls and data centres, where cooling demand is high for most of the year and energy savings from speed control are significant.

Information to send with an RFQ

Please send the full type designation with plus codes, the supply voltage and frequency, the motor power and rated current, the application (AHU fan, chilled water pump, cooling tower, compressor), the ambient temperature, the required enclosure, the building automation protocol and any disconnect, filter or fieldbus option. A nameplate photograph of the drive being replaced helps confirm a match with the ACH580-01-089A-4.

Documents and quotation

The ratings, cooling data, dimensions and options used in this description come from the ABB ACH580 HVACR catalog. Please verify the final selection of the ACH580-01-089A-4 against the current ABB documentation for your project.

Seven Star LLC supplies ABB drives in Oman and the GCC. Send the part number and your duty details and we will confirm the available documents and return a quotation with delivery information.

Other Models in the Abb Ach580 01 Wall Range

Seven Star LLC supplies models from the Abb Ach580 01 Wall range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
ABB ACH580-01-03A4-4 1.1 kW HVACR DriveAC DrivesView details
ABB ACH580-01-07A3-4 3 kW HVACR DriveAC DrivesView details
ABB ACH580-01-089A-4 45 kW HVACR DriveAC DrivesYou are viewing this model
ABB ACH580-01-246A-4 132 kW HVACR DriveAC DrivesView details
Datasheets & Documents
  • PDF Brochure ABB ACH580 HVACR Drive Flyer Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB ACH580-01-089A-4 45 kW HVACR Drive

Answers from our engineering team on installation, compatibility and integration.

01What is the difference between ACH580-01-089A-4 and ACH580-01-073A-4?
The 089A-4 is rated 45 kW and 89 A in frame R4 v2. The 073A-4 is rated 37 kW and 73 A and appears in ABB tables in both R4 and R4 v2 versions. Check the installed frame and enclosure when planning a replacement.
02Is ACH580-01-089A-4 an HVACR-specific drive?
Yes. The ACH580 series is dedicated to HVACR duties, with functions such as fireman’s override, air filter monitoring, intelligent pump control, motor preheating, frost protection and a cooling compressor package built into the software.
03Which building automation protocols does ACH580-01-089A-4 support?
BACnet MS/TP, Modbus RTU and N2 are embedded as standard on the EIA-485 port. Optional plug-in adapters add BACnet/IP, Modbus TCP, PROFINET IO, EtherNet/IP and other networks.
04What enclosure ratings are available for ACH580-01-089A-4?
The standard drive is IP21 (UL Type 1). An IP55 (UL Type 12) version is available with the +B056 code for dusty or humid environments, and frames R1 to R5 can add a main disconnect switch.
05What are the cooling and fuse requirements of ACH580-01-089A-4?
The catalog gives 159 m³/h of cooling air, 1028 W of typical heat loss, a maximum noise level of 70 dBA, and recommended input fuses of 100 A gG or 110 A UL Class T.