Brand: ABB
ABB ACS880-01-430A-3 Wall-Mounted Drive 250 kW 430 A
Description
A 250 kW industrial drive on a 400 V supply
The ACS880-01-430A-3 is an ABB ACS880-01 wall-mounted single drive for 380 to 415 V supplies. Nominal output is 430 A at 250 kW and the mechanical size is frame R9. Typical jobs are centrifugal loads needing 200 to 250 kW and the biggest wall-mounted jobs: large pumps, fans and compressors. The ACS880 platform brings direct torque control, built-in Safe Torque Off and a choke for harmonic filtering, so a cabinet needs little else around the power part.
Technical specifications
| Parameter | Specification |
|---|---|
| Type designation | ACS880-01-430A-3 |
| Series | ACS880-01, wall-mounted single drive, ACS880 industrial drive platform |
| Supply voltage | 3-phase 380 to 415 V (400 V table) |
| Nominal rating | 250 kW, 430 A |
| Light-overload rating | 400 A = 200 kW |
| Heavy-duty use | 200 kW, 363 A |
| Peak current IMAX | 545 A |
| Frame size | R9 |
| IP21 height, width, depth, weight | 955 mm with cable box (680 mm without), 380 mm, 413 mm, 95 kg |
| IP55 option | 955 x 380 x 477 mm, 102 kg |
| Noise level | 70 dB(A) |
| Power loss for cabinet design | 5797 W (90% frequency, full current) |
| Air flow | 1150 m3/h |
| Brake chopper | A selectable internal option, order code +D150 |
| Minimum brake resistance | 2 ohm for 160 kW braking power |
| Sine filter type | B84143V0390S229 (rated 352 A) |
Current ratings and installation size
Two duty classes apply: light overload at 400 A and 200 kW, heavy duty at 363 A and 200 kW. Maximum output current is 545 A. Light overload suits pumps and fans, whose torque falls with speed, while heavy duty is the choice for crushers, extruders and conveyors that need high starting torque. Always size from the motor nameplate current at your voltage and check the ambient temperature and altitude against the hardware manual.
Frame R9 in IP21: height 955 mm including the cable box and 680 mm without, width 380 mm, depth 413 mm, mass 95 kg. IP55 enclosures are larger, 955 x 380 x 477 mm at 102 kg. The drive loses about 5797 W, needs 1150 m3/h of cooling air and runs at 70 dB(A).
Brake chopper, EMC filter and output filters
Dynamic braking: chopper a selectable internal option, order code +D150; resistor SAFUR200F500 (2.7 ohm, 5400 kJ, 13.5 kW continuous); minimum 2 ohm at 160 kW. The EMC filter options are +E202 (C2), +E200 (C3) and +E201 (C3 on ungrounded supplies); the base drive is C4. For long cables, submersible pumps or noise reduction, ABB lists the B84143V0390S229 sine filter (352 A, 160 kW).
Standard I/O is 6 digital inputs, 2 DIO, 2 analog inputs, 2 analog outputs and 3 relay outputs, plus STO and the RS485 link. The control unit has three slots for adapters, I/O extension, feedback and safety modules.
Related ABB products: ABB ACQ580-01-490A-4 Water Drive 250 kW 490 A, ABB ACH580-01-430A-4 HVAC AC Drive 250 kW 430 A, ABB ACQ580-01-363A-4 Water Drive 200 kW 363 A, ABB ACQ580-01-046A-4 Water Drive 22 kW 45 A, ABB ACQ580-01-145A-4 Water Drive 75 kW 145 A and ABB ACQ580-01-039A-4 Water Drive 18.5 kW 38 A.
Documents and quotation
All values above come from ABB’s ACS880 single drives catalogue 3AUA0000098111 (linked here) and the ABB product page for the ACS880-01-430A-3. To request the ACS880-01-430A-3, send Seven Star LLC your motor data and supply details; availability comes with the quotation. Confirm before ordering: plus codes, motor current, enclosure class, filters, brake resistor and derating for temperature and altitude. Other sizes are listed in AC drives, and a smaller general purpose family is on the ABB ACS580 page.
Datasheets & Documents
- Catalog ABB ACS880 single drives catalog (3AUA0000098111) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB ACS880-01-430A-3 Wall-Mounted Drive 250 kW 430 A
Answers from our engineering team on installation, compatibility and integration.
01What are the duty ratings of the ACS880-01-430A-3?
ABB lists 430 A nominal (250 kW), 400 A (200 kW) for light overload, 363 A (200 kW) for heavy duty and 545 A maximum output current.
02What size and weight is the ACS880-01-430A-3 in IP21?
It is frame R9: 955 mm high with cable entry box, 380 mm wide, 413 mm deep and 95 kg; the IP55 version is 955 x 380 x 477 mm and 102 kg.
03Does the ACS880-01-430A-3 include a brake chopper?
The brake chopper is a selectable internal option, order code +D150; the catalogue lists SAFUR200F500 (2.7 ohm) and a minimum resistance of 2 ohm.
04How much heat and cooling air does the ACS880-01-430A-3 need?
The catalogue gives 5797 W of heat dissipation, 1150 m3/h of air flow and 70 dB(A) noise.
05Which EMC filter options exist for the ACS880-01-430A-3?
The catalogue lists +E202 for C2, +E200 for C3 and +E201 for ungrounded networks; category C4 is standard on 380 to 500 V ACS880-01 drives.