Where the ACS580-01-169A-4 fits

ABB’s ACS580 catalogue lists the ACS580-01-169A-4 as a wall-mounted general purpose drive for 400 V networks. Nominal output is 169 A at 90 kW, in frame R7. It suits main pumps and blowers, or heavy conveyors. A swinging choke, EMC filter, Modbus RTU interface and dual-channel SIL 3 STO are all inside the standard drive.

Technical specifications

Parameter Specification
Type designation ACS580-01-169A-4
Series ACS580-01, wall-mounted general purpose drive
Supply voltage 3-phase 380 to 415 V (400 V table)
Nominal rating 90 kW, 169 A
Light-overload rating 161 A = 90 kW
Heavy-duty use 75 kW, 145 A (150% overload)
Maximum output current 247 A
Frame size R7
IP21 height, width, depth 880 mm incl. glandbox, 284 mm, 370 mm
IP21 weight 54 kg
IP55 / UL Type 12 variant 880 x 284 x 381 mm; 56 kg
480 V light-overload 156 A, 125 Hp
480 V heavy duty 124 A, 100 Hp
Cooling air flow 450 m3/h (265 ft3/min)
Noise at full fan speed 67 dBA
Recommended fuses 250 A gG, UL class T 225 A
Safety Safe Torque Off (SIL 3)

Current ratings, fuses and heat loss

Two duty classes apply: light overload at 161 A and 90 kW, heavy duty at 145 A and 75 kW. Maximum output current is 247 A. The overload definitions are 110% (light) and 150% (heavy duty) for one minute every ten minutes at 40 degrees C. At 440 to 480 V the ratings become 156 A / 125 Hp and 124 A / 100 Hp. Pumps and fans fit the light-overload figures, conveyors and mixers the heavy-duty ones.

Fuses: 250 A gG on the IEC side, 225 A class T for UL. The drive dissipates 1976 W (6748 BTU/h) and needs 450 m3/h of cooling air at up to 67 dBA. Frames R4 to R9 are rated to +40 degrees C in IP21 and can run to +50 degrees C with derating.

Frame R7 in IP21: height 880 mm including the glandbox, 284 mm width, 370 mm depth, 54 kg. IP55 for dusty or wet rooms is ordered with +B056: 880 x 284 x 381 mm, 56 kg.

Filters, fieldbus and options

Read ACS580-01-169A-4 as series ACS580, construction 1 (wall-mounted drive), size 169A-4 where the digits are the nominal current, and voltage code 4 for 380 to 480 V. ABB’s option list includes +K458 for FSCA-01 Modbus RTU, +K462 for FCNA-01 ControlNet, +K469 for FECA-01 EtherCAT. Category C2 applies to wall-mounted drives and cabinets to R9, while modules and R10 or R11 cabinet drives meet C3 without external filters. A brake chopper is standard only up to R3; for frame R7 braking needs an external chopper and resistor.

Related ABB products: ABB ACQ580-01-062A-4 Water Drive 30 kW 62 A, ABB ACS580-01-106A-4 AC Drive 55 kW 106 A, ABB ACQ580-01-206A-4 Water Drive 110 kW 206 A, ABB ACQ580-01-363A-4 Water Drive 200 kW 363 A, ABB ACQ580-01-490A-4 Water Drive 250 kW 490 A and ABB ACS580-01-062A-4 AC Drive 30 kW 62 A.

Source document and RFQ

The ratings, dimensions, fuses and heat loss were read from ABB’s ACS580 catalogue 3AUA0000145061 (revision G, linked) and ABB’s page for the ACS580-01-169A-4. Seven Star LLC quotes the ACS580-01-169A-4 from Muscat after receiving the motor nameplate, supply voltage and option list. Before ordering, check the exact code and options, the motor rating, braking needs and site derating in the ACS580 hardware manuals. Send the motor nameplate, supply data, control interface and fieldbus requirement for the ACS580-01-169A-4 so that the offer lists exactly the plus codes that are needed. More sizes sit in AC drives, and the ABB ACS580 page introduces the family.

Datasheets & Documents
  • PDF Catalog ABB general purpose drives ACS580 catalog 3AUA0000145061 (Rev G) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB ACS580-01-169A-4 Wall-Mounted Drive 90 kW 169 A

Answers from our engineering team on installation, compatibility and integration.

01What are the duty ratings of the ACS580-01-169A-4?
ABB lists 169 A nominal (90 kW), 161 A (90 kW) light overload, 145 A (75 kW) heavy duty and 247 A maximum output current.
02What construction is the ACS580-01-169A-4?
It is the wall-mounted ACS580-01 in frame R7, IP21 as standard and IP55 with the +B056 option.
03How much heat does the ACS580-01-169A-4 produce?
The catalogue gives 1976 W of heat dissipation, 450 m3/h of air flow and 67 dBA of noise.
04Does the ACS580-01-169A-4 include Safe Torque Off?
Yes. Safe Torque Off (SIL 3) is part of the standard drive according to the ACS580 catalogue.
05Which fieldbus options fit the ACS580-01-169A-4?
The catalogue lists FDNA-01, FPBA-01, FCAN-01, FSCA-01, FCNA-01, FECA-01, FEPL-02, FENA-11 and FENA-21 adapters; Modbus RTU is built in.