Brand:

Pfannenberg PWS 7332 230V Air/Water Heat Exchanger, 3150 W

Description

PWS 7332 230V air/water heat exchanger: decoded part number

The PWS 7332 230V is a mid-size air/water heat exchanger that removes up to 3150 W from a sealed cabinet using a cooling-water circuit. It suits drive and power-electronics panels where the heat load is too large for filterfans and where a water loop is already provided.

Decoded: PWS = side-mounted air/water heat exchanger, 7332 = 3150 W model, 230V = 230 V single-phase. The order number is 12053010055; the 115 V 60 Hz twin is 12053017055. The 7332 shares a sheet with the 1500 W PWS 7152.

Technical specifications of the PWS 7332 230V

Parameter Specification
Manufacturer / part number Pfannenberg / PWS 7332 230V
Cooling capacity (W10/A35) 3150 W at 200 l/h water flow
Supply AC 230 V 1~ ±10 %, 50 / 60 Hz
UL file number SA33060
Airflow (free flow) Internal 1670 m³/h
Noise level 54 dB(A)
Pre-fuse T 6 A
Protection IP55 towards the enclosure
Water inlet temperature +1 °C to +35 °C
Maximum operating pressure 10 bar
Water connection 13 mm hose nozzle; other connectors on request
Controller Integrated thermostat with solenoid valve and temperature monitoring with alarm contact
Setpoint range +8 °C to +50 °C, adjustable; factory setting +35 °C
Ambient temperature range +1 °C to +70 °C
Duty cycle 100 %
Housing Galvanised steel, powder coated (200 °C), RAL 7035
Heat exchanger Copper pipe with aluminium fins
Weight 21.1 kg
Dimensions (H x W x D) 950 mm x 400 mm x 190 mm

Values are from the product page for article 12053010055 and the series sheet. Rated at 10 °C inlet water and 35 °C air.

How the PWS 7332 230V works

A fan inside the unit pulls hot cabinet air across a finned copper coil, and a water flow of 200 l/h at 10 °C inlet removes the heat. At the stated conditions (W10/A35) the capacity is 3150 W, which is more than three times the capacity of the PWS 7102.

The thermostat-controlled solenoid valve opens only when the setpoint is exceeded, with the factory setting at +35 °C and an adjustable range of +8 °C to +50 °C. A temperature monitor with an alarm contact signals faults.

Airflow inside the cabinet is 1670 m³/h free flow, so the unit moves a large volume of air; leave clear paths in front of the inlet and outlet.

Fit in the system and related Pfannenberg parts

It belongs to the PWS 7000 range, which is cut-out compatible within pairs of performance classes. In practice the PWS 7152 and 7332 share a sheet, and the 7502 and 7702 carry the high end.

  • 115 V 60 Hz twin: article 12053017055
  • PWS 7152 (1500 W) 230 V: article 12051510055
  • PWS 7502 (5200 W) 230 V: article 12055010055 for larger loads
  • IP65 on request is listed for the large 7502 and 7702 models, not for this one

Selection and ordering checklist for the PWS 7332 230V

Before ordering the PWS 7332 230V, settle the following points so that the right variant is quoted:

  • Cabinet heat load below 3150 W at the real water temperature
  • Water flow of 200 l/h at up to +35 °C and 10 bar
  • 230 V 1~ supply with a T 6 A fuse
  • Space for a 950 mm tall housing, 190 mm deep
  • Inner or outer mounting

Installation, commissioning and maintenance of the PWS 7332 230V

The unit weighs about 21 kg, so lift with two persons or a hoist. Seal the cut-out with the supplied mounting seal, connect the hose nozzles to the water lines through shut-off valves, and fill and vent before starting the fan.

Check that the alarm contact is wired to the control system and test it by shutting the water off for a short time and observing the alarm.

  • Check hose clamps for leakage every six months
  • Clean the coil and check the condensate drain
  • Flush or filter the water circuit if scale is expected
  • Verify the thermostat setpoint after maintenance

Typical applications in Oman and the GCC

A 3 kW water-cooled unit is suited to variable-speed drive cabinets, soft-starter panels and rectifier cabinets in compressor houses, pumping stations and desalination plants where a chilled-water or process-cooling loop is at hand.

Because the heat leaves in the water, high ambient temperatures in the plant room do not reduce the capacity as they do for air-cooled compressor units, provided the water inlet temperature stays within +35 °C.

Variants related to the PWS 7332 230V

Models shown by the manufacturer in the PWS 7332 / 7152 sheet:

Article Model Supply
12053010055 PWS 7332 – 3150 W 230 V – this variant
12053017055 PWS 7332 115 V 60 Hz
12051510055 PWS 7152 – 1500 W 230 V
12051517055 PWS 7152 115 V 60 Hz

Information to send with an RFQ for the PWS 7332 230V

To quote the PWS 7332 230V quickly, please send:

  • Part number PWS 7332 230V and article 12053010055
  • Quantity
  • Supply voltage and frequency
  • Heat load, target temperature and ambient inside the room
  • Cooling-water inlet temperature and flow available, and water quality
  • Delivery destination and date

Site conditions in Oman for the PWS 7332 230V

Panel cooling in Oman is sized for the worst case, not the average day. Summer shade temperatures in Muscat, Sohar and the interior regularly pass 45 °C, and a cabinet standing in direct sun gains further heat through its walls. When you size the PWS 7332 230V, add the internal losses of drives, power supplies and PLCs to the solar and wall gain, and compare the total with the useful cooling capacity at your real ambient and target cabinet temperature, rather than with a nominal figure stated at milder test conditions.

Coastal sites near Duqm, Salalah or Sur also bring humidity and salt-laden dust. Keep door seals intact, route the condensate drain away from live parts, and plan routine filter and coil cleaning so that the PWS 7332 230V keeps its rated performance through the long summer season.

Documents and quotation

A product sheet for the PWS 7332 and 7152 is attached on this page, with the capacity data and article numbers.

For a quotation on the PWS 7332 230V, send the part number or article number, quantity and the delivery destination in Oman or the GCC. Seven Star LLC is an independent supplier based in Muscat and confirms availability and lead time per request.

Other Models in the Pf Pws 7000 Range

Seven Star LLC supplies models from the Pf Pws 7000 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Pfannenberg PWS 7102 230V Air/Water Heat Exchanger, 950 WEnclosure Climate ControlView details
Pfannenberg PWS 7332 230V Air/Water Heat Exchanger, 3150 WEnclosure Climate ControlYou are viewing this model
Pfannenberg PWS 7502 230V Air/Water Heat Exchanger, 5200 WEnclosure Climate ControlView details
Pfannenberg PWS 7702 400V Air/Water Heat Exchanger, 7000 WEnclosure Climate ControlView details
Datasheets & Documents
  • PDF Datasheet Pfannenberg PWS 7332 230V Product Sheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pfannenberg is the German maker of thermal management and signalling products for electrical enclosures and industry: filter fans, cooling units, air-to-water heat exchangers, chillers, heaters, sirens and beacons. Otto Pfannenberg, an electrical engineer, founded the company in Hamburg in 1954, and in 1958 he invented the filter fan to stop components in control cabinets from overheating. Pfannenberg is still family-owned and headquartered in Hamburg.

Seven Star LLC is an independent supplier in Muscat. We list Pfannenberg signalling devices and enclosure climate products for panel builders and plant engineers in Oman and the GCC.

Pfannenberg company profile

Founded 1954, Hamburg, Germany
Founder Otto Pfannenberg, electrical engineer
Headquarters Hamburg, Germany; North American headquarters in Lancaster, New York
Ownership Family-owned
Product families PF Filterfans, DTS and DTI cooling units, air-to-water heat exchangers, process chillers, enclosure heaters and thermostats, PA and DS sirens, beacons and combined signalling devices

Milestones

  • 1954: Otto Pfannenberg founds the company in Hamburg.
  • 1958: Pfannenberg invents the filter fan for control cabinets.
  • 1962: The company introduces an industrial flashing light that does not need a bulb change after activation.

Pfannenberg product series

Signalling devices include the PATROL PA X combined flashing sounders from 105 to 122 dB(A), the PYRA flashing light sounder, the PRO 10-Ex sounder for zone 2 and zone 22, and the INTENSE BR 50 modular LED signal tower.

Thermal management covers FLZ enclosure thermostats, twin thermostats, hygrostats and Peltier thermostats, FLH radiant heaters and PFH and FLH-T fan heaters, PF filter fans in several installation sizes up to 785 m3/h and the PTF roof-mounted filter fan, and DTS and DTI cooling units, including the DTI outdoor version.

Where Pfannenberg products are used

Control and drive cabinets on machines and in plant rooms, outdoor enclosures in hot and humid climates, and alarm and evacuation signalling in industrial buildings and process areas. In the Gulf, cabinet cooling and condensation control are the main reasons for specifying Pfannenberg thermal products.

Pfannenberg products we list

Family Examples
Enclosure Climate Control FLH 060 Radiant Enclosure Heater, FLH-T 600 Fan Heater with Integrated, FLZ 510 Enclosure Thermostat, FLZ 541 Twin Thermostat, FLZ 600 Hygrostat for Control Cabinets, FLZ 700 Peltier Unit Thermostat, PFH 650 Compact Fan Heater
Fire & Gas Detectors INTENSE BR 50 Modular LED Signal Tower, PA X 1-05 PATROL Flashing Sounder 105 dB(A), PA X 20-10 PATROL Flashing Sounder 122 dB(A), PA X 5-05 PATROL Flashing Sounder 107 dB(A), PRO 10-Ex Explosion-Proof Sounder 116 dB(A), PY X-MA-05 PYRA Flashing Light Sounder 101
Cooling DTI 8401P Outdoor Cooling Unit, DTS 3061 Cooling Unit, PF 22.000 DC Filterfan, PF 66.000 Filterfan, PTF 60.500 Roof-Mounted Filterfan

Ordering Pfannenberg products: what we need

Send the article number or full designation, such as PA X 1-05 or DTI 8401P. For signalling devices add the supply voltage, lens and housing colour and any required approval such as EN 54-3 or an Ex certificate. For cooling units give the cooling capacity, voltage and frequency, mounting (side or roof, internal or external) and the ambient temperature. For fans and heaters give the installation size, voltage and airflow or heating power.

Facts checked against Pfannenberg's published company history, October 2026.

FAQ

Questions about the Pfannenberg PWS 7332 230V Air/Water Heat Exchanger,

Answers from our engineering team on installation, compatibility and integration.

01What is the capacity of the PWS 7332 230V?
3150 W at W10/A35 with 200 l/h water flow.
02What size and weight does it have?
950 mm x 400 mm x 190 mm and 21.1 kg according to the product page.
03Which water conditions apply?
Inlet water from +1 °C to +35 °C at a maximum of 10 bar, connected with 13 mm hose nozzles.
04What controller does it have?
A thermostat and solenoid valve for water control, with temperature monitoring and an alarm contact.
05How loud is it?
The sheet gives 54 dB(A) for this model class.