Pfannenberg PF 43000 400V IP54 Filterfan, 223-247 m3/h
Description
PF 43000 400V IP54 filterfan: decoded article 11643021055
The PF 43000 400V IP54 is a installation size 4 high-airflow filterfan for 400 V AC from Pfannenberg, intended to move cabinet-external air through a filter mat and into an electrical enclosure. It is built into a door or side panel cut-out and removes heat by exchanging the warm enclosure air for cooler ambient air, so it only works when the surrounding air is cooler than the maximum acceptable temperature inside the cabinet.
The model name decodes as follows: PF is the filterfan family, 43000 identifies installation size 4 (the cut-out and airflow class), 400 V AC is the supply voltage and IP54 is the protection class of the filterfan face. The full order number for this exact variant is 11643021055. The PF 43000 is the high-performance version of installation size 4, giving 223 to 247 m³/h where the PF 42500 gives 125 to 160 m³/h.
Technical specifications of the PF 43000 400V IP54
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Pfannenberg / PF 43000 400V IP54 (article 11643021055) |
| Supply voltage | AC 400 V ±10 %, 50 / 60 Hz |
| Unimpeded airflow | 223 m³/h at 50 Hz, 247 m³/h at 60 Hz |
| Airflow with exhaust filter | 201 m³/h at 50 Hz, 223 m³/h at 60 Hz |
| Power consumption | 41 W at 50 Hz, 38 W at 60 Hz |
| Connection | Spring-type terminal |
| Pre-fuse | gG, 6 A |
| Protection | IP54; NEMA Type 12 |
| Filter | Standard filter mat, 88 % filtration efficiency |
| Bearing | Ball bearing |
| Ambient temperature | -40 °C to +55 °C |
| Housing | Injection-moulded thermoplastic, self-extinguishing, UL 94 V0 |
| Colour | RAL 7035 |
| Cut-out (H x W) | 223 mm x 223 mm |
| Dimensions (H x W x D) | 252 mm x 252 mm x 119 mm; installation depth 113 mm |
| Weight | 1.67 kg |
Values are from the product page for article 11643021055. The page does not give a UL file number for this variant, so UL approval is not claimed here.
How the PF 43000 400V filterfan works
It uses the same 223 mm x 223 mm cut-out as the PF 42500, so a cabinet built for the lower class can be upgraded without re-cutting. The housing is deeper at 119 mm and the unit weighs 1.67 kg, reflecting the stronger motor.
In the PF 43000 400V IP54, air enters through the louvred front cover, passes through the filter mat and is pushed into the enclosure by a single axial fan. Warm air leaves the cabinet through a second opening, usually fitted with a matching exhaust filter, so that dust cannot enter through the outlet either. The louvres are shaped to give a high airflow for the size of the housing and to keep splash water and falling debris away from the filter mat.
Because the PF 43000 400V IP54 only moves air, the achievable cooling depends on the temperature difference between the inside and the outside of the enclosure and on the pressure drop of the filters and any rainhood. A thermostat is normally used to switch the fan on at a set cabinet temperature, which saves power and extends filter life.
Fit in the system and related Pfannenberg parts
This variant is one of the few filterfans in the series fed from 400 V AC, useful where a three-phase auxiliary supply is at hand and where a 230 V line is not.
The same family covers installation sizes 1 to 6, with sibling models such as PF 11000, PF 22000, PF 32000, PF 42500, PF 43000, PF 65000 and the slim PF 67000 SL. The exhaust counterpart carries the PFA prefix and shares the cut-out, so a filterfan and an exhaust filter of the same size can be combined for forced circulation.
- Exhaust filter, grey: article 11740001055
- Exhaust filter, black: article 11740001050
- Spare filter mats, pack of 5: article 18611600032
- Thermostat: article 17121000000; hygrostat: article 17207000000
- Rainhood in stainless steel: article 18102000017
Selection and ordering checklist for the PF 43000 400V IP54
Before ordering the PF 43000 400V IP54, confirm that the following points are settled so the correct variant is quoted:
- Cabinet heat load in watts and the permitted internal temperature
- Highest outdoor or room air temperature; a filterfan only cools when ambient is below the enclosure limit
- Supply: 400 V AC three-wire supply as listed on the page; other voltages carry other article numbers
- Cut-out of 223 mm x 223 mm and the installation depth behind the panel
- Whether the extra depth of 119 mm is available inside the door or wall
Choose this class when the heat load is too high for the standard size-4 unit but a cooling unit would be excessive. Because the unit draws 41 W from 400 V, wiring a small protective device in the cabinet is reasonable.
Installation, commissioning and maintenance of the PF 43000 400V IP54
Installing the PF 43000 400V IP54 uses a cut-out in the cabinet wall and the tool-free four-corner fastening of the Pfannenberg filterfan. A poured foam seal on the frame is pressed against the panel, which keeps the stated protection class intact without a separate gasket. Mount the fan so that the airflow is from outside to inside and place the exhaust outlet as far from the inlet as practical, ideally at the opposite side and higher up, so warm air rises out of the enclosure.
Connect the PF 43000 400V IP54 supply with the fuse stated in the data table and protect the circuit as described in the manual. For commissioning, run the fan for several minutes and confirm direction of air movement at the louvres, then check the enclosure temperature under real load.
- Inspect the filter mat at each service visit and replace it when visibly loaded; spare mats come in packs of five
- Verify that the exhaust opening is clear and that cables do not obstruct the louvres
- Verify the 400 V supply and fuse before first start-up and keep the terminal cover in place
In a large drive or MCC cabinet the airflow should pass over the heat-producing parts. Place the unit near the lower front and the exhaust high at the rear or on the opposite door.
Typical applications in Oman and the GCC
Typical applications are VFD cabinets, soft-starter panels, power-distribution boards in pump houses and compressor control panels in desert installations with clean indoor air.
Across the region, filterfans are used on control panels in oil and gas facilities, power stations and substations, desalination plants and petrochemical sites, where cabinets sit in electrical rooms or outdoor kiosks. Ambient temperatures above +40 °C for much of the year, fine sand and high humidity near the coast mean that the filter mat class, the protection class and the thermal margin should be checked rather than assumed. Where outdoor ambient air can approach the allowed enclosure temperature, a cooling unit or heat exchanger is the better choice than a filterfan.
Variants and voltages in the family of the PF 43000 400V IP54
The table lists the article numbers shown by the manufacturer for the same size, so you can see which variants exist around the one requested.
| Order number | Supply | Protection |
|---|---|---|
| 11643021055 | 400 V AC | IP54 – this variant |
| 11643101055 | 230 V AC | IP54 |
| 11643151055 | 115 V AC | IP54 |
| 11643851055 | 12 V DC | IP54 |
| 11643801055 | 24 V DC | IP54 |
| 11643701055 | 48 V DC | IP54 |
| 11643023055 | 400 V AC | IP55 fluted filter |
Information to send with an RFQ for the PF 43000 400V IP54
A complete request avoids delays. Please provide:
- Part number or article number, for example PF 43000 400V IP54 / 11643021055
- Quantity and whether exhaust filters, spare filter mats, thermostat or rainhood are needed
- Supply voltage and frequency available at the cabinet
- Maximum ambient temperature and the heat load to be removed, if you want a sizing opinion
- Site conditions: indoor room, outdoor kiosk, sand, oil mist or salt air
- Delivery destination in Oman or the GCC and required date
Documents and quotation
A product sheet for the PF 43000 400V IP54 series is attached on this page, and it shows the airflow data, article numbers for every voltage, accessory article numbers and the performance curves for the size.
To receive a quotation for the PF 43000 400V IP54, send us the part number, the quantity and the delivery destination in Oman or the GCC. Seven Star LLC is an independent supplier based in Muscat and confirms lead time and availability against each request.
Other Models in the Pf Filterfan Ip54 Range
Seven Star LLC supplies models from the Pf Filterfan Ip54 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Pfannenberg PF 11000 230V IP54 Filterfan, 19-24 m3/h | Enclosure Climate Control | View details |
| Pfannenberg PF 32000 230V IP54 Filterfan, 98-108 m3/h | Enclosure Climate Control | View details |
| Pfannenberg PF 42500 24V IP54 DC Filterfan, 125 m3/h | Enclosure Climate Control | View details |
| Pfannenberg PF 43000 400V IP54 Filterfan, 223-247 m3/h | Enclosure Climate Control | You are viewing this model |
Datasheets & Documents
- Datasheet Pfannenberg PF 43000 400V IP54 Product Sheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pfannenberg is the German maker of thermal management and signalling products for electrical enclosures and industry: filter fans, cooling units, air-to-water heat exchangers, chillers, heaters, sirens and beacons. Otto Pfannenberg, an electrical engineer, founded the company in Hamburg in 1954, and in 1958 he invented the filter fan to stop components in control cabinets from overheating. Pfannenberg is still family-owned and headquartered in Hamburg.
Seven Star LLC is an independent supplier in Muscat. We list Pfannenberg signalling devices and enclosure climate products for panel builders and plant engineers in Oman and the GCC.
Pfannenberg company profile
| Founded | 1954, Hamburg, Germany |
|---|---|
| Founder | Otto Pfannenberg, electrical engineer |
| Headquarters | Hamburg, Germany; North American headquarters in Lancaster, New York |
| Ownership | Family-owned |
| Product families | PF Filterfans, DTS and DTI cooling units, air-to-water heat exchangers, process chillers, enclosure heaters and thermostats, PA and DS sirens, beacons and combined signalling devices |
Milestones
- 1954: Otto Pfannenberg founds the company in Hamburg.
- 1958: Pfannenberg invents the filter fan for control cabinets.
- 1962: The company introduces an industrial flashing light that does not need a bulb change after activation.
Pfannenberg product series
Signalling devices include the PATROL PA X combined flashing sounders from 105 to 122 dB(A), the PYRA flashing light sounder, the PRO 10-Ex sounder for zone 2 and zone 22, and the INTENSE BR 50 modular LED signal tower.
Thermal management covers FLZ enclosure thermostats, twin thermostats, hygrostats and Peltier thermostats, FLH radiant heaters and PFH and FLH-T fan heaters, PF filter fans in several installation sizes up to 785 m3/h and the PTF roof-mounted filter fan, and DTS and DTI cooling units, including the DTI outdoor version.
Where Pfannenberg products are used
Control and drive cabinets on machines and in plant rooms, outdoor enclosures in hot and humid climates, and alarm and evacuation signalling in industrial buildings and process areas. In the Gulf, cabinet cooling and condensation control are the main reasons for specifying Pfannenberg thermal products.
Pfannenberg products we list
Ordering Pfannenberg products: what we need
Send the article number or full designation, such as PA X 1-05 or DTI 8401P. For signalling devices add the supply voltage, lens and housing colour and any required approval such as EN 54-3 or an Ex certificate. For cooling units give the cooling capacity, voltage and frequency, mounting (side or roof, internal or external) and the ambient temperature. For fans and heaters give the installation size, voltage and airflow or heating power.
Facts checked against Pfannenberg's published company history, October 2026.
Browse Pfannenberg products by category: Enclosure Climate Control, Fire & Gas Detectors, Cooling.
FAQ
Questions about the Pfannenberg PF 43000 400V IP54 Filterfan, 223-247
Answers from our engineering team on installation, compatibility and integration.
01How does the PF 43000 400V IP54 differ from the PF 42500?
Both fit the same 223 mm x 223 mm cut-out, but the PF 43000 offers a higher performance class of 223 to 247 m³/h instead of about 125 to 160 m³/h, and it draws about 40 W.
02What is the airflow with an exhaust filter?
The page gives 201 m³/h at 50 Hz and 223 m³/h at 60 Hz with the exhaust filter fitted.
03What supply does it need?
This article is for 400 V AC, 50/60 Hz, with a gG 6 A pre-fuse. Other voltages exist under other article numbers.
04What depth is required behind the panel?
The installation depth is 113 mm and the housing depth is 119 mm. Check the cabinet interior for interference with busbars and cable trunking.
05Is it IP55 rated?
This article is IP54 with a standard filter. IP55 variants with a fluted filter exist, for example article 11643023055 for 400 V AC.