Brand: Pfannenberg
Pfannenberg DTS 3081 230V LAP NEMA 4X Cooling Unit, 694 W
Description
DTS 3081 230V LAP cooling unit: decoded part number
The DTS 3081 230V LAP is a compact NEMA 4/4X cooling unit with a stainless-steel 304 housing for hot spots in small enclosures and for cabinets in wash-down or outdoor situations. The LAP version carries a low-ambient package, so the unit can be used in cold climates as well as in hot ones.
Decoded: DTS = side-mount, 3081 = NEMA 4/4X compact class of about 694 W (the 3061 is the NEMA 3R/4 twin), 230V = single-phase 230 V and LAP = Low Ambient Package. The article number is 13382341178.
Technical specifications of the DTS 3081 230V LAP
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Pfannenberg / DTS 3081 230V LAP |
| Cooling capacity (EN 14511) | 694 W at A35/A35; 428 W at A35/A50 |
| Supply | 230 V AC 1~, 50 / 60 Hz |
| Power consumption (A35/A35) | 663 W |
| Current consumption | 4.1 A; starting current 10.4 A |
| Pre-fuse | T 2.8 A |
| Airflow (free flow) | Internal 325 m³/h; external 150 m³/h |
| Noise level | Below 64 dB(A) |
| Controller | Standard Controller |
| Refrigerant | R513A, 400 g |
| Ambient temperature (LAP) | -40 °C to +55 °C |
| Setpoint range | +10 °C to +40 °C, adjustable |
| Duty cycle | 100 % |
| Protection | IP56; NEMA Type 4 / 4X towards the enclosure |
| Housing | Stainless steel 304; galvanised cover |
| Connection | Pluggable, plug included |
| Dimensions (H x W x D) | 512 mm x 254 mm x 274 mm |
Values are from the product page for article 13382341178 and the series sheet. The LAP package includes a 900 W enclosure heater and a thermostat to be placed inside the enclosure.
How the DTS 3081 230V LAP works
As in other Pfannenberg cooling units, a hermetic refrigeration circuit cools the internal air, and the heat is rejected through a separate external air path. The condenser fin spacing of 3 mm and fully coated heat exchangers and tubing make the unit tolerant of heavily contaminated air, which is the reason it is described as suitable for the food-and-beverage industry and for outdoor use.
The LAP package solves the low-temperature start problem: at low ambient the heater and thermostat warm the enclosure so that the compressor and the electronics remain in their safe operating range.
The unit must be selected for the enclosure rating: the stainless 4/4X version maintains a UL-tested NEMA 4/4X seal against the enclosure, whereas the 3R/4 version is for less demanding conditions.
Fit in the system and related Pfannenberg parts
The DTS 3000 family covers 694 to 2000 W in the NEMA 3R/4 and 4/4X versions. This 694 W unit is the smallest; the DTS 3181 gives 1140 to 1235 W and the DTS 3281 1900 to 2000 W.
- Standard version without LAP: article 13382341300 (230 V)
- 115 V 60 Hz versions: 13382344300 (SC) and 13382344178 (LAP)
- NEMA 3R/4 version DTS 3061: for example 13382341355 (230 V, SC)
- The sheet lists a condensate drain for this size, so provide a drain path or hose for the water
Selection and ordering checklist for the DTS 3081 230V LAP
Before ordering the DTS 3081 230V LAP, settle the following points so that the right variant is quoted:
- Heat load; 428 W at A35/A50 is the working figure for hot sites
- Cabinet size: the sheet states suitability for enclosures of 400 mm or less in depth
- Whether LAP is needed (cold climate) or the standard version is enough
- NEMA 4/4X stainless versus NEMA 3R/4 housing
- Supply 230 V or 115 V and available drain arrangements
Installation, commissioning and maintenance of the DTS 3081 230V LAP
The housing is mounted on the outside of the cabinet through a cut-out; use stainless-steel fasteners and a proper seal where the unit sees wash-down or outdoor exposure. This size is listed with a condensate drain, so the drain path must be arranged properly.
If LAP is fitted, place the thermostat inside the enclosure away from direct airflow so it senses the average cabinet temperature, and wire the 900 W heater according to the manual.
- Rinse or brush the condenser regularly; 3 mm fin spacing resists clogging but does not eliminate it
- Check that the drain remains clear
- Inspect seals and fasteners for corrosion
- Use qualified personnel for the refrigerant circuit
Typical applications in Oman and the GCC
A NEMA 4/4X stainless unit is the choice for outdoor instrument cabinets, offshore decks, wash-down areas and corrosive atmospheres near the coast, where a painted steel unit would not last. In the Gulf the high salt content of the air makes stainless 304 attractive for cabinets near the shore.
At 694 W it cools small junction boxes, analyser cabinets and PLC panels, or hot spots within a larger enclosure. For loads above 1 kW, look to the DTS 3181 or DTS 3281.
Variants related to the DTS 3081 230V LAP
Variants shown by the manufacturer for DTS 3061 / 3081:
| Article | Type | Supply |
|---|---|---|
| 13382341178 | DTS 3081 LAP, NEMA 4/4X | 230 V – this variant |
| 13382341300 | DTS 3081 SC, NEMA 4/4X | 230 V |
| 13382344178 | DTS 3081 LAP, NEMA 4/4X | 115 V 60 Hz |
| 13382341355 | DTS 3061 SC, NEMA 3R/4 | 230 V |
Information to send with an RFQ for the DTS 3081 230V LAP
To quote the DTS 3081 230V LAP quickly, please send:
- Part number DTS 3081 230V LAP and article 13382341178
- Quantity
- Supply voltage
- Heat load and minimum / maximum ambient temperature
- Enclosure type and depth
- Delivery destination and date
Site conditions in Oman for the DTS 3081 230V LAP
Panel cooling in Oman is sized for the worst case, not the average day. Summer shade temperatures in Muscat, Sohar and the interior regularly pass 45 °C, and a cabinet standing in direct sun gains further heat through its walls. When you size the DTS 3081 230V LAP, add the internal losses of drives, power supplies and PLCs to the solar and wall gain, and compare the total with the useful cooling capacity at your real ambient and target cabinet temperature, rather than with a nominal figure stated at milder test conditions.
Coastal sites near Duqm, Salalah or Sur also bring humidity and salt-laden dust. Keep door seals intact, route the condensate drain away from live parts, and plan routine filter and coil cleaning so that the DTS 3081 230V LAP keeps its rated performance through the long summer season.
Documents and quotation
A product sheet for the DTS 3061 and 3081 series is attached on this page, with capacity data, article numbers and accessory table.
For a quotation on the DTS 3081 230V LAP, send the part number or article number, quantity and the delivery destination in Oman or the GCC. Seven Star LLC is an independent supplier based in Muscat and confirms availability and lead time per request.
Datasheets & Documents
- Datasheet Pfannenberg DTS 3081 230V LAP Product Sheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pfannenberg is the German maker of thermal management and signalling products for electrical enclosures and industry: filter fans, cooling units, air-to-water heat exchangers, chillers, heaters, sirens and beacons. Otto Pfannenberg, an electrical engineer, founded the company in Hamburg in 1954, and in 1958 he invented the filter fan to stop components in control cabinets from overheating. Pfannenberg is still family-owned and headquartered in Hamburg.
Seven Star LLC is an independent supplier in Muscat. We list Pfannenberg signalling devices and enclosure climate products for panel builders and plant engineers in Oman and the GCC.
Pfannenberg company profile
| Founded | 1954, Hamburg, Germany |
|---|---|
| Founder | Otto Pfannenberg, electrical engineer |
| Headquarters | Hamburg, Germany; North American headquarters in Lancaster, New York |
| Ownership | Family-owned |
| Product families | PF Filterfans, DTS and DTI cooling units, air-to-water heat exchangers, process chillers, enclosure heaters and thermostats, PA and DS sirens, beacons and combined signalling devices |
Milestones
- 1954: Otto Pfannenberg founds the company in Hamburg.
- 1958: Pfannenberg invents the filter fan for control cabinets.
- 1962: The company introduces an industrial flashing light that does not need a bulb change after activation.
Pfannenberg product series
Signalling devices include the PATROL PA X combined flashing sounders from 105 to 122 dB(A), the PYRA flashing light sounder, the PRO 10-Ex sounder for zone 2 and zone 22, and the INTENSE BR 50 modular LED signal tower.
Thermal management covers FLZ enclosure thermostats, twin thermostats, hygrostats and Peltier thermostats, FLH radiant heaters and PFH and FLH-T fan heaters, PF filter fans in several installation sizes up to 785 m3/h and the PTF roof-mounted filter fan, and DTS and DTI cooling units, including the DTI outdoor version.
Where Pfannenberg products are used
Control and drive cabinets on machines and in plant rooms, outdoor enclosures in hot and humid climates, and alarm and evacuation signalling in industrial buildings and process areas. In the Gulf, cabinet cooling and condensation control are the main reasons for specifying Pfannenberg thermal products.
Pfannenberg products we list
Ordering Pfannenberg products: what we need
Send the article number or full designation, such as PA X 1-05 or DTI 8401P. For signalling devices add the supply voltage, lens and housing colour and any required approval such as EN 54-3 or an Ex certificate. For cooling units give the cooling capacity, voltage and frequency, mounting (side or roof, internal or external) and the ambient temperature. For fans and heaters give the installation size, voltage and airflow or heating power.
Facts checked against Pfannenberg's published company history, October 2026.
Browse Pfannenberg products by category: Enclosure Climate Control, Fire & Gas Detectors, Cooling.
FAQ
Questions about the Pfannenberg DTS 3081 230V LAP NEMA 4X Cooling Unit,
Answers from our engineering team on installation, compatibility and integration.
01What does LAP mean in the part name?
LAP is the Low Ambient Package. It includes a 900 W enclosure heater and a thermostat to be placed inside the enclosure, so the unit can operate at ambient temperatures down to -40 °C.
02What is the cooling capacity?
694 W at A35/A35 and 428 W at A35/A50 for the 230 V version, tested to EN 14511.
03What makes the DTS 3081 different from the DTS 3061?
The 3081 is the NEMA 4/4X version with a stainless-steel 304 housing; the 3061 is the NEMA 3R/4 version of the same performance class.
04What protection class does it have?
The product page lists IP56 and the sheet describes it as maintenance-free with a 3 mm fin spacing on the condenser against contaminated ambient air.
05What are its dimensions?
The page lists 512 mm x 254 mm x 274 mm for the housing.