Brand: Pfannenberg
Pfannenberg PF 22000 24V EMC IP54 EMC Filterfan
Description
PF 22000 24V EMC IP54 filterfan: decoded article 11822801055
The PF 22000 24V EMC IP54 is a installation size 2 EMC filterfan with a 24 V DC fan from Pfannenberg, intended to move cabinet-external air through a filter mat and into an electrical enclosure. It is built into a door or side panel cut-out and removes heat by exchanging the warm enclosure air for cooler ambient air, so it only works when the surrounding air is cooler than the maximum acceptable temperature inside the cabinet.
The model name decodes as follows: PF is the filterfan family, 22000 identifies installation size 2 (the cut-out and airflow class), 24 V DC is the supply voltage and IP54 is the protection class of the filterfan face. The full order number for this exact variant is 11822801055. The EMC suffix means the louvre opening is covered by a stainless-steel screen, so the filterfan can ventilate a cabinet without a large gap in the electromagnetic shield.
Technical specifications of the PF 22000 24V EMC IP54
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Pfannenberg / PF 22000 24V EMC IP54 (article 11822801055) |
| Supply voltage | DC 24 V |
| Unimpeded airflow | 61 m³/h |
| Airflow with exhaust filter | 44 m³/h |
| Power consumption | 5 W |
| Connection | Cable, 2-core, length 310 mm |
| Pre-fuse | gG, 6 A |
| Protection | IP54; NEMA Type 12 |
| Filter | Standard filter mat, 88 % filtration efficiency |
| Bearing | Ball bearing |
| Ambient temperature | -40 °C to +55 °C |
| Housing | Injection-moulded thermoplastic, self-extinguishing, UL 94 V0 |
| Colour | RAL 7035 |
| Cut-out (H x W) | 126.5 mm x 126.5 mm |
| Dimensions (H x W x D) | 145 mm x 145 mm x 69 mm; installation depth 64 mm |
| Weight | 0.5 kg |
| EMC version | Yes, with stainless-steel EMC screen |
| UL file number | E489500 |
Values are from the product page for article 11822801055. The EMC series carries a screen grid with improved contact springs; shielding attenuation figures are not given on the page, so none are quoted.
How the PF 22000 24V EMC filterfan works
Size 2 gives 61 m³/h of free airflow and 44 m³/h with the PFA 20000 EMC exhaust filter, while the DC fan draws only 5 W.
In the PF 22000 24V EMC IP54, air enters through the louvred front cover, passes through the filter mat and is pushed into the enclosure by a single axial fan. Warm air leaves the cabinet through a second opening, usually fitted with a matching exhaust filter, so that dust cannot enter through the outlet either. The louvres are shaped to give a high airflow for the size of the housing and to keep splash water and falling debris away from the filter mat.
Because the PF 22000 24V EMC IP54 only moves air, the achievable cooling depends on the temperature difference between the inside and the outside of the enclosure and on the pressure drop of the filters and any rainhood. A thermostat is normally used to switch the fan on at a set cabinet temperature, which saves power and extends filter life.
Fit in the system and related Pfannenberg parts
Contact between the screen grid and the cabinet panel is improved over earlier designs by new contact springs, which supports a stable shield even after many filter replacements.
The same family covers installation sizes 1 to 6, with sibling models such as PF 11000, PF 22000, PF 32000, PF 42500, PF 43000, PF 65000 and the slim PF 67000 SL. The exhaust counterpart carries the PFA prefix and shares the cut-out, so a filterfan and an exhaust filter of the same size can be combined for forced circulation.
- EMC exhaust filter: article 11920001055
- Spare filter mats, pack of 5: article 18611600030
- Thermostat: article 17121000000; hygrostat: article 17207000000
- Rainhood in stainless steel: article 18102000014
Selection and ordering checklist for the PF 22000 24V EMC IP54
Before ordering the PF 22000 24V EMC IP54, confirm that the following points are settled so the correct variant is quoted:
- Cabinet heat load in watts and the permitted internal temperature
- Highest outdoor or room air temperature; a filterfan only cools when ambient is below the enclosure limit
- Supply: 24 V DC; other voltages carry other article numbers
- Cut-out of 126.5 mm x 126.5 mm and the installation depth behind the panel
- Whether EMC screening of the opening is actually required by the installation standard or the equipment
Choose an EMC version where the panel is part of a screened system, for example cabinets that hold sensitive measuring, analyser or communication equipment next to drives and frequency converters.
Installation, commissioning and maintenance of the PF 22000 24V EMC IP54
Installing the PF 22000 24V EMC IP54 uses a cut-out in the cabinet wall and the tool-free four-corner fastening of the Pfannenberg filterfan. A poured foam seal on the frame is pressed against the panel, which keeps the stated protection class intact without a separate gasket. Mount the fan so that the airflow is from outside to inside and place the exhaust outlet as far from the inlet as practical, ideally at the opposite side and higher up, so warm air rises out of the enclosure.
Connect the PF 22000 24V EMC IP54 supply with the fuse stated in the data table and protect the circuit as described in the manual. For commissioning, run the fan for several minutes and confirm direction of air movement at the louvres, then check the enclosure temperature under real load.
- Inspect the filter mat at each service visit and replace it when visibly loaded; spare mats come in packs of five
- Verify that the exhaust opening is clear and that cables do not obstruct the louvres
- Check that the screen grid still makes metallic contact all around the cut-out after painting or repeated filter changes
The 24 V DC supply is usually taken from the same supply as the control electronics. Verify that the supply and its wiring are suitable for the small fan load and for the fan inrush.
Typical applications in Oman and the GCC
Typical uses are instrument cubicles, analyser shelter panels and compact control stations at oil and gas and water facilities with high emission from nearby variable-speed drives.
Across the region, filterfans are used on control panels in oil and gas facilities, power stations and substations, desalination plants and petrochemical sites, where cabinets sit in electrical rooms or outdoor kiosks. Ambient temperatures above +40 °C for much of the year, fine sand and high humidity near the coast mean that the filter mat class, the protection class and the thermal margin should be checked rather than assumed. Where outdoor ambient air can approach the allowed enclosure temperature, a cooling unit or heat exchanger is the better choice than a filterfan.
Variants and voltages in the family of the PF 22000 24V EMC IP54
The table lists the article numbers shown by the manufacturer for the same size, so you can see which variants exist around the one requested.
| Order number | Supply | Protection |
|---|---|---|
| 11822101055 | 230 V AC | IP54 |
| 11822151055 | 115 V AC | IP54 |
| 11822851055 | 12 V DC | IP54 |
| 11822801055 | 24 V DC | IP54 – this variant |
| 11822701055 | 48 V DC | IP54 |
| 11822803055 | 24 V DC | IP55 |
Information to send with an RFQ for the PF 22000 24V EMC IP54
A complete request avoids delays. Please provide:
- Part number or article number, for example PF 22000 24V EMC IP54 / 11822801055
- Quantity and whether exhaust filters, spare filter mats, thermostat or rainhood are needed
- Supply voltage and frequency available at the cabinet
- Maximum ambient temperature and the heat load to be removed, if you want a sizing opinion
- Site conditions: indoor room, outdoor kiosk, sand, oil mist or salt air
- Delivery destination in Oman or the GCC and required date
Documents and quotation
A product sheet for the PF 22000 24V EMC IP54 series is attached on this page, and it shows the airflow data, article numbers for every voltage, accessory article numbers and the performance curves for the size.
To receive a quotation for the PF 22000 24V EMC IP54, send us the part number, the quantity and the delivery destination in Oman or the GCC. Seven Star LLC is an independent supplier based in Muscat and confirms lead time and availability against each request.
Datasheets & Documents
- Datasheet Pfannenberg PF 22000 24V EMC IP54 Product Sheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pfannenberg is the German maker of thermal management and signalling products for electrical enclosures and industry: filter fans, cooling units, air-to-water heat exchangers, chillers, heaters, sirens and beacons. Otto Pfannenberg, an electrical engineer, founded the company in Hamburg in 1954, and in 1958 he invented the filter fan to stop components in control cabinets from overheating. Pfannenberg is still family-owned and headquartered in Hamburg.
Seven Star LLC is an independent supplier in Muscat. We list Pfannenberg signalling devices and enclosure climate products for panel builders and plant engineers in Oman and the GCC.
Pfannenberg company profile
| Founded | 1954, Hamburg, Germany |
|---|---|
| Founder | Otto Pfannenberg, electrical engineer |
| Headquarters | Hamburg, Germany; North American headquarters in Lancaster, New York |
| Ownership | Family-owned |
| Product families | PF Filterfans, DTS and DTI cooling units, air-to-water heat exchangers, process chillers, enclosure heaters and thermostats, PA and DS sirens, beacons and combined signalling devices |
Milestones
- 1954: Otto Pfannenberg founds the company in Hamburg.
- 1958: Pfannenberg invents the filter fan for control cabinets.
- 1962: The company introduces an industrial flashing light that does not need a bulb change after activation.
Pfannenberg product series
Signalling devices include the PATROL PA X combined flashing sounders from 105 to 122 dB(A), the PYRA flashing light sounder, the PRO 10-Ex sounder for zone 2 and zone 22, and the INTENSE BR 50 modular LED signal tower.
Thermal management covers FLZ enclosure thermostats, twin thermostats, hygrostats and Peltier thermostats, FLH radiant heaters and PFH and FLH-T fan heaters, PF filter fans in several installation sizes up to 785 m3/h and the PTF roof-mounted filter fan, and DTS and DTI cooling units, including the DTI outdoor version.
Where Pfannenberg products are used
Control and drive cabinets on machines and in plant rooms, outdoor enclosures in hot and humid climates, and alarm and evacuation signalling in industrial buildings and process areas. In the Gulf, cabinet cooling and condensation control are the main reasons for specifying Pfannenberg thermal products.
Pfannenberg products we list
Ordering Pfannenberg products: what we need
Send the article number or full designation, such as PA X 1-05 or DTI 8401P. For signalling devices add the supply voltage, lens and housing colour and any required approval such as EN 54-3 or an Ex certificate. For cooling units give the cooling capacity, voltage and frequency, mounting (side or roof, internal or external) and the ambient temperature. For fans and heaters give the installation size, voltage and airflow or heating power.
Facts checked against Pfannenberg's published company history, October 2026.
Browse Pfannenberg products by category: Enclosure Climate Control, Fire & Gas Detectors, Cooling.
FAQ
Questions about the Pfannenberg PF 22000 24V EMC IP54 EMC Filterfan
Answers from our engineering team on installation, compatibility and integration.
01What does EMC mean on the PF 22000 24V EMC IP54?
The filterfan is fitted with a stainless-steel EMC screen so that the ventilation opening does not weaken the electromagnetic shielding of the cabinet.
02What is the airflow?
The page gives 61 m³/h free flow and 44 m³/h with the exhaust filter. Because the EMC grid adds some restriction, use the lower value for design.
03How is it connected?
It has a 2-core cable of 310 mm length. The fan runs on 24 V DC and the page lists a power consumption of 5 W.
04What cut-out size is used?
The cut-out is 126.5 mm x 126.5 mm, and the installation depth is 64 mm.
05Does it have an IP55 version?
Yes, the EMC series has IP55 versions, for example article 11822803055 for 24 V DC, with a fluted filter.