- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Industrial Computers
- Servo Drives
- HMI Displays
- Motor Soft Starters
- Isolator & Barrier
- Pneumatic Cylinders
- Automation Software
- Machine Vision
- Robotics
Brand: JUMO
JUMO MIDAS DR 401009 Pressure Transmitter for Control Cabinets
Description
A DIN-rail pressure transmitter that snaps into the control cabinet
The JUMO MIDAS DR (type 401009) is a pressure transmitter built to be installed directly inside a control cabinet. It measures relative (gauge) pressure in liquid or gaseous media using the thick-film strain gauge principle on an aluminium-oxide ceramic (Al2O3) base, and converts the pressure to a standard electrical signal. The housing is stainless steel, it snaps onto a 35 mm DIN rail, and the medium connects through a pluggable DN6 hose gland or a Rp 1/8 internal thread. Gauge ranges run from 0 to 1.6 bar up to 0 to 16 bar and include compound ranges from -1 bar, with a choice of 2-wire 4 to 20 mA or 3-wire voltage outputs. At roughly 100 g and with a 4-pole screw terminal block, it suits air, water and inert gas monitoring in panels.
Technical specifications
| Parameter | Specification |
|---|---|
| Type | 401009 JUMO MIDAS DR pressure transmitter for control cabinet |
| Measuring principle | Thick-film strain gauge on Al2O3 ceramic (96 %), gauge (relative) pressure |
| Gauge ranges | 0 to 1.6, 2.5, 4, 6, 10 and 16 bar; -1 to 0.6, 1.5, 3, 5, 9 and 15 bar; special range on request |
| Overload and burst | Overload 3 x full scale; burst pressure 5 x full scale (0 to 16 bar range) |
| Outputs | 4 to 20 mA 2-wire; 0.5 to 4.5 V ratiometric 3-wire; 0 to 10 V; 1 to 5 V; 1 to 6 V |
| Supply | DC 10 to 30 V (current output and 1 to 5/6 V); DC 11.5 to 30 V (0 to 10 V); DC 5 V ±0.5 V (0.5 to 4.5 V); about 25 mA |
| Burden | Current output (UB – 10 V)/0.02 A; 0.5 to 4.5 V 20 kΩ; 1 to 6 V and 0 to 10 V 10 kΩ |
| Overall error | Below 1.5 % of full scale over -20 to +80 °C |
| Zero offset | 0.3 %; thermal hysteresis 0.8 % within compensated range; long-term stability 1 % per year |
| Step response | 3 ms for current output; 10 ms for voltage output |
| Process connection | Code 383 pluggable gland for 6 x 4 mm hose (DN6); code 547 Rp 1/8 internal |
| Wetted parts | Stainless steel 1.4305, Al2O3 96 %, FPM seal; brass (CuZn) gland |
| Temperature | Ambient -20 to +80 °C; medium -15 to +60 °C; storage -40 to +80 °C |
| Protection and EMC | IP40; DIN EN 61326 emission class B, industrial immunity; shock 100 g / 1 ms; vibration 20 g, 15 to 2000 Hz |
| Electrical connection | 4-pole screw terminal block, 5 mm pitch; 0.2 to 2.5 mm² flexible; strip 8 mm |
| Mounting and weight | DIN rail 35 mm to DIN EN 60715; approx. 100 g; any orientation |
| Approvals | EAC (TR TS 020/2011) |
Order code and options
The order code is 401009 / extension – range – output – connection – housing – seal – electrical connection / extra codes. Extension 000 is standard and 999 a special version. Range codes are 455 (0 to 1.6 bar), 456 (2.5 bar), 457 (4 bar), 458 (6 bar), 459 (10 bar) and 460 (16 bar), or 479 to 484 for -1 to 0.6, 1.5, 3, 5, 9 and 15 bar. Output codes are 405 (4 to 20 mA), 412 (0.5 to 4.5 V), 415 (0 to 10 V), 418 (1 to 5 V) and 420 (1 to 6 V). Connection code 383 is the hose gland and 547 the Rp 1/8 thread, housing 20 is stainless steel, seal 601 is FPM and electrical connection 06 is the terminal block. The order example is 401009/000-459-405-383-20-601-06/000.
Installation and typical applications
Because the unit is rated IP40, it belongs inside a cabinet or enclosure, not at a wet process point; route a 6 x 4 mm hose or tube from the measuring point to the pluggable gland. The compound ranges with a negative lower limit are only suitable for negative gauge pressure down to -0.95 bar when fitted with the hose gland, code 383. The wetted parts are stainless steel, ceramic and FPM, and the buyer should always confirm compatibility with the medium. Overload and burst values can differ depending on the process connection and tubing used. Supply voltage affects the output slightly, at 0.02 % per volt around 24 V, and voltage outputs should be wired in 3-wire form with a common ground.
A cabinet-mounted transmitter saves a field instrument and long impulse lines when the pressure source is already near the panel. Typical uses are compressed air supply monitoring, filter differential checks with two units, pump discharge and suction pressure on skids, hydraulic and lubrication circuits, cooling water and boiler feed monitoring. The 4 to 20 mA version suits long cable runs to PLCs and recorders, while the 0.5 to 4.5 V ratiometric output is meant for controllers that share the same 5 V reference. Browse the pressure instrumentation category for other transmitters and switches.
An enquiry should list the pressure range, whether a vacuum range is needed, the output signal and the supply voltage available in the cabinet. State the medium, which must be compatible with ceramic, stainless steel and FPM, and its temperature within -15 to +60 °C. Mention the hose size so that we can select the DN6 pluggable gland or the Rp 1/8 thread. The EAC certificate applies to this type.
Typical examples are a compressed air receiver feeding a pneumatic panel, a pump discharge line near the switchboard and a closed cooling circuit with a short impulse tube. The small 100 g body keeps rail space low.
Documents and quotation
The hosted document is JUMO data sheet 401009 (3 pages, English). Confirm range, output and connection codes before ordering. Seven Star LLC is an independent supplier in Muscat; send the medium and range for a quotation.
Datasheets & Documents
- Datasheet JUMO 401009 data sheet 401009 (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.
Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.
JUMO company profile
| Established | 1948, Fulda, Germany, by Moritz Kurt Juchheim |
|---|---|
| First products | Glass and contact thermometers; platinum glass sensors from 1966 |
| Ownership | Family-owned; renamed JUMO GmbH & Co. KG in 2003 |
| Product families | RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments |
Milestones
- 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
- 1966: Platinum glass temperature sensors are added.
- 2003: The parent company is renamed JUMO GmbH & Co. KG.
JUMO products we list
| Family | Models | Typical use |
|---|---|---|
| RTD and thermocouple probes | 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp | Temperature measurement in pipes, vessels, machines, HVAC and food plants |
| Thermowells and inserts | 909710 thermowells, 909740 measuring inserts | Protecting sensors and replacing them without opening the process |
| Temperature transmitters | dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch | Converting sensor signals to 4-20 mA, HART or IO-Link |
| Pressure and level | dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 | Pressure in process, hydraulic and OEM systems; tank and well level |
| Controllers, limiters and recorders | DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T | Furnace, oven and process control, over-temperature protection and recording |
| Liquid analysis and flow | AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 | pH, conductivity, oxygen and turbidity in water treatment; liquid flow |
Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.
Where JUMO products are used
In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.
Ordering JUMO products: what we need
Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.
Facts checked against JUMO's company history, October 2026.
Browse JUMO products by category: Temperature Instrumentation, Pressure Instrumentation, Liquid Analysis Sensors, Controllers & Data Acquisition, Level Transmitter.
Related products
Frequently Asked Questions
Relative (gauge) pressure in liquids or gases, using a ceramic thick-film strain gauge sensor.
4 to 20 mA 2-wire, 0.5 to 4.5 V ratiometric, 0 to 10 V, 1 to 5 V and 1 to 6 V.
0 to 1.6 up to 16 bar, compound ranges from -1 bar, and special ranges on request.
Inside a control cabinet on a 35 mm DIN rail, with a hose or Rp 1/8 process connection; the rating is IP40.
An overall error below 1.5 % of full scale over -20 to +80 °C.

Reviews
There are no reviews yet.