LV434020: PowerTag M250 wireless energy sensor for 250 A breakers

The LV434020 is a Schneider Electric PowerLogic PowerTag M250 energy sensor, a wireless three-pole current and voltage sensing device that bolts onto the bottom terminals of a circuit breaker in a switchboard. It is the 250 A member of the PowerTag Monoconnect family and reports its measurements over radio rather than over a wired meter bus.

The datasheet describes the form factor as Monoconnect, mounted by bolting on, with the mounting location at the bottom of the breaker and the mounting support listed as on circuit breaker. Because the sensor is installed in the power path, its measured current range, basic current and saturation current all depend on the 250 A size: the basic current Ib is 40 A, the starting current is 160 mA and the saturation current is 500 A.

LV434020 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / LV434020
Range / product name PowerLogic / PowerTag M250
Product type Energy sensor
Poles 3P
Maximum current [Imax] 250 A
Basic current [Ib] 40 A
Starting current 160 mA
Saturation current 500 A
Permanent maximum [Imp] 1.2 x In
Form factor / mounting Monoconnect; bolt-on, on circuit breaker, bottom of breaker
Connection pitch 35 mm
Tightening torque 10 N.m
Radio link IEEE 802.15.4, 2.4 to 2.4835 GHz, emission power 10 mW
Supply voltage 230 V AC ±20 % phase-neutral; 400 V AC ±20 % between phases
Maximum power consumption 3.7 VA
Network frequency 50 Hz; 60 Hz
Product destination Switchboard
Dimensions H × W × D 57 × 105 × 86 mm
Net weight 250 g
Colour Dark grey (RAL 7016)
Standards IEC 61557-12, IEC 61010-1, ETSI EN 301 489-1, IEC 61010-2-030, IEC 61326-1, ETSI EN 300 328
Certifications IEC, DNV Marine, CE
IP / IK protection IP20; IK07
Operating / storage temperature -25 to 70 °C / -50 to 85 °C
Relative humidity 0–95 % at 55 °C
Overvoltage / measurement category IV (IEC 61010-1) / Category III (IEC 61010-2-030)

Breakers and gateways compatible with the LV434020

The sensor is sized for the breakers listed in the datasheet range compatibility: ComPacT NSX NSX100, ComPacT NSX NSX250, Compact NS100, Compact NS250, TeSys GV5, TeSys GV7, EasyPact CVS100, EasyPact CVS160, EasyPact CVS250. Choosing the sensor means choosing the breaker frame first, because the sensor bolts straight onto it.

Data leaves the sensor by radio to a concentrator. The datasheet lists these compatible gateways: EcoStruxure Panel Server Entry, EcoStruxure Panel Server Universal, EcoStruxure Panel Server Advanced, Harmony Hub, Acti9 Smartlink SI B, Acti9 Smartlink SI D, Acti9 PowerTag Link, Acti9 PowerTag Link HD. One gateway can serve many sensors in the same switchboard, so the radio link replaces the individual wiring of a metering loop.

LV434020 against the other Monoconnect sensor in this group

Two sizes of PowerTag Monoconnect are in this catalogue group: the LV434020 for 250 A and the LV434022 for 630 A. The comparison below shows how the datasheet ratings and physical size scale between them.

Item LV434020 LV434022
Maximum current 250 A 630 A
Basic current Ib 40 A 100 A
Starting current 160 mA 400 mA
Saturation current 500 A 1260 A
Connection pitch 35 mm 45 mm
Tightening torque 10 N.m 50 N.m
Dimensions H x W x D (mm) 57 x 105 x 86 91 x 140 x 110
Net weight 250 g 800 g

The larger sensor pairs with the larger breaker frames and needs more torque and more space; the radio, supply and accuracy data are the same.

Installation, torque and radio considerations for the LV434020

The connection pitch is 35 mm and the bolts are tightened to 10 N.m. That figure is high enough that a calibrated wrench is the right tool, and the breaker terminals and lugs must be reassembled to the breaker maker’s instructions after the sensor is fitted. The housing is 57 mm high, 105 mm wide and 86 mm deep and weighs 250 g.

The radio link works at 2.4 GHz with a transmission time of less than 5 ms and an emission power of 10 mW, to IEEE 802.15.4. Metal enclosures attenuate radio, so the gateway should be in the same compartment or in a position with a clear radio path. The datasheet gives the supply as 230 V AC phase to neutral or 400 V AC between phases, with a maximum power consumption of 3.7 VA.

Using the LV434020 in Oman and the GCC

Energy monitoring is increasingly asked for in commercial buildings, data rooms, water and wastewater plants and industrial utility switchboards in Oman and the GCC, where cooling load makes electricity a major running cost. A 250 A sensor is typically placed on a main incomer or a large feeder to a chiller, pump or sub-board.

The datasheet gives an operating range of -25 to 70 °C, a storage range of -50 to 85 °C and humidity up to 95 % at 55 °C, with IP20 protection. Inside a switchboard in a hot plant room, the real temperature near the breaker lugs at full load is what to check against these limits.

Selection checklist and RFQ details for the LV434020

  • Breaker model and frame: the sensor must match one of the ranges in the compatibility list for the 250 A size
  • Number of sensors and the gateway or concentrator that will collect them
  • Load current profile against the measured range of 8–250 A and the starting current of 160 mA
  • Panel space for a sensor 57 mm high, 105 mm wide and 86 mm deep, and the clearance at the breaker terminals
  • Radio path from the sensor to the gateway inside the metal enclosure
  • Supply configuration: 230 V phase-neutral or 400 V between phases

Please include the following in an enquiry:

  • Part number LV434020 and quantity
  • Breaker type and rating the sensor will be fitted to
  • Gateway or software platform in use
  • Delivery location and required date

Measurement functions and accuracy of the LV434020

The LV434020 measures active and reactive energy, active, reactive and apparent power, current, voltage and power factor, and the datasheet states accuracy classes to IEC 61557-12 at 25 °C. The current range measured is 8–250 A, and active power is covered from 88 W–416 kW, which sets the span of loads the sensor can resolve on a 250 A feeder.

Quantity Accuracy class (IEC 61557-12)
Active energy Class 1
Reactive energy Class 2
Active power Class 1
Reactive power Class 2
Apparent power Class 2
Current Class 1
Voltage Class 0.5
Power factor Class 1

Voltage is measured between phases from 320 to 480 V and between phase and neutral from 184 to 276 V, frequency from 45 to 65 Hz. The sensor also detects voltage loss with the measured current at the moment of loss, which is useful for diagnosing nuisance outages. The datasheet lists energy management, overload alarm, power factor, load monitoring and circuit monitoring as the product-specific applications.

Documents and quotation

The Schneider Electric manufacturer datasheet for the LV434020 is attached on this page as a PDF. It is the reference for every rating quoted above, and it is worth checking the revision against your project documents before an order is placed. The accuracy classes, compatibility lists and environmental data are all in it.

Seven Star LLC is an independent supplier in Muscat that serves buyers in Oman and the GCC. Send the part number LV434020, the quantity and the delivery site, and we will reply with a quotation and the availability we can confirm.

Datasheets & Documents
  • PDF Datasheet Schneider Electric LV434020 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric LV434020 PowerTag 250 A 3P

Answers from our engineering team on installation, compatibility and integration.

01Which breakers is the LV434020 compatible with?
The datasheet lists ComPacT NSX NSX100, ComPacT NSX NSX250, Compact NS100, Compact NS250, TeSys GV5, TeSys GV7, EasyPact CVS100, EasyPact CVS160, EasyPact CVS250.
02What does the LV434020 measure?
Active and reactive energy, active, reactive and apparent power, current, voltage and power factor, with accuracy classes to IEC 61557-12.
03How does the LV434020 communicate?
By radio at 2.4 to 2.4835 GHz to IEEE 802.15.4, to a concentrator such as EcoStruxure Panel Server Entry, EcoStruxure Panel Server Universal, EcoStruxure Panel Server Advanced or others listed in the datasheet.
04What is the maximum current and size of the LV434020?
Maximum current is 250 A. The housing is 57 mm high, 105 mm wide and 86 mm deep and weighs 250 g.
05How is the LV434020 mounted?
It is a Monoconnect sensor that bolts onto the circuit breaker at the bottom, with a 35 mm pitch and a tightening torque of 10 N.m.