Schneider Electric PowerLogic PM5560 Power Meter

Description

Overview

The Schneider Electric PowerLogic PM5560 is a high-accuracy multifunction power meter designed for revenue-grade energy monitoring, power quality analysis, and sub-metering in commercial and industrial electrical networks. It provides facility engineers with detailed visibility into voltage, current, power, harmonics, and energy consumption at a single measurement point.

Working closely with plant engineers in the region, Seven Star LLC proudly supplies the Schneider Electric PowerLogic PM5560 across the Sultanate of Oman and the wider GCC. Every unit is supplied with manufacturer documentation and local technical backing, giving procurement teams in Muscat, Sohar, and Salalah a formal quotation and support with selection. Seven Star LLC has a dedicated instrumentation and controls division that provides technical support with selection and specification for the Schneider Electric PowerLogic PM5560 and the wider Schneider Electric portfolio.

Operating Principle

The PM5560 samples voltage and current waveforms on each monitored phase at high resolution, computing true RMS values, power factor, and harmonic content up to the 63rd harmonic in real time. Its Class 0.2S accuracy class makes it suitable for billing-grade energy measurement, tenant sub-metering, and utility interface verification.

Measured data is continuously logged to onboard non-volatile memory and made available over Modbus RTU or Ethernet to a building management system, SCADA platform, or Schneider Electric’s EcoStruxure Power Monitoring Expert software. Configurable alarm thresholds on voltage, current, and power quality parameters allow the PM5560 to flag abnormal conditions before they cause equipment damage or unplanned downtime.

Engineering Design of the Schneider Electric PowerLogic PM5560

The Schneider Electric PowerLogic PM5560 is built into a panel-mount enclosure with a bright graphical display for local readout of key parameters, and rear terminal blocks for voltage and current transformer connections. The unit is designed for installation on switchboard doors or dedicated metering panels within low-voltage distribution assemblies.

Multiple communication ports, including Ethernet and RS-485 Modbus RTU, allow the PM5560 to integrate into existing building or plant networks alongside other PowerLogic meters and third-party devices. Onboard digital I/O (4 digital inputs and 2 digital outputs) and support for Modbus TCP, BACnet/IP and DNP3 over Ethernet serve more complex metering architectures.

Key Features

The Schneider Electric PowerLogic PM5560 is engineered to deliver dependable performance in demanding industrial and commercial environments. Key features include:

  • Class 0.2S revenue-grade accuracy suitable for billing and tenant sub-metering applications.
  • Power quality analysis including harmonic measurement up to the 63rd harmonic.
  • Onboard data logging with configurable alarm thresholds for early fault detection.
  • Ethernet and RS-485 Modbus RTU connectivity for SCADA and building management integration.
  • Bright graphical local display for on-site readout without a laptop or software.
  • Compatibility with EcoStruxure Power Monitoring Expert for enterprise-wide energy analytics.
  • Panel-mount form factor suited to switchboard door and metering panel installation.
  • Onboard 4 digital inputs, 2 digital outputs and 52 alarms for control and event monitoring.

Applications

The Schneider Electric PowerLogic PM5560 is specified in commercial towers, data centers, hospitals, and industrial plants across Oman and the GCC where accurate energy accounting, tenant billing, or power quality diagnostics are required. It is frequently paired with EcoStruxure Power Monitoring Expert to give facility managers a plant-wide view of energy consumption trends.

With fast quotation turnaround and technical support, Seven Star LLC distributes the Schneider Electric PowerLogic PM5560 to system integrators, panel builders, and EPC contractors throughout Oman and the GCC, supporting district cooling plants, desalination facilities, oil and gas installations, commercial towers, hospitality developments, and the Sohar and Salalah economic zones. Lead time is confirmed at quotation, and Seven Star LLC’s engineering team assists with product selection, coordination with the wider Schneider Electric ecosystem, and answers to technical enquiries.

Technical Specifications

The table below summarizes the key technical specifications of the Schneider Electric PowerLogic PM5560 for engineering reference and system design.

Parameter Specification
Model PowerLogic PM5560
Type Multifunction power quality meter
Accuracy Class Class 0.2S for active energy (IEC 62053-22); reactive energy ±1%
Communication 2 Ethernet ports (10/100 Mbit/s, daisy chain; Modbus TCP, BACnet/IP, DNP3) and 1 RS-485 port (Modbus RTU/ASCII)
Measurements Voltage, current, frequency, power factor, active and reactive power, energy, harmonics up to the 63rd
Display Backlit LCD, 128 x 128 pixels
Mounting Flush mount (panel/switchboard door)
Software Compatibility EcoStruxure Power Monitoring Expert
Supply Voltage 90 to 528 VAC (45 to 65 Hz); 100 to 300 VDC
Digital I/O 4 digital inputs, 2 digital outputs
Alarms 52 alarms
Data Logging Memory 1.1 MB (data, alarm, event and maintenance logs with time stamping)
Sampling Rate 128 samples per cycle
Tariffs 8 (multi-tariff)
Operating Temperature -25 to 70 °C (storage -40 to 85 °C)
Ingress Protection IP54 display, IP30 rear
Dimensions 96 mm width × 96 mm height × 72 mm depth; weight 450 g
Standards IEC 61557-12, IEC 62053-22, IEC 62053-24, EN 50470-1/-3, ANSI C12.20

Metering and Power Quality Functions

The PM5560 belongs to the PowerLogic PM5000 range and measures voltage, current, frequency, power factor, active and reactive power and energy, with harmonic analysis up to the 63rd harmonic. It samples at 128 samples per cycle and supports 3P+N, 3P and 1P+N network types, with 1A or 5A rated current inputs.

Schneider Electric specifies Class 0.2S for active energy under IEC 62053-22, with typical accuracy of ±0.1% for voltage, ±0.1% for current and ±0.2% for active power. Eight tariffs support multi-tariff metering, and the device is listed for WAGES metering and power monitoring. Refer to the Schneider Electric PM5560 datasheet for the full list of power quality functions.

Communications, Inputs and Logging

The PM5560 provides two Ethernet ports with daisy chain support, carrying Modbus TCP/IP, BACnet/IP and DNP3, plus an RS-485 port for Modbus RTU and ASCII. A built-in web server offers predefined diagnostic pages and real-time data viewing, and alarm notification by e-mail, SNTP time synchronization and SNMP traps are listed.

Four digital inputs and two digital outputs are available onboard, alongside 52 alarms. A 1.1 MB memory holds data, alarm, event and maintenance logs with time stamping, together with min/max values of instantaneous measurements. The meter accepts 90 to 528 VAC or 100 to 300 VDC supply and mounts flush in a 96 × 96 mm cut-out.

Why Choose Seven Star LLC

Seven Star LLC supplies the Schneider Electric PowerLogic PM5560 and the broader Schneider Electric catalogue to industrial, commercial and utility customers across Oman and the GCC. Supply is on request, with lead time confirmed at quotation, and our technical staff can support product selection, panel integration and commissioning on request.

Get a Quote

To request a formal quotation for the Schneider Electric PowerLogic PM5560, contact the Seven Star LLC instrumentation and controls division directly. Seven Star LLC supplies on request across Oman and the GCC, offers downloadable technical datasheets for engineering review, and provides pre-sales application support for panel builders and end users alike. With engineering support in Muscat, Seven Star LLC supplies the Schneider Electric PowerLogic PM5560 with technical documentation and responsive local support – reach out today to confirm availability, lead time, and pricing for your project.

Because the Schneider Electric PowerLogic PM5560 supports both revenue-grade billing metering and general power quality analysis in one device, facility owners across Oman can consolidate what would otherwise require two separate meters at critical distribution points. Seven Star LLC’s metering specialists can advise on CT and PT sizing to ensure the PM5560 is correctly matched to the monitored circuit before commissioning.

Related Products

Datasheets & Documents
  • PDF Datasheet Schneider Electric PowerLogic PM5560 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Circuit breakers make up the largest part of our Schneider Electric listing, from Acti9 modular devices through ComPacT NSX molded case breakers to MasterPact air circuit breakers. Schneider Electric, which dates from 1836 and is headquartered in Rueil-Malmaison, France, is equally established in drives, PLCs and power metering.

Seven Star LLC is an independent supplier of Schneider Electric circuit breakers, Altivar drives, Modicon I/O, power meters, soft starters and dry-type transformers to panel builders and plants in Oman and the GCC.

Schneider Electric product families on this page

Low voltage protection covers Acti9 miniature breakers and their communicating system, ComPacT NSX and PowerPacT H-frame molded case breakers and MasterPact NW air circuit breakers. Altivar 320 variable speed drives appear in several ratings, for example the ATV320U22N4C at 2.2 kW and the ATV320U75N4B at 7.5 kW. Automation is represented by Modicon TM3 expansion modules such as the TM3TM thermocouple input module. Metering includes the EasyLogic PM2000 power meter and iEM2000 modular energy meters. Trihal cast resin transformers and Spacial enclosure accessories complete the electrical distribution side.

Where Schneider Electric equipment is used

Main and distribution switchboards in buildings, utilities and industrial plants carry the breakers and meters. Altivar drives run pumps, fans, conveyors and packaging machines. Modicon controllers with TM3 I/O are common in machine builders' panels, and Trihal transformers serve indoor substations where a dry-type unit is specified.

Ordering Schneider Electric parts: what we need

The commercial reference printed on the product or its carton is the fastest route. For breakers without a reference send rated current, breaking capacity, number of poles, trip unit type, fixed or drawout construction and the accessories fitted, such as shunt trip, auxiliary contacts or motor mechanism. For drives give motor power, supply voltage and the communication option. For transformers send rated power, primary and secondary voltage, vector group and enclosure rating.

Frequently Asked Questions

What is the PowerLogic PM5560 used for?
It is an advanced power and energy meter used for power quality analysis, harmonics monitoring, and energy sub-metering in commercial and industrial facilities.
What accuracy class does the PM5560 offer?
The PM5560 offers Class 0.2S accuracy for active energy (IEC 62053-22), suitable for revenue-grade and power quality applications.
What software integrates with the PM5560?
It communicates over Modbus TCP, BACnet/IP, DNP3 and Modbus RTU, so it can be connected to power monitoring and SCADA systems; confirm software compatibility with us for your project.
Does the PM5560 monitor harmonics?
Yes, it analyzes harmonics up to the 63rd order, helping identify power quality issues affecting sensitive equipment.
Is the PowerLogic PM5560 available through Seven Star LLC?
Yes, Seven Star LLC is a trusted supplier of Schneider Electric products supplying PowerLogic meters across Oman and the GCC.