Schneider Electric A9L15687 Acti9 iPF K 40 kA Surge Arrester

Description

A9L15687 iPF K surge arrester, single-phase plus neutral (1P + N)

The A9L15687 is Schneider Electric’s iPF K from the Acti9 line: a Type 2 distribution surge arrester with a nominal discharge current of 15 kA and a maximum discharge current of 40 kA. It is a 1P + N device for 230 V AC (± 10 %) at 50/60 Hz networks, without a remote-signalling contact, and it is built for the TT, TN-S earthing arrangements named in its datasheet. Seven Star LLC supplies the A9L15687 in Oman and the GCC as an independent supplier based in Muscat.

This page reads the official datasheet of the A9L15687 and turns it into selection notes: what the ratings mean for a distribution board, which upstream protection the maker pairs with it, how it differs from the neighbouring models in the range, and what to send us when you ask for a quotation. It is a fixed-ratings component, so every number on this page is taken from the datasheet and nothing is inferred beyond it.

A9L15687 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / A9L15687
Range / product name IPF K (Acti9 iPF K)
Product type Surge arrester
Device short name iPF K
Poles 1P + N
Remote signalling Without
Surge arrester class Type 2
Technology MOV + GDT
Rated operational voltage 230 V AC (± 10 %) at 50/60 Hz
Earthing system TT / TN-S
Nominal discharge current Common mode: 15 kA (L/PE); Common mode: 15 kA (N/PE); Differential mode: 15 kA (L/N)
Maximum discharge current Common mode: 40 kA L/PE; Common mode: 40 kA N/PE; Differential mode: 40 kA L/N
Maximum continuous operating voltage Uc Common mode: 260 V N/PE; Differential mode: 340 V L/N
Voltage protection level Up (maximum) Common mode 1.5 kV type 2 N/PE; Differential mode 1.5 kV type 2 L/N
Temporary overvoltage Ut 337 V L/N 5 s withstand; 442 V L/PE 5 s withstand; 1200 V N/PE 200 ms withstand; 1453 V L/PE 200 ms withstand
Standards IEC 61643-11:2011
Certifications / labels EAC, CE
Mounting Clip-on (DIN rail); 4 modules of 9 mm
Dimensions H x W x D 81 mm x 36 mm x 69 mm
Net weight 210 g
Terminals Tunnel type terminal (top or bottom) 25 mm² rigid; Tunnel type terminal (top or bottom) 16 mm² flexible; Tunnel type terminal (top or bottom) 16 mm² flexible with ferrule
Tightening torque 3.5 N.m
Operating temperature -25–60 °C
Storage temperature -40–85 °C
Warranty 18 months

What the A9L15687 ratings mean in practice

The ratings of the A9L15687 are expressed in the usual Type 2 terms: a nominal discharge current of 15 kA in every mode that applies (Common mode: 15 kA (L/PE); Common mode: 15 kA (N/PE); Differential mode: 15 kA (L/N)) and a maximum of 40 kA (Common mode: 40 kA L/PE; Common mode: 40 kA N/PE; Differential mode: 40 kA L/N). The voltage protection level is Common mode 1.5 kV type 2 N/PE; Differential mode 1.5 kV type 2 L/N, and the continuous operating voltages are Common mode: 260 V N/PE; Differential mode: 340 V L/N.

The datasheet adds temporary-overvoltage figures (337 V L/N 5 s withstand; 442 V L/PE 5 s withstand; 1200 V N/PE 200 ms withstand; 1453 V L/PE 200 ms withstand). They tell a designer how the arrester behaves when a fault on the medium-voltage side or a lost neutral pushes the supply voltage up for seconds rather than microseconds, and they are the reason Uc is chosen with margin above the 230 V AC nominal.

Backup protection paired with the A9L15687

A surge arrester needs short-circuit protection in series so that a failed cartridge or element is isolated from the network. The datasheet of this unit names the associated devices below. The ampere figure shown is the rating of that breaker or fuse, and Icu is the breaking capacity quoted for it.

  • Associated circuit breaker iK60N 40 A curve C – Icu 6 kA
  • Associated fuse gG 63 A – Icu 25 kA

Poles, earthing and wiring of the A9L15687

One phase conductor and the neutral are brought to the arrester, plus the protective-earth connection on the earth terminal. It is the right shape for a single-phase supply, or for a single-phase sub-circuit tapped from a three-phase board.

The earthing arrangement named on the datasheet is TT and TN-S. Terminals are Tunnel type terminal (top or bottom) 25 mm² rigid; Tunnel type terminal (top or bottom) 16 mm² flexible; Tunnel type terminal (top or bottom) 16 mm² flexible with ferrule, tightened to 3.5 N.m. The wire-stripping length is 11 mm. Keep the earth conductor between the arrester and the main earth bar as short and straight as the board layout allows, because inductance in the lead adds directly to the let-through voltage.

A9L15687 against the other models in the range

The table compares this unit with related Acti9 surge arresters, using the figures printed in each datasheet. Pole count, remote contact and maximum discharge current are the three differences that drive most selections.

Part number Device Poles Remote contact Type Imax
A9L15687 (this page) iPF K 1P + N Without Type 2 40 kA
A9L15688 iPF K 3P + N Without Type 2 40 kA
A9L15692 iPF K 1P + N Without Type 2 20 kA
A9L15693 iPF K 3P + N Without Type 2 20 kA
A9L16282 iPRD1 12.5 1P + N With Type 1 + 2 50 kA (Iimp 12.5 kA L/N)
A9L20500 iPRD20 1P + N Without Type 2 20 kA

Selection checklist for the A9L15687

  • Confirm the system: 230 V AC (± 10 %) at 50/60 Hz, earthing TT and TN-S.
  • Confirm pole count (1P + N) against the board: single-phase, three-phase with neutral, or four-pole.
  • Decide whether a remote contact is needed (this version has none).
  • Check the class: Type 2; match it to the position in the installation and to the lightning exposure.
  • Check the voltage protection level (Common mode 1.5 kV type 2 N/PE; Differential mode 1.5 kV type 2 L/N) against the withstand level of the loads downstream.
  • Choose the backup breaker or fuse from the list on this page and confirm it fits the board’s short-circuit level.

Installation and maintenance of the A9L15687

  • Fit the arrester with its associated breaker or fuse on the same DIN rail (clip-on (din rail)), using the 4 module positions the unit occupies.
  • Observe the operating window of -25–60 °C; a board in direct sun or with little ventilation can exceed it.
  • Tighten to 3.5 N.m and re-torque after the first thermal cycles of commissioning.
  • This version has no remote contact, so schedule a visual check of the cartridge status indicator at each board inspection.

After a major lightning event or a supply fault, inspect surge protection even when no alarm has been raised. Keep a spare cartridge or a complete spare A9L15687 for plants where downtime is expensive; send us the part number and we will confirm what can be supplied.

Where the A9L15687 is used in Oman and the GCC

This Type 2 unit fits main and sub-distribution boards in commercial buildings, workshops, telecom shelters and light industrial sites across Oman and the GCC, where switching surges from compressors, pumps and chillers are the most common source of damage. Lightning activity in the mountains, long overhead feeders to remote sites and hot, dusty switchrooms make surge protection and good board ventilation worth planning together. Check the ambient range on the datasheet against the real temperature inside the cabinet, not the room.

Documents and quotation

The official Schneider Electric datasheet of this unit is attached on this page for download, so the ratings above can be checked against the source.

To request a quotation, send us the part number A9L15687 with the quantity and delivery location through the RFQ form. Seven Star LLC replies with availability and lead time.

Datasheets & Documents
  • PDF Datasheet Schneider Electric A9L15687 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9L15687 Acti9 iPF K 40 kA Surge

Answers from our engineering team on installation, compatibility and integration.

01What is the A9L15687?
It is the Schneider Electric Acti9 iPF K, a 1P + N Type 2 surge arrester for 230 V AC systems, without a remote-signalling contact. It clips onto a DIN rail and occupies 4 modules of 9 mm.
02What discharge ratings does the A9L15687 have?
The datasheet lists Common mode: 15 kA (L/PE) as nominal and Common mode: 40 kA L/PE as maximum discharge current.
03Which backup protection is listed for the A9L15687?
The datasheet names associated breakers and fuses, for example Associated circuit breaker iK60N 40 A curve C - Icu 6 kA. The full list is on this page, and the choice depends on the short-circuit level at the board.
04Does the A9L15687 have a remote contact?
No. This version has no remote-signalling contact, so cartridge status is checked on the device itself during inspection. A remote-contact version exists in the range; send us the part number you need and we will compare.
05What operating temperature range applies to the A9L15687?
The datasheet gives -25…60 °C in operation and -40…85 °C in storage, with relative humidity of 5…95 % and an altitude up to 2000 m.