Schneider Electric EZ9S16240 Easy9 2P 40 A Switch Disconnector

Description

EZ9S16240: Easy9 2P, 40 A switch disconnector

The EZ9S16240 is a Schneider Electric Easy9 modular switch disconnector, listed in the datasheet as: Easy9 switch disconnector – 2P – 40 A – 400 V. It is a manual clip-on device for DIN rail distribution boards. It opens and closes the circuit by hand and offers isolation, but it has no tripping unit, so a circuit breaker or fuse must protect the circuit upstream. Seven Star LLC supplies the EZ9S16240 in Oman and the GCC as an independent supplier based in Muscat.

In the reference, Easy9 is the economy modular range, 2P is the number of poles, and the 40 A figure is the rated operational current at 400 V, utilisation category AC-22A. The two-pole 40 A version is the smallest Easy9 switch in this group. It fits the mains isolator of a single-phase consumer unit, the local switch of a split air-conditioner or water heater circuit, and the isolation point of a small sub-board in a villa or shop.

Technical specifications of the EZ9S16240

Parameter Specification
Manufacturer / part number Schneider Electric / EZ9S16240
Description Easy9 switch disconnector – 2P – 40 A – 400 V
Range / application Easy9 / Distribution
Poles 2P
Utilisation category AC-22A
Rated operational current [Ie] 40 A at 400 V 50/60 Hz
Rated operational voltage [Ue] 400 V AC 50/60 Hz
Rated insulation voltage [Ui] 500 V AC 50/60 Hz
Rated impulse withstand [Uimp] 4 kV
Short-circuit making capacity [Icm] 0.6 kA
Short-time withstand [Icw] 0.48 kA during 1 s
Control / indication Toggle; ON/OFF indication; contact position indicator
Mounting Clip-on, DIN rail
Dimensions (H x W x D) 81 mm x 36 mm x 66.5 mm
Width in 9 mm modules 4
Net weight 162 g
Colour Grey
Mechanical / electrical durability 8500 cycles / 1500 cycles
Terminals tunnel type terminal (top or bottom) 1 to 35 mm² rigid; tunnel type terminal (top or bottom) 1 to 25 mm² flexible
Tightening torque 3.5 N.m
Standards IEC 60947-3
Certification CE
IP degree of protection IP20 conforming to IEC 60529
Ambient temperature Operation -5 to 55 °C; storage -5 to 70 °C

Size, terminals and endurance of the EZ9S16240

The EZ9S16240 measures 81 mm high, 36 mm wide and 66.5 mm deep, 4 modules of 9 mm, and weighs 162 g. It is a grey clip-on device with a toggle that shows ON and OFF and a contact position indicator. Terminals are listed as tunnel type terminal (top or bottom) 1 to 35 mm² rigid; tunnel type terminal (top or bottom) 1 to 25 mm² flexible, tightened to 3.5 N.m.

Mechanical durability is 8500 cycles and electrical durability is 1500 cycles. The first figure is operation without load; the second is operation while breaking current, so for a switch that is used as a regular on-off device the second number is the one that sets the maintenance interval. The 63 A sibling EZ9S16263 uses the same 36 mm body and terminals, so the choice between them is about the current of the circuit.

Reading the making and withstand data of the EZ9S16240

The datasheet gives a short-circuit making capacity of 0.6 kA and a short-time withstand current of 0.48 kA during 1 s. Both scale with the rating: the making capacity works out to 15 times the rated current and the withstand to 12 times it, across every Easy9 switch in this group. These figures are small compared with industrial switchgear, which is why the switch is meant for building and light commercial boards where an upstream breaker limits the fault energy.

Utilisation category AC-22A covers resistive and mixed inductive loads including moderate overloads. The insulation voltage is 500 V AC 50/60 Hz and the impulse withstand voltage is 4 kV. Two poles open line and neutral together, which is appropriate for single-phase supplies; on a three-phase circuit use a three or four-pole reference. Its short-circuit making and withstand figures are the lowest in the table, so make sure the upstream protective device keeps the fault energy within them.

Easy9 switch references compared with the EZ9S16240

The table lists the Easy9 switch disconnectors covered on this site; width follows the pole count.

Part number Poles Rating Width Making capacity Weight
EZ9S16240 2P 40 A 36 mm 0.6 kA 162 g
EZ9S16263 2P 63 A 36 mm 0.945 kA 182 g
EZ9S16291 2P 100 A 36 mm 1.5 kA 166 g
EZ9S16292 2P 125 A 36 mm 1.875 kA 182 g
EZ9S16340 3P 40 A 54 mm 0.6 kA 244 g
EZ9S16363 3P 63 A 54 mm 0.945 kA 243 g
EZ9S16380 3P 80 A 54 mm 1.2 kA –
EZ9S16391 3P 100 A 54 mm 1.5 kA 254 g
EZ9S16392 3P 125 A 54 mm 1.875 kA 274 g
EZ9S16440 4P 40 A 72 mm 0.6 kA 326 g

Selection checklist for the EZ9S16240

Before ordering the EZ9S16240, check the following.

  • Circuit current: 40 A at 400 V 50/60 Hz.
  • Poles: 2P, and whether the neutral must be isolated.
  • Upstream protection: it must hold the fault current within the making capacity of 0.6 kA.
  • Space: 4 modules of 9 mm, 36 mm wide.
  • Cable: tunnel type terminal (top or bottom) 1 to 35 mm² rigid; tunnel type terminal (top or bottom) 1 to 25 mm² flexible.
  • Ambient temperature: -5 to 55 °C in operation, which is narrower than industrial switchgear.

Where the EZ9S16240 is used in Oman and the GCC

In Oman and the GCC, economy modular switches are common in villa and apartment boards, shop and office distribution, camp accommodation, small pump rooms and auxiliary panels. They give a local isolation point at moderate cost.

The EZ9S16240 is not an industrial switchgear item. Where the site has high temperature, dust or heavy duty, compare the datasheet range with the real conditions and consider the heavier ComPacT or Acti9 ranges instead.

Installation and maintenance of the EZ9S16240

Clip the EZ9S16240 onto the DIN rail, strip the conductors to the length marked on the device, and tighten the terminals to 3.5 N.m. Check that the toggle movement is firm and that the position indication matches the contacts. Mark the circuit it isolates, because the value of a switch disconnector is a known, labelled isolation point.

Re-check torque after the first weeks, look for heat marks, and keep the front clean. The operating range of -5 to 55 °C is narrow, so mount the board away from direct sun and ensure ventilation; a cabinet in a hot Gulf plant room can easily exceed the upper limit.

Documents and quotation

A datasheet for this product is attached on this page. It carries the electrical, mechanical and environmental data summarised above, so check it against your own single-line diagram or panel drawing before ordering.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and operates separately from the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric EZ9S16240 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric EZ9S16240 Easy9 2P 40 A Switch

Answers from our engineering team on installation, compatibility and integration.

01What is the EZ9S16240?
The EZ9S16240 is a Schneider Electric Easy9 2P switch disconnector rated 40 A at 400 V, category AC-22A, for DIN rail mounting.
02Does the EZ9S16240 give overload protection?
No. It is a manual switch with isolation capability and no trip unit. Overload and short-circuit protection must come from an upstream breaker or fuse.
03What are the short-circuit figures of the EZ9S16240?
The datasheet lists a making capacity of 0.6 kA and a short-time withstand of 0.48 kA during 1 s.
04How wide is the EZ9S16240?
The datasheet lists 81 mm x 36 mm x 66.5 mm (H x W x D), which is 4 modules of 9 mm and a weight of 162 g.
05What temperature range applies to the EZ9S16240?
Operation is listed at -5 to 55 °C and storage at -5 to 70 °C, with IP20 protection.