Schneider Electric 31330 800 A 3-Pole ComPacT INS Switch

Description

31330: ComPacT INS800, 800 A, 3 poles

The 31330 is a Schneider Electric ComPacT INS switch-disconnector, listed in its datasheet as the switch-disconnector Compact INS800 – 800 A – 3 poles, rated 800 A with 3 poles. In plain terms it is a heavy-duty manual load-break switch that makes and breaks load current and isolates, but contains no tripping element, so it never replaces the circuit breaker upstream. Seven Star LLC supplies the 31330 in Oman and the GCC as an independent supplier based in Muscat.

In the model name, INS is the ComPacT switch-disconnector family and the number is the thermal rating in amperes. For this reference that gives INS800, 800 A and 3 poles. It has a black direct front rotary handle and front connections. This is the first reference of the large frame and the natural step above the 630 A group. It is typically used as the incomer of a main low-voltage panel, the isolator of a large motor feeder, or the load-break switch ahead of a busbar riser.

Technical specifications of the 31330

Parameter Specification
Manufacturer / part number Schneider Electric / 31330
Description switch-disconnector Compact INS800 – 800 A – 3 poles
Range / product name ComPact / ComPacT INS
Poles 3P
Rated operational voltage [Ue] 690 V AC 50/60 Hz and 125 V DC
Rated insulation voltage [Ui] 1000 V AC 50/60 Hz
Rated impulse withstand [Uimp] 12 kV
Conventional free-air thermal current [Ith] 800 A at 60 °C
Rated operational current [Ie] 800 A in AC-21A, AC-22A and AC-23A across the voltage bands listed
Short-circuit making capacity [Icm] 75 kA switch-disconnector alone, 330 kA with upstream protection circuit breaker (690 V AC)
Short-time withstand [Icw] 50 kA for 0.5 s, 42 kA for 0.8 s, 35 kA for 1 s, 20 kA for 3 s, 10 kA for 20 s and 8 kA for 30 s
Isolation / position indicator Suitable for isolation; contact position indicator; no visible break
Control / handle Direct front rotary handle, black
Intermittent duty class Class 120 – 60 %
Mounting Fixed, rail or plate, front connection
Connection pitch 70 mm
Mechanical durability 3000 cycles
Electrical durability 500 cycles in AC-21A, AC-22A and AC-23A, and 500 cycles in the DC categories
Dimensions (H x W x D) 300 x 340 x 146.5 mm
Net weight 14 kg
Standards IEC 60947-1, 60947-3
Certifications KEMA-KEUR
IP / IK protection IP40 (IEC 60529) / IK07 (EN 50102)
Ambient temperature Operation -25 to 70 °C; storage -50 to 85 °C

Frame, handle and mounting of the 31330

The 31330 measures 300 mm high, 340 mm wide and 146.5 mm deep, at a connection pitch of 70 mm, and weighs 14 kg. It is fixed-mounted on a rail or a plate, with front connection top and bottom. The handle is a black front rotary handle fixed directly on the device, and a contact position indicator shows whether the switch is open or closed. The datasheet states no visible break.

Mechanical durability is 3000 cycles, and the electrical durability is 500 cycles in AC-21A, AC-22A and AC-23A, and 500 cycles in the DC categories. The mechanical figure applies to operation without load; the electrical figure is the life when the switch actually breaks current.

Duty categories and short-circuit data of the 31330

For this reference the datasheet gives the rated operational current as 800 A in AC-21A, AC-22A and AC-23A across the voltage bands listed. AC-21A means resistive loads, AC-22A mixed resistive and inductive loads, and AC-23A motors and other highly inductive loads; read the AC-23A line when a motor or transformer sits behind the switch.

On DC the datasheet lists DC-21A, DC-22A and DC-23A at 800 A and 125 V DC with two poles in series; a rating given with poles in series is valid only for that wiring. At 340 mm wide, 14 kg and with a 70 mm pitch it is identical in size to the 1000, 1250 and 1600 A three-pole references, which means the frame stays the same while the thermal rating climbs.

The AC-23 motor-switching capacity is given per voltage band: 250 kW at 220/240 V; 400 kW at 380/400 V; 500 kW at 415 V; 560 kW at 500/525 V; 710 kW at 660/690 V. The 31330 makes 75 kA as a switch-disconnector alone and 330 kA with an upstream circuit breaker (690 V AC), carries 50 kA for 0.5 s, 42 kA for 0.8 s, 35 kA for 1 s, 20 kA for 3 s, 10 kA for 20 s and 8 kA for 30 s for the short-time withstand periods, and has insulation voltage 1000 V AC 50/60 Hz with 12 kV impulse withstand. Moving to the large frame changes more than the current: insulation voltage rises to 1000 V, impulse withstand to 12 kV, and the short-circuit making capacity alone to 75 kA, but mechanical life falls to 3000 cycles. Treat it as a different class of device rather than a bigger 630 A switch.

ComPacT INS references compared with the 31330

Frame width stays at 185 mm up to 630 A and then jumps to 340 mm (three poles) or 410 mm (four poles). Compare the 31330 with its neighbours:

Part number Model Rating Poles Width Weight
31112 INS500 500 A 3P 185 mm 4.6 kg
31114 INS630 630 A 3P 185 mm 4.6 kg
31115 INS630 630 A 4P 185 mm 4.9 kg
31330 INS800 800 A 3P 340 mm 14 kg
31331 INS800 800 A 4P 410 mm 18 kg
31332 INS1000 1000 A 3P 340 mm 14 kg
31333 INS1000 1000 A 4P 410 mm 18 kg
31334 INS1250 1250 A 3P 340 mm 14 kg
31335 INS1250 1250 A 4P 410 mm 18 kg
31336 INS1600 1600 A 3P 340 mm 14 kg
31337 INS1600 1600 A 4P 410 mm 18 kg

Selection checklist for the 31330

Before ordering the 31330, collect the following.

  • Rated current: 800 A, with the operational current in the category that matches the load (AC-21A, AC-22A, AC-23A or a DC category).
  • Poles: 3, and whether the neutral must be switched.
  • Voltage: up to 690 V AC, and 125 V DC with two poles in series for DC.
  • Prospective short-circuit current compared with the 75 kA making capacity alone and the upstream breaker.
  • Space: 300 x 340 x 146.5 mm, 14 kg, 70 mm pitch.
  • Cabinet temperature compared with -25 to 70 °C operation.

Where the 31330 fits in Oman and the GCC

In Oman and the GCC, switch-disconnectors of this class are found in main low-voltage switchboards of oil and gas facilities, power stations, desalination and water treatment plants, petrochemical units and large commercial buildings. They serve as incoming isolators, bus-section switches and as the isolating point next to large breakers when maintenance staff need a clear off position.

Heat, dust and humidity are the usual stress factors, so compare the cabinet temperature with the datasheet range. The 31330 is manual and must always be combined with a breaker or fuse sized for the network fault level.

Installation, commissioning and care of the 31330

Mount the 31330 on its rail or plate and make the front busbar or cable connections without letting weight hang on the terminals. Torque them to the figures in the installation sheet.

Maintenance is mostly visual and thermal. Check terminals for discolouration and re-check torque after the first weeks of service. In an installation with frequent load switching, count operations against the electrical durability of 500 cycles in AC-21A, AC-22A and AC-23A, and 500 cycles in the DC categories and plan replacement before that number is reached. IP40 applies to the device itself, so the enclosure must supply any extra protection.

Documents and quotation

A datasheet for this product is attached on this page. It carries the electrical, mechanical and environmental data summarised above, so check it against your own single-line diagram or panel drawing before ordering.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and operates separately from the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric 31330 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric 31330 800 A 3-Pole ComPacT INS

Answers from our engineering team on installation, compatibility and integration.

01What is the 31330?
The 31330 is a Schneider Electric ComPacT INS800 switch-disconnector rated 800 A with 3 poles and a direct front rotary handle, listed in its datasheet as switch-disconnector Compact INS800 - 800 A - 3 poles.
02Does the 31330 protect against overload or short circuit?
No. It is a manual load-break switch with isolation capability and has no trip unit. Overload and short-circuit protection must come from an upstream breaker or fuse; the datasheet gives 75 kA making capacity alone and 330 kA with upstream protection.
03What are the dimensions and weight of the 31330?
The datasheet lists 300 x 340 x 146.5 mm (H x W x D) and a net weight of 14 kg, with a connection pitch of 70 mm.
04Can the 31330 be used on DC?
The datasheet lists DC ratings: DC-21A, DC-22A and DC-23A at 800 A and 125 V DC with two poles in series. The pole wiring has to match the arrangement stated there.
05What temperature range applies to the 31330?
Operation is listed at -25 to 70 °C and storage at -50 to 85 °C, with IP40 and IK07 protection of the device. The free-air thermal current is quoted at 60 °C.