Schneider Electric DBV30606MS DBSeT VTPN 6+6 Board

Description

DBV30606MS: VTPN DBSeT 6+6 way, 125 A surface three-phase board

The DBV30606MS is a Schneider Electric VTPN distribution board in the DBSeT range, built for three-phase low-voltage distribution at 125 A with a modular incomer. The datasheet lists 6 + 6 (outgoer) ways, a pan assembly, earthing bar and neutral bar, and a plain flat door on a painted steel enclosure. It is the surface-mounting version. Seven Star LLC supplies the DBV30606MS in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference from the title and datasheet, DBV3 relates to a three-phase board, the next digits (06, 12, 18, 24, 30 and 12) give the module counts of the two outgoer banks, and MF or MS gives surface mounting. In DBV30606MS the banks are 6 and 6, adding up to 12 outgoer ways. This is our reading of the names and not a published ordering key.

Short-circuit ratings and devices for the DBV30606MS

This family stands out for the short-circuit data given in the datasheet. The rated short-time withstand current (Icw) is 17 kA for 0.25 s and the rated peak withstand current (Ipk) is 34 kA. The impulse withstand voltage (Uimp) is 6 kV, the insulation voltage (Ui) is 500 V AC and the rated voltage is 240…415 V AC at 50/60 Hz on three phases. The board is designed to IEC 61439-3 and IEC 61439-1 and the datasheet lists DEKRA certification.

The options are RCBOs and miniature circuit breakers on the outgoing side and an isolator with an RCCB as the incomer. Those figures describe the assembly and should be compared with the prospective fault current at the point of installation and with the data of the devices fitted. The datasheet describes the incomer as modular, so the main protection is a modular device and not a moulded-case breaker; DBV30606MS is therefore not intended for incoming supplies above its 125 A rating.

Surface mounting of the DBV30606MS

This version fixes to the face of the wall, so there is no recess to form and the 124.9 mm depth stands in the room. The enclosure measures 425 × 555 × 124.9 mm (W × H × D), and the weight on the carton label is 13.335 kg, with a pack size of 55.5 cm by 42.5 cm by 12.49 cm. A board of this weight needs secure wall fixings, and the wall construction should be checked first.

Cables enter through the removable gland plate at the top and bottom of the enclosure, so surface conduit or trunking can be brought in from both directions. The flush-mount twin is the DBV30606MF, with a packed weight of 13.125 kg; the other listed figures are the same.

Commissioning and care of the DBV30606MS

The enclosure is painted sheet steel 1.2 mm thick in White (RAL 9003), with IP41 (IEC 60529) and IK08 ratings, and an ambient temperature of 50 °C for operation. IP41 limits use to indoor, dry places; for dust or splash exposure use another enclosure. The door is a plain flat door with no window.

After mounting, fit the incomer and outgoer devices on the pan assembly, connect neutral and earth conductors to their bars, label each way, and check the torque of every terminal. Test RCCBs and RCBOs on site and record the readings in the commissioning file. During service, thermal imaging under load is a useful check for loose connections. The datasheet lists an 18-month contractual warranty for DBV30606MS.

What the 6+6 outgoer layout provides

The datasheet lists the ways as 6 + 6 (outgoer). Two banks are given, which suggests the pan assembly is split into two ranks of outgoing positions, giving 12 single-pole spaces in total. As with every module-based board, a three-pole breaker or an RCBO takes more than one space, so the count of circuits will be lower than 12. Plan the layout by listing every device and add spare positions.

This is the smallest board in the group, so no smaller sibling exists, and the next size up is the DBV30612MS with 6 + 12 outgoer ways. All references keep the 425 mm width and 124.9 mm depth. Height of DBV30606MS is 555 mm and the packed weight is 13.335 kg, which is why lifting and wall space need checking before delivery.

Selection checklist and RFQ information for DBV30606MS

  • Confirm a three-phase 240…415 V AC, 50/60 Hz supply and a maximum of 125 A.
  • Compare the prospective fault level with the 17 kA / 0.25 s and 34 kA peak values.
  • Count outgoers against 6 + 6 ways and allow for multi-pole devices and spares.
  • Decide on flush or surface mounting and verify wall space for 425 × 555 × 124.9 mm.
  • Decide whether the incomer and outgoer devices are to be supplied with the board.

For the RFQ please send the reference, quantity, delivery location, project name and a draft of the circuit schedule if one exists.

Technical specifications of the DBV30606MS

Parameter Specification
Manufacturer / part number Schneider Electric / DBV30606MS
Range DBSeT
Product type Distribution board (Distribution enclosure)
Application Low voltage electrical distribution
Number of ways 6 + 6 (outgoer)
Rated current [In] 125 A
Rated voltage 240…415 V AC 50/60 Hz
Network 3 phases
Rated short-time withstand [Icw] 17 kA for 0.25 s
Rated peak withstand [Ipk] 34 kA
Rated impulse withstand [Uimp] 6 kV
Rated insulation voltage [Ui] 500 V AC
Protection device options Residual current circuit breaker with overcurrent protection (RCBO) (outgoer); Miniature circuit breaker (MCB) (outgoer); Isolator + residual current circuit breaker (RCCB) (incomer)
Provided equipment pan assembly, earthing bar, neutral bar, enclosure
Mounting Surface
Door Plain flat door
Cable entry Removable gland plate at top and bottom of the enclosure
Material Painted sheet steel 1.2 mm thick
Colour White (RAL 9003)
Width / height / depth 425 / 555 / 124.9 mm
IP degree of protection IP41 conforming to IEC 60529
IK degree of protection IK08
Operating ambient temperature 50 °C
Standards IEC 61439-3, IEC 61439-1
Product certification DEKRA
Packed weight 13.335 kg
Package size (L / W / H) 55.5 cm / 42.5 cm / 12.49 cm
Recyclability potential 96 %
Warranty 18 months

The VTPN DBV family compared with the DBV30606MS

The DBV references share the 125 A modular incomer, the 17 kA and 34 kA short-circuit values and the 425 mm width. The table shows the figures that change from one to the next.

Reference Capacity W × H × D (mm) Packed weight
DBV30606MS 6 + 6 outgoer ways 425 × 555 × 124.9 13.335 kg
DBV30612MS 6 + 12 outgoer ways 425 × 555 × 124.9 13.965 kg
DBV31212MS 12 + 12 outgoer ways 425 × 685 × 124.9 16.8 kg
DBV31218MS 12 + 18 outgoer ways 425 × 685 × 124.9 17.115 kg
DBV31224MS 12 + 24 outgoer ways 425 × 715 × 124.9 17.43 kg
DBV31230MS 12 + 30 outgoer ways 425 × 715 × 124.9 18.27 kg

The ways, height and weight grow with each step, while the rating, voltage and protection class stay constant. The datasheets give the recyclability as 96 %.

Where the DBV30606MS is typically used in Oman and the GCC

A three-phase board at 125 A with a modular incomer serves buildings that are larger than a villa but smaller than a plant substation: office floors, accommodation blocks, retail units, workshops, warehouses and utility buildings at oil and gas, power and desalination sites. It distributes three-phase and single-phase circuits to lighting, air-conditioning, pumps and small machines.

The 12 outgoer ways of DBV30606MS are suited to a floor or a building section where the circuits are known. In hot climates the 50 °C ambient limit and the IP41 rating should be checked against the actual room; an electrical room that is air-conditioned is generally well suited, a roof-top plant cabinet is not.

Documents and quotation

The manufacturer datasheet for the DBV30606MS is attached on this page for reference. It carries the electrical ratings, enclosure details, packing data and environmental profile summarised above.

To request a quotation, send the part number, quantity and delivery location. Seven Star LLC will confirm lead time and commercial terms, and can quote related devices alongside the board on request.

Other Models in the Se Dbset Dbv Range

Seven Star LLC supplies models from the Se Dbset Dbv range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric DBV30606MF DBSeT VTPN 6+6 BoardSwitchgear, Enclosures & DistributionView details
Schneider Electric DBV30606MS DBSeT VTPN 6+6 BoardSwitchgear, Enclosures & DistributionYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric DBV30606MS Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric DBV30606MS DBSeT VTPN 6+6 Board

Answers from our engineering team on installation, compatibility and integration.

01What short-circuit values are listed for the DBV30606MS?
The datasheet lists a rated short-time withstand current (Icw) of 17 kA for 0.25 s and a rated peak withstand current (Ipk) of 34 kA. Compare these with the prospective fault level at the site.
02What incomer does the DBV30606MS use?
The datasheet describes a modular incomer: an isolator with an RCCB. The board is rated 125 A at 240 to 415 V AC, three phases.
03How many outgoing ways does the DBV30606MS have?
The datasheet lists 6 + 6 outgoer ways, 12 single-pole spaces in total. Multi-pole breakers and RCBOs take more than one space.
04Does the DBV30606MS come with breakers?
No. The listed equipment is a pan assembly, earthing bar, neutral bar and enclosure. MCBs, RCBOs and the incomer devices are fitted separately.
05Where can the DBV30606MS be installed?
It is fixed on the wall surface, rated IP41 and IK08 with an ambient temperature of 50 degC, so it is for indoor dry locations. The enclosure is 425 by 555 by 124.9 mm.