Schneider Electric A9S60220 Acti9 iSW 2P 20 A Switch

Description

A9S60220: Acti9 iSW 2P, 20 A switch-disconnector

The A9S60220 is a Schneider Electric Acti9 iSW modular switch, listed by the manufacturer as: switch Acti9 iSW – 2 poles – 20 A – 415V. It is a manual on/off device for DIN rail panels. It switches and isolates a circuit by hand and carries no overload or short-circuit element, so it always works together with a miniature circuit breaker or fuse upstream. Seven Star LLC supplies the A9S60220 in Oman and the GCC as an independent supplier in Muscat.

The reference reads as follows: Acti9 is the modular device range, iSW is the switch-disconnector line, 2P gives the number of poles and the 20 A figure is the rated operational current at 415 V. The category is AC-22A. The two-pole 20 A version occupies only two 9 mm modules, 18 mm in total, which makes it the natural local isolator for a single-phase final circuit: a lighting group, a small extractor fan, a water heater or a split air-conditioner outdoor unit fed from a distribution board.

Technical specifications of the A9S60220

Parameter Specification
Manufacturer / part number Schneider Electric / A9S60220
Description switch Acti9 iSW – 2 poles – 20 A – 415V
Range / device Acti9 / iSW switch-disconnector
Poles 2P
Utilisation category AC-22A
Rated operational current [Ie] 20 A at 415 V
Rated operational voltage [Ue] 415 V AC
Rated insulation voltage [Ui] 500 V AC conforming to EN/IEC 60669-2-4
Rated impulse withstand [Uimp] 4 kV
Control / signalling Toggle, ON/OFF indication
Dimensions (H x W x D) 77 mm x 18 mm x 70 mm
Width in 9 mm modules 2
Net weight 66 g
Colour White
Mechanical / electrical durability 300000 cycles / 30000 cycles
Terminals tunnel type terminals: 10 mm² rigid; 10 mm² flexible; 10 mm² flexible with ferrule
Stripping length / tightening torque 9 mm / 1.2 N.m
Standard EN/IEC 60669-2-4
IP / pollution degree IP40 / 2
Ambient temperature Operation -20 to 50 °C; storage -40 to 70 °C
Relative humidity 95 % at 55 °C

How to read the ratings of the A9S60220

Utilisation category AC-22A means the switch is built for resistive and mixed inductive loads including moderate overloads, so the 20 A rating at 415 V applies to circuits of that kind. The insulation voltage of 500 V AC conforming to EN/IEC 60669-2-4 and the impulse withstand of 4 kV describe how the switch behaves with respect to the supply and overvoltages, and they are different from the operating voltage.

A switch-disconnector has no tripping element. If the load is a motor, remember that the starting current is several times the running current, so the switch must be backed by a proper starter or a motor-rated device; the A9S60220 is a means of switching and isolating, not of protecting. Two poles mean line and neutral are both opened, which is what you want on a single-phase circuit. On a three-phase load it is the wrong choice, and 20 A at 415 V in AC-22A is the limit, so motors with a high starting current need a dedicated starter and not just this switch.

Acti9 iSW references compared with the A9S60220

Its 32 A two-pole sibling A9S60232 has the same body and terminals, so the choice between the two is purely about the load current and the upstream protection.

The table lists the iSW references covered on this site:

Part number Poles Rating Width Weight
A9S60220 2P 20 A 18 mm 66 g
A9S60232 2P 32 A 18 mm 65 g
A9S60332 3P 32 A 36 mm 117 g
A9S60420 4P 20 A 36 mm –
A9S60432 4P 32 A 36 mm 130 g
A9S61220 2P 20 A 18 mm –
A9S66291 2P 100 A 36 mm 179 g
A9S66492 4P 125 A 72 mm 348 g

Size, terminals and wiring of the A9S60220

The A9S60220 measures 77 mm high, 18 mm wide and 70 mm deep, which is 2 modules of 9 mm on the DIN rail and weighs 66 g. It is fixed-mounted on a DIN rail and finished in white. The toggle gives a clear ON/OFF indication, and the contact position is signalled.

Terminals are specified as tunnel type terminals: 10 mm² rigid; 10 mm² flexible; 10 mm² flexible with ferrule. The stripping length is 9 mm and the tightening torque 1.2 N.m, so use a torque screwdriver for repeatable connections. Keep conductor cross-sections within the stated 10 mm² limit.

Installation and maintenance of the A9S60220

Snap the A9S60220 onto the DIN rail, connect supply and load as shown by the markings on the device and the wiring diagram, and tighten to 1.2 N.m. Switch it on and off a few times without load to confirm the toggle movement and the position indication. Label the circuit clearly, because the whole purpose of the switch is to give a maintenance person a known point of isolation.

In service, look for heat marks near the terminals and re-check torque after the first weeks. The listed electrical durability of 30000 cycles refers to switching under load, so a switch that is operated frequently under load wears sooner than one that is only used for isolation.

Selection checklist for the A9S60220

Before ordering the A9S60220, confirm the following.

  • Load current at the supply voltage: 20 A at 415 V.
  • Number of poles: 2P, and whether the neutral must be switched.
  • Upstream protection: the switch needs a breaker or fuse sized for the cable and the fault level.
  • Space: 2 modules of 9 mm, 18 mm wide.
  • Terminal cross-section and number of conductors per terminal: tunnel type terminals: 10 mm² rigid; 10 mm² flexible; 10 mm² flexible with ferrule.
  • Ambient temperature: -20 to 50 °C in operation.

Where the A9S60220 is used in Oman and the GCC

In Oman and the GCC, modular switch-disconnectors of this kind appear in building services boards, small industrial panels, utility rooms of water and desalination plants, camp accommodation, and equipment skids in the oil and gas sector. They give electricians a local isolation point without opening the whole panel.

Panel temperature is the practical concern in the region: compare the operating range of -20 to 50 °C with the temperature inside the enclosure on a summer afternoon, and add shading or ventilation if the margin is small. The A9S60220 should be treated as a switching and isolating device and combined with suitable protection.

Documents and quotation

A datasheet for this product is attached on this page. It carries the electrical, mechanical and environmental data summarised above, so check it against your own single-line diagram or panel drawing before ordering.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and operates separately from the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric A9S60220 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric A9S60220 Acti9 iSW 2P 20 A Switch

Answers from our engineering team on installation, compatibility and integration.

01What is the A9S60220?
The A9S60220 is a Schneider Electric Acti9 iSW 2P switch-disconnector rated 20 A at 415 V, in utilisation category AC-22A, mounted on a DIN rail.
02Does the A9S60220 protect against overload?
No. It is a manual switch without a trip element. The circuit must be protected by an upstream breaker or fuse selected for the cable and fault level.
03How wide is the A9S60220?
The datasheet lists 77 mm x 18 mm x 70 mm (H x W x D), which is 2 modules of 9 mm and a weight of 66 g.
04What terminals does the A9S60220 have?
The datasheet describes tunnel type terminals: 10 mm² rigid; 10 mm² flexible; 10 mm² flexible with ferrule, with a stripping length of 9 mm and a tightening torque of 1.2 N.m.
05What temperature range applies to the A9S60220?
Operation is listed at -20 to 50 °C and storage at -40 to 70 °C, with relative humidity of 95 % at 55 °C.