Schneider Electric VCCF0 Vario 25 A Emergency Stop Switch

Description

VCCF0: TeSys Vario emergency stop switch disconnector, 25 A

The VCCF0 is the 25 A starting size of the TeSys Vario emergency stop switch disconnector series. The datasheet lists it as a TeSys Vario switch disconnector of the VCCF type with three poles and three normally open contacts, supplied as three parts: the switch body, the shaft extension and a red rotary handle on a yellow front plate. The switch sits at the back of the enclosure on a rail or plate and the handle is fixed on the door, so the operator reaches the disconnect without opening the cabinet. Seven Star LLC supplies the VCCF0 in Oman and the GCC as an independent supplier in Muscat.

The conventional free-air thermal current is 25 A and the enclosed thermal current is 20 A, and that second figure is the one to compare with your load when the switch is inside a closed panel. The unit is suited to a single small machine: a pump skid, a conveyor drive, a packaging machine or a compact fan unit where the motor is a few kilowatts and the operator needs a clearly marked red-and-yellow disconnect at the door.

VCCF0 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / VCCF0
Description TeSys Vario – emergency stop switch disconnector – 25 A – back of enclosure
Range / product name TeSys / TeSys VARIO
Product type Emergency stop switch disconnector
Device composition Shaft extension; Switch; Handle
Mounting support Handle: door; Switch: symmetrical rail; Switch: plate
Number of poles / contacts 3P / 3 NO
Rated operational voltage [Ue] 690 V AC 50/60 Hz
Rated power AC-3 11 kW at 690 V (AC-3); 4 kW at 230 to 240 V (AC-3); 5.5 kW at 400 to 415 V (AC-3); 7.5 kW at 500 V (AC-3)
Rated operational current [Ie] 14.5 A AC-23 Ue: 400 V
Free-air thermal current [Ith] 25 A
Enclosed thermal current [Ithe] 20 A
Making capacity 250 A at 400 V AC-21A; 250 A at 400 V AC-22A; 250 A at 400 V AC-23A
Breaking capacity 200 A at 400 V (AC-21A); 200 A at 400 V (AC-22A); 200 A at 400 V (AC-23A)
Conditional short-circuit current 10 kA at 400 V – associated fuse 25 A aM; 10 kA at 400 V – associated fuse 25 A gG
Short-circuit making capacity [Icm] 1 kA at 400 V at Ipeak
Short-time withstand [Icw] 300 A at 400 V duration: 1 s
Suitability for isolation Yes
Intermittent duty class 30
Control type / handle style Rotary handle / Extended
Handle colour / front plate Red / Yellow
Padlocking 1 to 3 padlocks 4 to 8 mm
Mechanical durability 100000 cycles
Electrical durability 100000 cycles AC-21; 30000 cycles DC-1 to 5
Power terminals Power circuit: screw clamp terminals 10 mm² – solid; Power circuit: screw clamp terminals 6 mm² – flexible – with cable end
Tightening torque Power circuit: 2.1 N.m – on screw clamp terminals
Base dimension 60 x 60 mm
Standards IEC 60947-3
Certifications UL; CSA; CCC; GL; UKCA
Degree of protection IP20 conforming to IEC 60529; IP65
Mechanical robustness Vibrations 10 to 150 Hz (1 gn) conforming to IEC 60068-2-6; Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27
Ambient temperature (operation) -20 to 50 °C

Selection checklist for the VCCF0

  • Load current: stay inside 20 A enclosed thermal current for the real panel conditions.
  • Motor power: 5.5 kW at 400 to 415 V in category AC-3 is the figure for direct motor duty.
  • Fuse: the 10 kA conditional rating assumes a 25 A aM or gG fuse upstream.
  • Cable: up to 10 mm² solid or 6 mm² flexible with end sleeve, torque 2.1 N.m.
  • Door and panel: base 60 x 60 mm, handle on the door, switch on rail or plate.
  • Certification need: the datasheet lists UL; CSA; CCC; GL; UKCA; tell us if the project demands another.

Endurance and site conditions for the VCCF0

The mechanical durability is 100000 cycles and the electrical durability is 100000 under AC-21 and 30000 cycles under DC-1 to 5. The intermittent duty class is 30. These numbers describe how often an operator can use the handle over the life of the switch; for an emergency stop that is rare, but the same switch used as a daily disconnect uses its cycles faster.

The operating ambient is -20 to 50 °C and the datasheet gives IP20 for the switch and IP65 for the handle. In an Oman installation, remember that a panel standing in the sun in the Gulf summer can exceed the cabinet ambient limit, so measure the temperature inside, not outside. The VCCF0 is typically found in pump houses, desalination and water-treatment skids, process plants and building plant rooms with dust and heat.

TeSys Vario VCCF series around the VCCF0

The eight references in this group share the same concept, a rear-mounted switch with an extended door handle, and move up through the thermal-current ladder. The row for the VCCF0 is highlighted.

Part number Ith / Ithe (A) AC-3 at 400 to 415 V Max conductor (solid / flexible mm²) Torque (N.m) Mechanical cycles
VCCF0 25 / 20 5.5 kW 10 / 6 2.1 100000
VCCF01 20 / 16 4 kW 10 / 6 2.1 100000
VCCF1 32 / 25 7.5 kW 10 / 6 2.1 100000
VCCF2 40 / 32 11 kW 10 / 6 2.1 100000
VCCF3 63 / 50 18.5 kW 25 / 16 4 30000
VCCF4 80 / 63 22 kW 25 / 16 4 30000
VCCF5 125 / 100 30 kW 95 / 70 22.6 30000
VCCF6 175 / 140 37 kW 95 / 70 22.6 30000

Mounting and padlocking the VCCF0

The datasheet lists the mounting support as the handle on the door and the switch on a symmetrical rail or on a plate, fixed by clips for the rail and by screws for the plate; the handle is held by four screws. The base measures 60 x 60 mm and the body is 74 mm high and 60 mm wide.

The handle accepts 1 to 3 padlocks 4 to 8 mm, and its marking is 0-1. Padlocking in the OFF position is the usual lock-out routine for maintenance; agree the lock-out procedure with the site safety team before the panel is released. The 60 mm base frame keeps the cut-out and the space behind the door small, which suits compact machine panels.

Current, power and fault ratings of the VCCF0

In utilisation category AC-23 at 400 V the datasheet lists a rated operational current of 14.5 A. For motor duty in category AC-3 it lists 4 kW at 230 to 240 V, 5.5 kW at 400 to 415 V, 7.5 kW at 500 V and 11 kW at 690 V, and 7.5 kW at 400 to 415 V in category AC-23A.

The switch can make 250 A and break 200 A at 400 V in AC-21A, AC-22A and AC-23A. Its conditional short-circuit rating is 10 kA at 400 V when it is protected by a 25 A aM or gG fuse, and the short-time withstand is 300 A for one second. The rated impulse withstand is 8 kV.

Because the conditional rating depends on the 25 A fuse, treat the fuse as part of the product selection: a larger fuse, or none, is not covered by the datasheet figure.

Details to send with an RFQ for the VCCF0

A short request is enough. If the VCCF0 is a replacement, tell us whether the handle, the shaft extension and the switch are all needed, because the datasheet describes them as a set.

  • Part number VCCF0 and quantity.
  • Supply voltage, frequency and prospective short-circuit current.
  • Motor or load rating, and the upstream fuse rating.
  • Door thickness and enclosure depth where the handle is fitted.
  • Certification and delivery requirements.

Documents and quotation

A datasheet for this product is attached on this page. It lists the ratings and dimensions summarised above and is the document to check against your drawings and load calculations.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric VCCF0 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric VCCF0 Vario 25 A Emergency Stop

Answers from our engineering team on installation, compatibility and integration.

01What is the thermal current of the VCCF0?
The datasheet gives 25 A free-air thermal current and 20 A enclosed thermal current, with a rated operational current of 14.5 A at 400 V in AC-23.
02What does the VCCF0 consist of?
The datasheet lists a handle, a switch and a shaft extension. The handle is red on a yellow front plate and mounts on the door; the switch mounts on rail or plate at the back of the enclosure.
03What motor power can the VCCF0 switch?
In utilisation category AC-3 the datasheet lists 5.5 kW at 400 to 415 V and 4 kW at 230 to 240 V. Always check the real motor nameplate and starting duty.
04How many padlocks fit the VCCF0?
The handle takes 1 to 3 padlocks 4 to 8 mm, which allows the OFF position to be locked by several people during maintenance.
05Which protection degree applies to the VCCF0?
The datasheet gives IP20 conforming to IEC 60529; IP65. Operating ambient is -20 to 50 °C.