Brand: Endress+Hauser (E & H)
Endress+Hauser TMT82 HART Temperature Transmitter, 2-Channel
Description
Endress+Hauser TMT82 iTEMP Endress+Hauser TMT82 overview
The Endress+Hauser iTEMP Endress+Hauser TMT82 is a HART temperature transmitter with two universal sensor inputs, available as a head, field or DIN rail device. It accepts RTD, thermocouple, resistance and voltage signals and communicates with HART 7.
Because the TMT82 can connect two independent sensors, it supports redundancy and average or differential measurement. It carries international hazardous-area approvals and SIL certification up to SIL 2, and can be used in marine applications.
Seven Star LLC lists the TMT82 for buyers in Oman and the GCC who need the exact model that is already installed or specified. Engineers often search by the model code, and the TMT82 is one of the products that plants reorder for replacement, expansion and maintenance work.
Key features of the TMT82
- Two universal inputs for RTD, thermocouple, resistance and mV signals
- HART 7 communication with analog output 4 to 20 mA or 20 to 4 mA
- SIL certification up to SIL 2, SC3 according to IEC 61508:2010
- Sensor-transmitter matching for highest accuracy
- Sensor and hardware failure detection with NAMUR NE 107 status information
- Push-in terminals for tool-free wiring
- Head form B per DIN EN 50446, field housing up to IP 68, or DIN rail housing 17.5 mm wide
TMT82 technical specifications
| Parameter | Value |
|---|---|
| Type | HART temperature transmitter, head, field or DIN rail |
| Inputs | Two independent universal inputs: RTD, thermocouple, resistance, voltage |
| Output | 4 to 20 mA or 20 to 4 mA, HART 7, FSK plus or minus 0.5 mA |
| Supply, head transmitter | 11 to 42 V standard, 11 to 32 V in SIL mode |
| Ambient temperature | Minus 40 to 85 degrees C, optional minus 50 to 85 degrees C |
| RTD response time | 0.9 to 1.5 s depending on connection |
| Protection, head transmitter | IP 20; field housing with separate terminal compartment IP 67 |
| Functional safety | SIL 2, SC3 per IEC 61508:2010 |
| Approvals | FM, CSA, ATEX, EAC, NEPSI, IECEx, DNV GL |
| DIN rail width | 17.5 mm |
The values above are taken from the manufacturer Technical Information for the TMT82. Exact limits depend on the selected version, material, process connection and approval, so confirm the order code against the datasheet before purchase.
Typical applications of the TMT82 in Oman and the GCC
The TMT82 is used on thermowell sensors in reactors, heat exchangers, furnaces, pipelines and turbines. In Oman and the GCC, it is common in oil and gas and power plants, where it converts the sensor signal into a robust HART loop signal and, in a field housing, withstands hot and dusty outdoor conditions.
Across oil and gas, utilities, water and wastewater, and manufacturing plants in the region, the TMT82 is selected where the application matches the limits listed in the specifications table. Hot ambient conditions, dust and long cable runs are normal in the Gulf, so check the ambient temperature range and the housing protection against the site conditions.
Selection and compatibility notes for the TMT82
Choose the housing style for the installation: head mount in a terminal head, field housing, or DIN rail in a cabinet. Select hazardous-area approval and SIL mode according to the plant requirement. With two inputs you can configure redundancy, so check that the connected sensors are suitable and confirm the order code details.
Installation and commissioning of the TMT82
Mount the head version in a terminal head form B or use the DIN rail housing in the cabinet. Wire the sensors using push-in terminals and configure the sensor type, range and damping with HART tools or FieldCare. Run sensor-transmitter matching if a calibrated RTD set is supplied.
Always follow the Operating Instructions of the TMT82 and the local rules for electrical installation, especially in hazardous areas. Document the tag, configuration and as-found values at commissioning so that later service checks can be compared with them.
Maintenance of the TMT82
A scheduled inspection of the TMT82 should cover the wetted parts or sensing element for damage or build-up, the cable glands and seals for tightness, the housing cover and gasket, and the loop signal against a reference. Keep a record of the device serial number and order code, because they identify the exact version when you need a spare or replacement.
Related products and ordering notes for the TMT82
The TMT82 belongs to the iTEMP product line of the manufacturer. Neighbouring models in the same Technical Information share much of the documentation and accessories, so confirm which model the project needs. Accessories such as weather covers, mounting hardware and remote displays are specified by their own order codes.
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Product names and model codes are used only to identify the item that the buyer wants to purchase.
When you prepare a purchase request for the TMT82, collect the full order code from the existing nameplate if you are replacing a unit, the tag number, the measuring range or probe length, the process connection, the electrical output and the hazardous-area certificate. Matching these details avoids mistakes with look-alike versions, and it lets the supplier confirm availability and lead time without delay. For spare or legacy requirements, the serial number printed on the nameplate helps identify the exact build.
TMT82 frequently asked questions in brief
How many sensors can the TMT82 connect? It has two independent universal sensor inputs for RTD, thermocouple, resistance and voltage signals. What communication does the TMT82 use? It uses HART 7 with a 4 to 20 mA analog output. Is the TMT82 SIL certified? Yes, the datasheet lists SIL certification up to SIL 2, SC3 according to IEC 61508:2010.
Documents and quotation
The manufacturer Technical Information for the TMT82 is available as a datasheet that you can download from this product page, and it lists the full ordering structure. To receive a quotation, send an RFQ with the part number TMT82, the quantity, the required version and options, and the delivery location. We reply with availability and lead time for your Oman or GCC project.
Datasheets & Documents
- Datasheet Endress+Hauser TMT82 HART Temperature Transmitter, 2-Channel Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Endress+Hauser makes process measurement instruments for flow, level, pressure, temperature and liquid analysis. Georg H. Endress and Ludwig Hauser started the business in Lörrach, Germany, on 1 February 1953, first selling level meters, and the Endress+Hauser name has been used since 1957. The group is headquartered in Reinach, Switzerland, and has been wholly owned by the Endress family since 1975.
Seven Star LLC is an independent supplier listing Endress+Hauser flowmeters, level and pressure transmitters, temperature assemblies and liquid analysis products for buyers in Oman and the GCC. Instruments are matched from the full order code on the nameplate.
Endress+Hauser company profile
| Origin | Founded in Lörrach, Germany, on 1 February 1953 by the Swiss engineer Georg H. Endress and Ludwig Hauser |
|---|---|
| Headquarters | Endress+Hauser AG, Reinach (Basel-Landschaft), Switzerland |
| Ownership | Family owned; the Endress family has been the sole shareholder since 1975, and a family charter commits the company to stay family owned |
| Size | About 16,500 employees and sales of about EUR 3.7 billion (2023, as reported by the company) |
| Product families | Proline flowmeters, Micropilot and Levelflex radar, Liquiphant switches, Cerabar and Deltabar pressure, iTEMP and iTHERM temperature, Liquiline and Memosens liquid analysis |
Milestones
- 1953: Georg H. Endress and Ludwig Hauser start the business in Lörrach on 1 February, first selling level meters.
- 1957: The Endress+Hauser name comes into use.
- 1975: The Endress family becomes sole shareholder.
- 2023: About 16,500 employees and sales of about EUR 3.7 billion, as reported by the company.
Endress+Hauser product lines
| Line | Measuring principle | Typical use |
|---|---|---|
| Promass F 300, Promass 80F, 83F/84F | Coriolis mass flow | Direct mass flow and density of liquids and gases, hydrocarbon transfer and chemical dosing |
| Promag P 300, P 500, H 300, W 400, W 10, 50P | Electromagnetic flow | Water, wastewater, slurries and other conductive liquids |
| Prowirl F 200, 72F | Vortex flow | Steam, gas and low-viscosity liquids |
| Prosonic Flow 92F, t-mass 65F | Ultrasonic and thermal mass flow | Water lines; compressed air and industrial gases |
| Micropilot FMR62, FMR67, FMR60, FMR10B, FMR20, FMR50, FMR52 | Free-space radar level, 80 GHz and 26 GHz | Tanks, process vessels, silos and open water channels |
| Levelflex FMP51, FMP50, FMP54, FMP55 | Guided wave radar level | Level and interface in vessels, separators and bypass chambers |
| Liquiphant FTL51, Prosonic S FMU90 | Vibronic point level; ultrasonic level | High and low level alarms, pump protection, open channel flow |
| Cerabar PMC71B, PMP51B, PMP71, Deltabar PMD78B, PMD75 | Pressure and differential pressure | Process pressure, hydrostatic level and DP flow |
| iTEMP TMT82, TMT162, iTHERM TM101, TR66, TR10 | Temperature transmitters and thermometers | RTD and thermocouple points with thermowells |
| Liquiline CM444, CM442, Memosens CPS11E, Stamolys reagents | Liquid analysis | pH, ORP, conductivity, dissolved oxygen and nutrient analysis in water treatment and process |
Where Endress+Hauser instruments are used
In Oman and the GCC, Endress+Hauser instruments are common in oil and gas production and processing, refineries and petrochemicals, desalination and water networks, wastewater treatment, power plants and food and beverage plants. Coriolis meters measure hydrocarbon and chemical flows, electromagnetic meters cover water and wastewater, radar transmitters handle tank and silo level, and Liquiline analysers monitor water quality. Proline 300 and 500 flowmeters include Heartbeat Technology for in-situ verification, which reduces the need to remove a meter for checks.
Ordering Endress+Hauser instruments: what we need
The order code on the nameplate (for example PMP71-1QA1S11RDADU) defines every option: measuring range, process connection, materials, output, approvals and display. Send it with the serial number; Endress+Hauser can retrieve the original configuration from the serial number. For a new instrument add the medium, operating and design pressure and temperature, range, line size or tank geometry, process connection, wetted materials, output or protocol (4-20 mA HART, PROFIBUS, FOUNDATION Fieldbus, Modbus) and the hazardous-area approval required. Older models such as Promass 80/83 or Micropilot M are replaced by current Proline or 80 GHz Micropilot devices.
Facts checked against Endress+Hauser company history and product information, October 2026.
Browse Endress+Hauser products by category: Flowmeters, Level Transmitter, Pressure Instrumentation, Temperature, Liquid Analysis Sensors, Liquid Analytical Systems.
FAQ
Questions about the Endress+Hauser TMT82 HART Temperature Transmitter,
Answers from our engineering team on installation, compatibility and integration.
01How many sensors can the TMT82 connect?
It has two independent universal sensor inputs for RTD, thermocouple, resistance and voltage signals.
02What communication does the TMT82 use?
It uses HART 7 with a 4 to 20 mA analog output.
03Is the TMT82 SIL certified?
Yes, the datasheet lists SIL certification up to SIL 2, SC3 according to IEC 61508:2010.
04What housing options exist?
Head transmitter for terminal head form B, field housing, and DIN rail housing 17.5 mm wide.
05How do I order the TMT82 from Seven Star LLC?
Send an RFQ with the part number TMT82, the quantity, the housing type, approvals and configuration. We reply with availability and a quotation.