- Automation & ControlView all 2,895 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Yokogawa
Yokogawa YS1700 Programmable Indicating Controller
Description
Yokogawa YS1700 overview: programmable single-loop indicating controller with TFT display
The Yokogawa YS1700 is a programmable indicating controller that can be tailored to many applications by running a user program. It combines a full-dot TFT LCD, dual-CPU fail-safe design and expandable I/O, and it is offered in several types, including compatible versions designed to replace earlier Yokogawa controllers in the same panel cutout.
The Yokogawa YS1700 can be used in function selection mode for single-loop, cascade or selector control without programming, or in programmable mode with text programming of up to 1000 steps or function block programming of up to 400 modules using the YSS1000 setting software.
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. We list YS1700 so that maintenance, instrumentation and procurement teams can quote the exact model code that appears in the manufacturer documentation.
Key features of YS1700
- Full-dot TFT LCD with meter, trend, bar graph, alarm and event displays and all parameters set from the front panel.
- Dual CPU, one for control and one for display, and an independent hard manual circuit that lets the output be adjusted during a digital circuit failure (not incorporated with the -2xx suffix option).
- Non-volatile memory with no battery or capacitor for backup.
- AC and DC dual power supply: 80 to 138 V AC or 20 to 132 V DC for the dual-drive models.
- Basic type with 250 mm depth and an IP54 dust and splash-proof faceplate.
- Optional Ethernet (Modbus/TCP, basic type), RS485 and DCS-LCS communication.
- Basic type with expandable I/O offers eight analog inputs, four analog outputs and fourteen digital inputs and outputs in total.
YS1700 technical specifications
The table below lists values published by the manufacturer for the product family of YS1700. Where a value depends on the ordered configuration, the model and suffix code table in the General Specifications governs.
| Parameter | Value |
|---|---|
| Model | YS1700 programmable indicating controller (suffix codes select the type) |
| Basic type | YS1700-x0x: 5 analog inputs (1 to 5 V), 3 analog outputs, 6 digital I/O |
| Basic type with expandable I/O | YS1700-x1x: 8 analog inputs, 4 analog outputs, 14 digital I/O |
| Compatible types | YS100, YS80 internal unit, EBS and I series, EK and HOMAC, 100 line compatible types |
| Program capacity | 1000 steps (text program); 400 modules (function block program) |
| Control period | 50, 100 or 200 ms (programmable mode); 100 ms (function selection mode) |
| Rated accuracy of input conversion | Plus or minus 0.2 percent of span for 1 to 5 V inputs |
| Display | Color LCD, 120 by 320 pixels |
| Normal working ambient temperature | 0 to 50 deg C |
| Normal working humidity | 5 to 90 percent RH, no condensation |
| Power supply | 80 to 138 V AC or 20 to 132 V DC (dual-drive); 138 to 264 V AC (220 V AC models) |
Typical applications of YS1700 in Oman and the GCC
- Boiler combustion, drum level and feedwater control in power and steam plants.
- Stand-alone control of heaters, dosing, pH and utility loops in refineries and desalination units.
- Replacement of older YS100 and YS80 series controllers in existing panels.
- Cascade and selector control schemes with custom calculations.
- Backup control stations behind a distributed control system.
Panel-mounted single-loop controllers and indicators remain in service for decades in power stations, refineries, desalination plants and process units across Oman and the GCC, often as the last manual-station layer behind a DCS or as stand-alone control on boilers, heaters, dosing and utility loops. Plant owners therefore search for the exact model code, such as YS1700, so that a failed unit can be replaced with one that fits the existing panel cutout and wiring.
Selection and compatibility notes for YS1700
The YS1700 name covers many suffix code combinations: type (basic, expandable I/O or compatible type), hard manual circuit, power supply, communication and options. For a replacement, read the full model and suffix code from the nameplate of the existing unit; for a new application, tell us the I/O count and protocol needed.
The compatible types keep the panel cutout and depth of the earlier series, so check which earlier series (YS100, YS80, EBS and I series, EK or HOMAC) is being replaced.
The model code of YS1700 is only the beginning, because the suffix codes select the type (basic, expandable I/O, or one of the compatible types for older Yokogawa lines), the power supply, the communication option and optional functions. Send us the full code from the nameplate of the unit being replaced, or the specification you want, and we will compare it with the model and suffix code table in the manufacturer General Specifications before quoting.
Installation and commissioning
Check the panel cutout and depth, wire the terminals according to the manufacturer terminal diagram, and confirm the supply type (100 V AC or DC dual drive, or 220 V AC) on the nameplate before energising. Set the programmable mode or function selection mode, scale the inputs and outputs and test manual-to-automatic changeover.
Check the panel cutout and depth against the type you ordered, wire the input, output and power terminals according to the manufacturer terminal diagram, and verify the power supply type on the nameplate before energising. After power-up, set the input ranges, alarms and control parameters from the engineering displays, then run a manual-to-automatic changeover test with the process in a safe state.
Maintenance, calibration and service
Verify input and output accuracy periodically against a calibrator, keep the user program and parameters saved from the YSS1000 software, and note that internal unit replacement and repair are described by the manufacturer as work for qualified service personnel.
Controllers of this class use non-volatile memory and need no battery replacement, so routine care is mostly inspection of terminals, cleaning of the front panel and periodic verification of input and output accuracy against a calibrator. Record the tuning parameters and any user program, and keep a spare configuration file so that a replacement can be commissioned quickly.
Related products and ordering notes for YS1700
- YS1500 indicating controller and YS1310 indicator with alarms from the same series.
- YSS1000 setting software and YS110 standby manual station accessories.
When you request YS1700, tell us whether the item is for a new installation, a like-for-like replacement or a spares stock, because that changes which accessories and documents are worth adding to the same quotation. We can also check related codes so that a single RFQ covers the instrument and the parts that go with it.
Frequently asked questions about YS1700
- What is YS1700? YS1700 is a programmable indicating controller for single-loop and custom control that can run a user program or work in function selection mode without programming.
- What power supply does YS1700 need? Dual-drive models run from 80 to 138 V AC or 20 to 132 V DC, and 220 V AC models from 138 to 264 V AC, as listed in the manufacturer data sheet.
- Can YS1700 replace older Yokogawa controllers? The manufacturer offers compatible types with the same panel cutout and depth as earlier YS series units, so confirm the earlier model and suffix code.
- Which communication options exist for YS1700? Optional Ethernet (Modbus/TCP, basic type only), RS485 and DCS-LCS communication are listed by the manufacturer.
- How do I order YS1700? Send Seven Star LLC the full model and suffix code from the nameplate, the quantity and delivery location. We will confirm and quote in writing.
Documents and quotation
The manufacturer General Specifications for the family of YS1700 is available and we can send it with your quotation. To request pricing and lead time, send an RFQ to Seven Star LLC with the part number YS1700, the quantity, the full model and suffix code or the nameplate details of the unit being replaced, the delivery location and any certificate requirements. We will confirm availability and reply in writing with a quotation for YS1700.
Datasheets & Documents
- Datasheet Yokogawa YS1700 Programmable Indicating Controller Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa YS1700 Programmable Indicating Controller
Answers from our engineering team on installation, compatibility and integration.
01What is YS1700?
YS1700 is a programmable indicating controller for single-loop and custom control that can run a user program or work in function selection mode without programming.
02What power supply does YS1700 need?
Dual-drive models run from 80 to 138 V AC or 20 to 132 V DC, and 220 V AC models from 138 to 264 V AC, as listed in the manufacturer data sheet.
03Can YS1700 replace older Yokogawa controllers?
The manufacturer offers compatible types with the same panel cutout and depth as earlier YS series units, so confirm the earlier model and suffix code.
04Which communication options exist for YS1700?
Optional Ethernet (Modbus/TCP, basic type only), RS485 and DCS-LCS communication are listed by the manufacturer.
05How do I order YS1700?
Send Seven Star LLC the full model and suffix code from the nameplate, the quantity and delivery location. We will confirm and quote in writing.


















Reviews
There are no reviews yet.