Brand: AMETEK
AMETEK 7000-815-TE WDG-V RTD Combustibles Detector Kit
Description
AMETEK 7000-815-TE overview
AMETEK 7000-815-TE is the replacement combustibles detector kit, RTD type, for the Thermox WDG-V analyzer versions that measure combustibles. The WDG-VC datasheet states that the analyzer is SIL 2 compliant for excess oxygen and for combustibles when the RTD catalytic detector is used, which makes the RTD kit the safety-relevant combustibles sensor in that family. The AMETEK listing describes the product as a replacement kit for the WDG-V combustibles detector, RTD. The manual spare parts list marks it with an asterisk and gives the number 7000-815-TE next to the hot wire alternative.
The Thermox WDG-VC measures excess oxygen and combustibles (CO plus H2) in flue gas, and the WDG-VCM adds methane. The datasheet states that the analyzers are SIL 2 compliant for excess oxygen and for combustibles with the RTD catalytic detector, and capable for use in SIS combustion safety systems. The combustibles range is 0-500 ppm to 0-10,000 ppm with 0-2000 ppm as standard.
Key features of 7000-815-TE
- RTD catalytic combustibles detector kit for WDG-VC and WDG-VCM
- Used for the SIL 2 compliant combustibles measurement described in the datasheet
- Wires: white with red stripe to Cact, plain white to Cref
- Two 4.0 mm hex screws hold the detector in the heater block
- Always installed with a new o-ring according to the manual
- Hot wire alternative is a separate number, 7002-426-TE
7000-815-TE technical specifications
| Item | Detail |
|---|---|
| Part number | 7000-815-TE |
| Description | Kit, RTD combustible detector, WDG-V |
| Detector type | RTD catalytic detector |
| Combustibles range (WDG-VC datasheet) | 0-500 ppm to 0-10,000 ppm, 0-2000 ppm standard |
| Accuracy (datasheet) | Plus or minus 2 percent of full scale or plus or minus 40 ppm, whichever is greater |
| Response (datasheet) | 90 percent of a step change in less than 25 seconds with flame arrestors |
| Principle (datasheet) | Zirconium oxide for O2, catalytic detectors for combustibles |
| O2 output range | 0-1 percent to 0-100 percent |
| Combustibles range | 0-500 ppm to 0-10,000 ppm, 0-2000 ppm standard |
| Combustibles accuracy | Plus or minus 2 percent of full scale or plus or minus 40 ppm, whichever is greater |
| Combustibles response | 90 percent of a step change in under 25 seconds with flame arrestors |
| Outputs | Three isolated linear current outputs, five alarms, Modbus RTU |
| Max sample dew point | 200 degrees C (392 degrees F) |
| Enclosure | Hinged IP65 (NEMA 4X) stainless steel |
Values marked as datasheet come from the AMETEK Process Instruments product data sheet for the analyzer family, and parts information comes from the AMETEK parts listing for 7000-815-TE. Always check the nameplate and serial number of the installed analyzer, because options change from unit to unit.
Typical applications in oil and gas, utilities, water and manufacturing
The datasheet lists process heaters, steam boilers and thermal oxidizers, serving refining and petrochemical, power and steam generation, and furnaces and boilers. In Oman and the GCC the combustibles measurement is valued on fired heaters and boilers where a rise in CO plus H2 signals incomplete combustion and an excess-oxygen measurement alone is not enough for burner management.
Where 7000-815-TE is used on utilities, water or manufacturing sites, the common thread is a measurement that has to stay available between shutdowns. A spare held on the shelf turns a long outage into a short maintenance task.
Selection and compatibility notes for 7000-815-TE
Confirm whether the analyzer is a WDG-VC (combustibles) or WDG-VCM (combustibles and methane), and whether it uses an RTD or hot wire combustibles detector, because the detector type changes the kit, the wiring colours and the main processor board.
Part number 7000-815-TE is an exact orderable number in the AMETEK parts listing. Do not substitute by description alone: neighbouring numbers differ by supply voltage, detector type, or analyzer model, and a part that looks similar can be wrong for the unit. If the nameplate or an old purchase order shows a different number, send it to us and we will help to cross-check against the listing.
Installation and commissioning
Per the manual, disconnect the combustibles detector wires from the Cact and Cref terminal block on the sensor board. For an RTD detector the white wire with a red stripe goes to Cact and the plain white wire goes to Cref. Loosen the two 4.0 mm hex screws that hold the detector in its housing, remove it and keep the screws, then fit 7000-815-TE aligned on the two screw positions of the heater block with a new o-ring. Tighten until the face is flush with the block and the gasket is fully compressed, taking care not to damage the element ends, and reconnect the leads.
Always follow the manufacturer service manual, site permit-to-work and electrical isolation practice when fitting 7000-815-TE. Wear suitable protective equipment around hot analyzer components, and record the new part number, date and calibration results in the maintenance log.
Maintenance and service life
The analyzer tracks detector age and shows a Comb Detector Life Nearing Its End message based on calibration history. The manual notes the combustibles detector faces outward and the methane detector faces inward from the factory.
Related products and ordering notes
Check 7001-226-TE combustibles block kit, 3000-337-JE Kalrez o-ring for the detector housing and 1000-630-JE box temperature RTD for combustibles units.
For a spare parts plan, list 7000-815-TE against the analyzer tag number, record the serial number of the unit and note the date of the last replacement. A short register of this kind lets the next planner see at a glance whether the item is due, and it makes an RFQ faster because the exact number, quantity and analyzer details are ready to send.
Operators in Oman and the Gulf work in high ambient temperatures, dust and humidity, and sites often plan turnarounds months ahead, so confirming the exact number of every spare before the shutdown window is valuable. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer, and we handle enquiries for hard-to-find and legacy numbers directly.
Frequently asked questions about 7000-815-TE
- What is AMETEK 7000-815-TE? It is the replacement RTD combustibles detector kit for the Thermox WDG-V analyzer versions that measure combustibles.
- Is 7000-815-TE a hot wire detector? No. It is the RTD type. The manual lists the hot wire detector kit separately, and AMETEK lists 7002-426-TE as the replacement for the earlier hot wire number 7000-816-TE.
- Which wires go where on 7000-815-TE? For an RTD detector the manual says the white wire with a red stripe goes to Cact and the plain white wire goes to Cref.
Documents and quotation
The manufacturer datasheet for the analyzer family is attached to this page where the file is available, and it gives the performance data quoted above. To request pricing and lead time for AMETEK 7000-815-TE, send the RFQ with the part number 7000-815-TE, the quantity, the analyzer model and serial number if known, and your delivery location in Oman or the GCC. Seven Star LLC will reply with availability.
Datasheets & Documents
- Datasheet AMETEK WDG-VC Combustion Flue Gas Analyzer Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
AMETEK is the American maker of electronic instruments and electromechanical devices, headquartered in Berwyn, Pennsylvania. It was founded in 1930 as American Machine and Metals. In process industries it is known through brands such as Western Research (sulfur recovery and H2S analysers), Thermox (oxygen analysers), Land (pyrometers), Drexelbrook (RF level) and Chandler Engineering.
Seven Star LLC is an independent supplier in Muscat. We list AMETEK process analysers, pyrometers, portable testers and spare parts, and supply them to gas plants, refineries and power stations in Oman and the GCC.
AMETEK company profile
| Established | 1930, USA, as American Machine and Metals; later renamed AMETEK |
|---|---|
| Headquarters | Berwyn, Pennsylvania |
| Structure | Two groups: Electronic Instruments (EIG) and Electromechanical (EMG) |
| Process brands | Western Research, Thermox, Land, Drexelbrook, Chandler Engineering, Ranarex |
Milestones
- 1930: American Machine and Metals is formed in March and listed on the New York Stock Exchange as AME.
- Early 1960s: The company is renamed AMETEK.
- 2021: AMETEK acquires Magnetrol.
AMETEK products we list
| Product | Type | Typical use |
|---|---|---|
| 888, 900, 930 | Western Research sulfur recovery analysers | Tail gas, air demand and H2S in sulfur pits on Claus units |
| 931, 933, 9900RM/WM | UV gas analysers | H2S in natural gas and multi-component process streams |
| 5000, 3050-OLV, 5100HD, 5100P | Moisture analysers | Water content in natural gas and process gases; the 5100 models use TDLAS |
| 241CE II, Chanscope II / Model 13 | Dew point analysers and testers | Hydrocarbon and water dew point of natural gas |
| WDG 1200/1210, WDG-V, TM2000 | Thermox oxygen analysers | Combustion control on heaters and boilers, and trace oxygen |
| SPOT+, Cyclops L | Land pyrometers | Non-contact temperature of furnaces, kilns, tubes and hot metal |
| 120HD, Ranarex, Drexelbrook RCT-1210 | Portable analysers and level | Hydrogen purity in generators, gas specific gravity, RF level measurement |
Most of these analysers work on light absorption. UV analysers such as the 933 and 9900 measure H2S and SO2 by their absorption bands, and tail gas analysers use this to keep the H2S to SO2 ratio near 2:1 for the best Claus conversion. TDLAS moisture analysers use a tuned laser on a single water line, so they respond fast and do not suffer from the glycol and methanol contamination that affects sensor-based analysers.
Where AMETEK instruments are used
In Oman and the GCC, AMETEK analysers run on gas processing and sulfur recovery units, gas pipelines and custody points, refinery heaters and boilers, power station generators and steel and cement furnaces.
Ordering AMETEK products: what we need
Send the model and the complete part or sales order number from the nameplate. For a new analyser, send the gas composition, the component and range to be measured, the sample pressure and temperature, and the hazardous area classification. For spare parts, send the part number and the analyser serial number.
Facts checked against AMETEK company history, October 2026.
Browse AMETEK products by category: Gas Analyzer Accessories, Gas Analyzer Systems, Liquid Analytical Accessories, Level Transmitter.
FAQ
Questions about the AMETEK 7000-815-TE WDG-V RTD Combustibles Detector
Answers from our engineering team on installation, compatibility and integration.
01What is AMETEK 7000-815-TE?
It is the replacement RTD combustibles detector kit for the Thermox WDG-V analyzer versions that measure combustibles.
02Is 7000-815-TE a hot wire detector?
No. It is the RTD type. The manual lists the hot wire detector kit separately, and AMETEK lists 7002-426-TE as the replacement for the earlier hot wire number 7000-816-TE.
03Which wires go where on 7000-815-TE?
For an RTD detector the manual says the white wire with a red stripe goes to Cact and the plain white wire goes to Cref.
04Why is the RTD detector important for safety?
The WDG-VC datasheet says the analyzer is SIL 2 compliant for combustibles when the RTD catalytic detector is used.
05How do I request a quotation for 7000-815-TE?
Send the part number 7000-815-TE, the quantity and your delivery location to Seven Star LLC, and we will respond with availability.


















Reviews