Schneider Electric ABL8WPS24200 Phaseo 24 V DC 20 A 3-Phase

Description

ABL8WPS24200 24 V DC 20 A power supply fed from a three-phase line

The ABL8WPS24200 is a Schneider Electric product listed in the datasheet as: Regulated switch power supply, modicon power supply, 3 phases, 380 to 500V AC, 24V, 20A. The ABL8WPS24200 is a regulated switch-mode power supply that converts a three-phase 380 to 500 V AC input into 24 V DC at 20 A (480 W). Three-phase input balances the load on the line and avoids the large single-phase current of an equivalent single-phase unit. Seven Star LLC supplies the ABL8WPS24200 in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference: ABL8 is the Phaseo regulated supply series, W marks the three-phase input version, PS the power supply type, 24 the output voltage in volts and 200 the output current of 20.0 A.

Technical specifications of the ABL8WPS24200

Parameter Specification
Manufacturer / part number Schneider Electric / ABL8WPS24200
Description Regulated switch power supply, modicon power supply, 3 phases, 380 to 500V AC, 24V, 20A
Range of Product Modicon Power Supply
Product or Component Type Power supply
Power supply type Regulated switch mode
Nominal input voltage 380 to 500 V AC three phase L1, L2, L3
Rated power in W 480 W
Output voltage 24 V DC
Power supply output current 20 A
Permissible temporary current 1.5 x In for 4 s
Anti-harmonic filter Low frequency harmonic currents
Efficiency at full load 320 to 550 V AC
Inrush current 25 A
Power factor 0.65 at 24 V DC
Efficiency 92 %
Output voltage adjustment 24 to 28.8 V adjustable
Power dissipation in W 38.4 W
Provided equipment Power factor correction filter IEC 61000-3-2
Output protection type Against overload, protection technology: manual or automatic reset; Against overvoltage, protection technology: 30 to 32 V, manual reset
Connections – terminals Removable screw terminal block 2 x 2.5 mm², diagnostic relay; Screw type terminals 3 x 0.5 to 3 x 4 mm², 22 AWG–12 AWG input connection
Status LED 1 LED (green and red) output voltage; 1 LED (green, red and orange) output current
Depth 160 mm
Height 143 mm
Width 96 mm
Net Weight 1.6 kg
Output coupling Series; Parallel
Mounting support 35 x 7.5 mm symmetrical DIN rail; 35 x 15 mm symmetrical DIN rail
Operating position Vertical
Supply SELV IEC 60950-1; SELV IEC 60204-1; SELV IEC 60364-4-41
Dielectric strength 3500 V with between input and ground; 4000 V with between input and output; 500 V with between output and ground
Standards CSA C22.2 No 60950-1; UL 508; EN/IEC 62368-1
Product certifications CCSAus; EAC; UL; RCM
Environmental characteristic EMC conforming to IEC 61000-6-1; EMC conforming to IEC 61000-6-3; EMC conforming to EN 55024; EMC conforming to IEC 61000-6-4
Operating altitude 2000 m
IP degree of protection IP20 conforming to IEC 60529
Ambient air temperature (operation or storage, as listed) 50 to 60 °C with derating factor mounting position A < 6561.68 ft 2000
operation m; -25 to 50 °C without derating mounting position A < 2000 m

Input, output and protection of the ABL8WPS24200

Input: 380 to 500 V AC three phase L1, L2, L3. Rated power: 480 W. Output voltage: 24 V DC. Output current: 20 A. Efficiency: 320 to 550 V AC. Adjustment: 24 to 28.8 V adjustable. Inrush current: 25 A. Output protection: Against overload, protection technology: manual or automatic reset; Against overvoltage, protection technology: 30 to 32 V, manual reset. Overload: 1.5 x In for 4 s.

The output can be adjusted above 24 V to compensate for cable drop on long runs, and units can be paralleled for capacity or redundancy where the datasheet permits. A temporary overload margin lets the supply start loads with high inrush such as contactor banks.

Lifecycle and replacement planning for the ABL8WPS24200

The datasheet carries lifecycle notices, so this unit mainly matters for replacement in panels that already use it. Check the successor series and confirm physical size and terminal layout before substituting.

For redundancy, add a diode or redundancy module and parallel two supplies; for a single supply feeding a PLC rack and field devices, consider a separate supply for the field side.

The datasheet downloaded for this page carries lifecycle notices: Discontinued on: Dec 31, 2025; To be end-of-service on: Dec 31, 2026. For a plant that already runs this reference that makes the ABL8WPS24200 a spare-and-replacement item, and it is worth fixing the stock level and the long-term successor plan at the same time. We can discuss compatible alternatives once we know the installation.

Selection checklist for the ABL8WPS24200

  • Total 24 V DC load plus margin: 20 A rating at 480 W.
  • Three-phase supply availability: 380 to 500 V AC.
  • Operating temperature and derating.
  • Parallel or redundant arrangement.
  • Breaker or fuse on the input.
  • Mounting space: width 96 mm.

Installing and checking the ABL8WPS24200

Mount vertically on rail, leave spacing above and below for convection, connect the three phases and earth, then the 24 V DC output. Set the output voltage and test with a load.

Measure ripple and voltage at the farthest load, check the status LEDs, and verify at commissioning that the input protection trips correctly.

Typical applications of the ABL8WPS24200 in Oman and the GCC

Industrial panels with many I/O, drives control and instrumentation in oil and gas and process plants in the region. Heat in panels reduces capacity, so size with margin.

Dimensions, environment and approvals of the ABL8WPS24200

For the ABL8WPS24200, plan the mounting space from the datasheet: 96 mm (W) x 143 mm (H) x 160 mm (D). The ABL8WPS24200 weighs 1.6 kg. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.

Ambient temperature limits in the datasheet: 50 to 60 °C with derating factor mounting position A < 6561.68 ft 2000. Ingress protection: IP20 conforming to IEC 60529. Operating altitude: 2000 m. Standards listed: CSA C22.2 No 60950-1; UL 508; EN/IEC 62368-1. Certifications listed for this reference: CCSAus; EAC; UL; RCM.

Information to send with an RFQ for the ABL8WPS24200

  • Full reference and quantity required
  • Existing equipment, panel or rack it must fit
  • Supply voltage, load or signal details of the application
  • Required delivery location and timing
  • Whether a spare, a replacement or a new installation

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric ABL8WPS24200 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric ABL8WPS24200 Phaseo 24 V DC 20 A

Answers from our engineering team on installation, compatibility and integration.

01What output does the ABL8WPS24200 provide?
The datasheet gives 20 A at 24 V DC.
02What input does it need?
Input: 380 to 500 V AC three phase L1, L2, L3.
03What is its efficiency?
Stated as 320 to 550 V AC.
04Can the voltage be adjusted?
Datasheet: 24 to 28.8 V adjustable.
05What is its width?
The width is 96 mm.