Brand: Schneider Electric
Schneider Electric BMXCPS2000 X80 Power Supply 100-240 V AC
Description
BMXCPS2000 Modicon X80 power supply module: what it is and how the code reads
The BMXCPS2000 is a Schneider Electric product described in the datasheet as: power supply module, Modicon X80, 100 to 240V AC, 20W. The BMXCPS2000 is the Modicon X80 power supply module for a standard rack, converting 100 to 240 V AC into the rack voltages and a 24 V DC sensor supply. Seven Star LLC supplies the BMXCPS2000 in Oman and the GCC as an independent supplier based in Muscat.
Decoding the reference: BMX is the M340 / X80 platform, CPS the power-supply module type, and 2000 the AC input, 20 W model. The datasheet title gives power supply module, Modicon X80, 100 to 240V AC, 20W.
Technical specifications of the BMXCPS2000
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / BMXCPS2000 |
| Description | power supply module, Modicon X80, 100 to 240V AC, 20W |
| Range | Modicon X80 |
| Product type | Power supply module |
| Backplane compatibility | Not compatible with BMEXBP..02 |
| Primary voltage | 100 to 240 V |
| Supply circuit type | AC |
| Primary voltage limit | 85 to 264 V |
| Network frequency | 50/60 Hz |
| Network frequency limits | 47 to 63 Hz |
| Apparent power | 0.07 kVA |
| Input current | 0.31 A 240 V; 0.61 A 115 V |
| Inrush current | 30 A 120 V; 60 A 240 V |
| Secondary power | 10.8 W 24 V DC sensor power supply; 16.8 W 24 V DC I/O module power supply and processor; 8.3 W 3.3 V DC I/O module logic power supply |
| Current at secondary voltage | 0.45 A 24 V DC sensor power supply; 0.7 A 24 V DC I/O module power supply and processor; 2.5 A 3.3 V DC I/O module logic power supply |
| Maximum power dissipation | 8.5 W |
| Protection | Internal fuse not accessible primary circuit; Overload protection secondary circuit; Overvoltage protection secondary circuit; Short-circuit protection secondary circuit |
| MTBF | 4638000 H |
| Immunity to microbreaks | 1 ms |
| Electrical connection | 1 connector 2 alarm relay; 1 connector 5 line supply, protective earth, 24 V DC input sensor |
| Status LED | 1 LED (Green) rack voltage OK; 1 LED (Green) sensor voltage |
| Control | RESET push-button cold restart |
| Dielectric strength | 1500 V primary/secondary I/O module logic power supply; 1500 V primary/secondary I/O module power supply and processor; 2300 V primary/secondary sensor power supply; 1500 V primary/ground |
| Net weight | 0.3 kg |
| Degree of protection | IP20 |
| Operating temperature | 0 to 60 °C |
| Operating altitude | 0 to 2000 m; 2000 to 5000 m with derating factor |
How the BMXCPS2000 powers the rack
The module takes an AC primary of 100 to 240 V (limits 85 to 264 V) at 50/60 Hz and produces regulated supplies for the rack logic and I/O. The datasheet lists a secondary power of 10.8 W 24 V DC sensor power supply; 16.8 W 24 V DC I/O module power supply and processor; 8.3 W 3.3 V DC I/O module logic power supply.
Inrush is 30 A 120 V; 60 A 240 V at switch-on, so the upstream breaker must tolerate it. Protection includes Internal fuse not accessible primary circuit; Overload protection secondary circuit; Overvoltage protection secondary circuit; Short-circuit protection secondary circuit, and the datasheet lists an alarm relay output wired to a connector for monitoring.
Where the BMXCPS2000 fits in an X80 rack
The module mounts in the leftmost slot of the rack and feeds the processor and the I/O modules through the backplane. Check that it is compatible with the backplane type: the datasheet states Not compatible with BMEXBP..02. A processor such as BMXP342020 and an input module such as BMXDDI1602 are typical neighbours.
If the I/O population is large, add up the 3.3 V and 24 V loads of all modules against the module’s secondary current ratings before ordering, and consider a second rack with its own supply.
Selection and ordering checklist for the BMXCPS2000
- Primary supply: 100 to 240 V AC only; confirm site voltage and frequency.
- Sum the current of all modules in the rack against the secondary ratings.
- Backplane compatibility as stated above.
- Alarm relay wiring and reset behaviour.
- Breaker and cable sizing for inrush.
- Spare module holding for critical racks.
Installation, commissioning and maintenance of the BMXCPS2000
Mount the supply in the first slot of the rack, secure it and connect the line, protective earth and alarm relay at the connectors. The module weighs 0.3 kg and dissipates up to 8.5 W. Power the rack, verify that the rack-voltage and sensor-voltage LEDs are on, and test the alarm relay.
Maintenance involves checking the LEDs at routine rounds, keeping vents clear and dusting the rack. A supply is a common cause of unexplained rack resets, so verify AC quality when faults recur. Do not open the module; the primary fuse is internal and not accessible.
Typical applications of the BMXCPS2000 in Oman and the GCC
The BMXCPS2000 powers X80 racks in process utilities, water and wastewater, oil and gas and building plants across Oman and the GCC. Because supplies age with heat, a spare unit is a cheap insurance for racks that cannot be shut down.
Information to send with an RFQ for the BMXCPS2000
- Full reference BMXCPS2000 and quantity
- Rack type and backplane
- Number and type of modules in the rack
- Site supply voltage
- Delivery location and timing
Site conditions in Oman for the BMXCPS2000
Electrical rooms and outdoor panels in the Gulf often operate well above the 25 °C reference temperature used in many catalogues. Before you finalise the BMXCPS2000, compare the expected panel temperature with the operating range and any output derating stated in the manufacturer documentation, and leave the recommended clearance above and below the device for convection. Supply quality also varies between sites, so confirm the input voltage range, frequency and any requirements for protection on the supply side.
Where the device feeds or monitors critical loads, plan how faults will be signalled to the control system and how a replacement can be installed quickly. Keeping one spare BMXCPS2000 per site and recording its settings helps maintenance teams in Oman restore service with minimum downtime.
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.
Other Models in the Se Bmx Range
Seven Star LLC supplies models from the Se Bmx range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric BMXP342020 M340 Processor Module | PLC & I/O Cards | View details |
| Schneider Electric BMXCPS2000 X80 Power Supply 100-240 V AC | Power Modules | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric BMXCPS2000 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric BMXCPS2000 X80 Power Supply
Answers from our engineering team on installation, compatibility and integration.
01What AC supply does the BMXCPS2000 accept?
The datasheet lists 100...240 V with limits 85...264 V.
02How much power does the BMXCPS2000 deliver?
It lists 10.8 W 24 V DC sensor power supply; 16.8 W 24 V DC I/O module power supply and processor; 8.3 W 3.3 V DC I/O module logic power supply.
03What inrush current does the BMXCPS2000 have?
30 A 120 V; 60 A 240 V.
04Is the BMXCPS2000 compatible with every backplane?
The datasheet states: Not compatible with BMEXBP..02.
05What temperature range does the BMXCPS2000 cover?
0…60 °C.