The Phoenix Contact CBMC E4 24DC/1-10A IOL (order no. 2910411) takes the four-channel CBMC electronic circuit breaker and adds an IO-Link interface. Like the N/O-contact version it protects four 24 V DC branches with settable nominal currents from 1 A to 10 A, but instead of one collective relay contact it talks to an IO-Link master over a standard three-wire sensor cable. The designation reads CBMC for the family, E4 for four electronic channels, 24DC for the nominal voltage, 1-10A for the setting range, and IOL for IO-Link. Through the interface a controller can read channel status and load values and set parameters remotely, which is valuable when the cabinet is far from the control room.

Seven Star LLC supplies this device as an independent supplier in Muscat for customers across Oman and the GCC.

Technical specifications of the CBMC E4 24DC/1-10A IOL

Parameter Specification
Manufacturer / part number Phoenix Contact CBMC E4 24DC/1-10A IOL (order no. 2910411)
Product family CBMC, DIN-rail module, one piece, 4 channels, IO-Link
Operating voltage 18 V DC … 30 V DC
Rated current per channel 1 to 10 A DC in 1 A steps; pre-adjusted 4 A
Maximum input current max. 40 A; derating 36 A at 41 °C, 32 A at 47 °C, 28 A at 54 °C, 24 A at 60 °C
Short-circuit switching capacity 300 A
Fail-safe element 15 A DC per output channel
Shutdown time ≤ 10 ms above 2.0 x IN; 1 s at 1.2 to 2.0 x IN
Maximum capacitive load 40000 μF, depending on current setting and short-circuit current
IO-Link specification V1.1, 230.4 kbps (COM3), min. cycle time 40 ms
Process data 8 bytes input, 3 bytes output
IO-Link identifiers Vendor ID 176 (00B0 hex); Device ID 393504 (060120 hex)
IO-Link supply 24 V DC, max. 30 mA at L+, reverse polarity protected
Dimensions (W x H x D) 36 x 90 x 98 mm including DIN rail
Ambient temperature, operation -25 °C to 60 °C
Listings shown for this device UL/C-UL Listed UL 508, UL Recognized UL 2367

How the CBMC E4 24DC/1-10A IOL protects each output channel

The power stage behaves like the other CBMC E4 modules: each channel is monitored separately, an overload of 1.2 to 2.0 times nominal is switched off after 1 second, and a short circuit above twice nominal is cleared in 10 ms or less, followed by a 5 second wait. What changes is the communication side. The IO-Link port has its own push-in terminal, accepts a 24 V DC supply with reverse-polarity protection and draws at most 30 mA. It exchanges 8 bytes of input process data and 3 bytes of output process data, so a PLC can see more than a simple on or off state, and a green flashing IO-Link LED confirms an active connection.

The front LEDs remain fully functional, so local technicians do not depend on the fieldbus. The manufacturer also states that the product is being prepared for the EU Cyber Resilience Act, which is worth noting if your project has cybersecurity documentation requirements.

Where the CBMC E4 24DC/1-10A IOL fits in a 24 V DC system

This module is intended for cabinets that already use IO-Link masters, for example on remote I/O stations in water pumping, compressor and packaging-style skid systems. It lets a single IO-Link port deliver diagnostic information from the protection layer without extra wiring to digital inputs. If the plant has no IO-Link infrastructure, the NO versions 2906032 (1-10 A) and 2906031 (1-4 A) are simpler. For installations that also need a reset input and a status output at the front, the CBM E4 24DC/0.5-10A NO-R (2905743) is the related design.

Selection and ordering checklist

  • Confirm that an IO-Link master and its parameter tool are available in the control system.
  • Check the IO-Link device description requirements using the Vendor and Device IDs above.
  • Confirm all branches are 10 A or less and the total is within the 40 A input and derating curve.
  • Check capacitive loads against the 40000 μF limit.
  • Plan a separate 24 V DC feed for the IO-Link L+ line.
  • Decide whether a hard-wired alarm to the PLC is also needed as a back-up.

Installation, commissioning and maintenance

Mount the module on a 35 mm rail and wire the supply, the four loads and the IO-Link line using the push-in terminals. Remember that the negative pole must be connected to IN- so the internal electronics are powered. After power-up, wait for module initialisation of about 1.6 s before expecting channel output. Set the initial current values locally or through IO-Link, lock them, and then check each channel against its real load. When an IO-Link connection is established, the dedicated LED flashes green; no light means there is no communication.

For service, keep a record of the parameter set so a replacement module can be configured identically. The channel LEDs make a field diagnosis possible even when the master is offline.

Typical applications in Oman and the GCC

In Oman and the GCC, remote-monitored panels are common at wellhead pads, booster stations, water transfer pumping stations and unmanned electrical substations, where site visits are costly and a trip should be visible to the control room immediately. Using IO-Link status from the breaker means the operator can distinguish a tripped sensor circuit from a lost supply. The 60 °C operating limit and the derating table make it important to ventilate or shade outdoor enclosures in summer conditions.

Comparison with sibling devices

Device Distinguishing data
CBMC E4 24DC/1-10A IOL (2910411) 1-10 A, IO-Link V1.1, 40000 μF, no relay contact
CBMC E4 24DC/1-10A NO (2906032) 1-10 A with N/O contact, 45000 μF
CBMC E4 24DC/1-4A NO (2906031) 1-4 A, 16 A input, N/O contact
CBM E4 24DC/0.5-10A NO-R (2905743) 0.5-10 A, reset and status connections, DNV listing

Information to send with an RFQ

  • Full part number and quantity.
  • IO-Link master type and version.
  • Number of branches and currents.
  • Panel ambient temperature.
  • Required approvals.
  • Delivery location and date.

Documents and quotation

Send us the part number CBMC E4 24DC/1-10A IOL and the quantity you need, and we will confirm which official documents are available for this device. Seven Star LLC is an independent supplier in Muscat and quotes for projects across Oman and the GCC; we do not act on behalf of the manufacturer.

Please also tell us the delivery location and required timeline so that availability can be checked before you commit to a project schedule.

Other Models in the Phoenix Cbmc E4 Range

Seven Star LLC supplies models from the Phoenix Cbmc E4 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Phoenix Contact CBMC E4 24DC/1-10A NO Circuit BreakerPower ModulesView details
Phoenix Contact CBMC E4 24DC/1-4A NO Circuit BreakerPower ModulesView details
Phoenix Contact CBMC E4 24DC/1-10A IOL IO-Link BreakerPower ModulesYou are viewing this model
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Phoenix Contact is a German, family-owned manufacturer of electrical connection technology and industrial automation, founded in 1923 in Essen by Hugo Knümann. It began as a sales company, and in 1928 Knümann developed the modular terminal block mounted on a rail, the product the company is still best known for. Phoenix Contact is headquartered in Blomberg, North Rhine-Westphalia.

Seven Star LLC lists Phoenix Contact surge protection, power supplies and safety relays, and sources these components by order number for panel builders and maintenance teams in Oman.

Phoenix Contact company profile

Founded 1923, Essen, Germany, by Hugo Knümann, as Phönix Elektro- und Industrie-Bedarfsgesellschaft
Headquarters Blomberg, Germany
Ownership Family-owned (Eisert and Stührenberg families)
Key invention The modular terminal block on a DIN rail, 1928
Product families CLIPLINE terminal blocks, PCB terminals and connectors, QUINT and TRIO power supplies, relay modules, surge protection, signal conditioners, Ethernet switches and PLCnext controllers

Milestones

  • 1923: Hugo Knümann founds the company in Essen.
  • 1928: The first modular terminal block is developed.
  • Later: Headquarters move to Blomberg, Ostwestfalen-Lippe.

Phoenix Contact parts listed on this page

The TTC-6-2X1-24DC-UT (order number 2906799) is a surge protection device with screw connection for two 24 V DC signal wires that share a common reference potential. The QUINT-PS/1AC/24DC/10 is a single-phase DIN rail power supply delivering 24 V DC at 10 A. The PSR-SCP-24DC/ESP4/2X1/1X2 (order number 2981020) is a single-channel PSR safety relay for emergency stop and safety door monitoring, with two enabling current paths and plug-in screw terminals.

Phoenix Contact products we list

Family Examples
Isolator & Barrier 2906799 TTC-6-2X1-24DC-UT Surge Protector, MACX MCR-EX-SL-RPSSI-I Signal Isolator, MINI MCR-2-UI-UI 3-Way Signal Conditione…, PLT-SEC-T3-230-FM Type 3 Surge Protectio…
Power Modules QUINT-PS/1AC/24DC/10 QUINT Power Supply, QUINT4-PS/1AC/24DC/10 Power Supply, TRIO-PS-2G/1AC/24DC/10 Power Supply, UNO-PS/1AC/24DC/100W Power Supply
Automation Accessories PLC-RSC-24DC/21 Relay Module, PSR-SCP-24DC/ESP4/2X1/1X2 Safety Relay (…

Ordering Phoenix Contact components: what we need

Phoenix Contact items are ordered by a seven-digit order number together with the type designation, both printed on the side of the module. Send both, plus the quantity. If the number is unreadable, send the type text and a photo. For power supplies, state input voltage, output current and whether the unit runs in parallel or with a redundancy module. For buyers in the GCC replacing an older unit, we check the manufacturer's documentation for the listed successor type.

Facts checked against Phoenix Contact's own company history (phoenixcontact.com), October 2026.

FAQ

Questions about the Phoenix Contact CBMC E4 24DC/1-10A IOL IO-Link

Answers from our engineering team on installation, compatibility and integration.

01What does the IOL version add compared with the NO version?
It replaces the N/O remote-indication contact with an IO-Link V1.1 interface at 230.4 kbps, with 8 bytes of input and 3 bytes of output process data.
02What are its IO-Link identifiers?
Vendor ID 176 (00B0 hex) and Device ID 393504 (060120 hex).
03What supply does the IO-Link side need?
A 24 V DC I/O supply, with reverse-polarity protection and a current consumption of at most 30 mA at IO-Link L+.
04How are overloads and short circuits handled?
Overloads of 1.2 to 2.0 times nominal switch the channel off after 1 s, and short circuits above 2.0 times nominal in 10 ms or less, with a 5 s wait before restart.
05What is the maximum total current?
Up to 40 A at IN+, with derating from 36 A at 41 degrees C down to 24 A at 60 degrees C.