Brand:

Danfoss 132H2225 VLT MCD 600 Soft Starter, 215 A

Description

Danfoss 132H2225 VLT Soft Starter MCD 600, 215 A

The Danfoss 132H2225 is a VLT Soft Starter MCD 600 rated 215 A, with the model code MCD60215CT5S2X00CV2. It is a non-bypassed (continuous connection) starter for three-phase supplies of 200 to 525 V AC, supplied in frame size 2 as an IP00 open-frame unit with a control supply of 110 to 120 V AC or 220 to 240 V AC. The MCD 600 combines soft start, soft stop, motor protection and communication options in one device, with a graphical display and a remote LCP option. Seven Star LLC supplies the 132H2225 in Oman and the GCC as an independent supplier in Muscat.

The “C” in the model code means the thyristors stay in circuit while the motor runs, which simplifies the power circuit because no bypass contactor is needed, but it changes the heat load of the cabinet, as explained below.

Decoding MCD60215CT5S2X00CV2

Code element Meaning
MCD6 VLT Soft Starter MCD 600 series
0215 Nominal current rating 215 A
C Non-bypassed, continuous connection (B would be internally bypassed)
T5 Mains voltage 200 to 525 V AC (T7 would be 380 to 690 V AC)
S2 Frame size 2
00 IP00, open frame (20 would be IP20)
CV2 Control voltage 110 to 120 V AC or 220 to 240 V AC (CV1 is 24 V AC/DC)

132H2225 technical specifications

Parameter Specification
Manufacturer / part number Danfoss 132H2225 (MCD60215CT5S2X00CV2)
Nominal current rating 215 A
Mains voltage 200 to 525 V AC (+/-10 percent), 50 to 60 Hz (+/-5 Hz)
Control voltage 110 to 120 V AC (+10/-15 percent) or 220 to 240 V AC (+10/-15 percent), 600 mA
Bypass None, continuous connection
Protection class IP00
Frame size 2
Net weight 12.7 kg (gross 13.5 kg)
Rated insulation voltage / impulse 690 V AC / 6 kV
Short-circuit coordination Type 2 with semiconductor fuses; type 1 with HRC fuses
Relay outputs 10 A at 250 V AC resistive, 5 A at 250 V AC AC-15 (pf 0.3)
Motor overload default Class 10, trip at 105 percent of FLA
Operating temperature -10 to +60 °C, derating above 40 °C
Altitude 0 to 1000 m, derating above 1000 m
Humidity / pollution degree 5 to 95 percent relative humidity / pollution degree 3
Heat dissipation About 4.5 W per ampere during start and run
EMC IEC 60947-4-2 Class B emissions
Marine Lloyd’s Marine No 1 specification applies to all models listed in the guide

Current ratings of 132H2225

The nominal 215 A applies to one specified duty. The Operating Guide expresses the rating in the AC-53a format, for example 3.5-15:50-6, meaning a start current of 3.5 times the full load current, a start time of 15 seconds, a 50 percent on-load duty cycle and 6 starts per hour. At lighter or heavier duty the usable current changes, so do not simply choose a starter equal to the motor nameplate current.

Installation 3.0-10:50-6 A 3.5-15:50-6 A 4.0-10:50-6 A 4.0-20:50-6 A 5.0-5:50-6 A
In-line 260 215 205 180 192
Inside delta 390 323 306 270 288

NEMA ratings in the guide for this model are 176 A (60 hp at 240 V, 125 hp at 480 V, 150 hp at 600 V) at normal duty (350 percent for 30 s, four starts per hour) and 143 A (50 hp at 240 V, 100 hp at 480 V, 150 hp at 600 V) at heavy duty (450 percent for 30 s, four starts per hour).

Heat and enclosure planning for a non-bypassed starter

At 4.5 W per ampere the 132H2225 dissipates about 0.97 kW when it is carrying 215 A, and the same figure applies during the run because the thyristors never bypass. For a bypassed version of similar size the run-time loss is a few hundred watts at most. A cabinet housing this starter in a hot plant room therefore needs forced ventilation or an air conditioner sized for roughly 0.97 kW plus the other equipment, and the manufacturer warns of derating above 40 °C. In Oman, where switchrooms commonly stay above 35 °C in summer, this is usually the deciding factor in choosing between B and C versions.

Functions that matter on pumps, fans and compressors

Beyond simple soft start the MCD 600 offers soft stop for pump-hammer reduction, current ramp, DC brake and soft brake, pump clean (a reverse and forward cycle), reverse-direction operation, jog and inside-delta operation, according to the contents of the Operating Guide. The starter also provides motor thermistor input, motor overload protection and excess start time protection. On pumps the soft-stop function is the feature most often used, because abrupt flow stoppage causes pressure surges in long discharge lines.

132H2225 within the MCD 600 family

Frame size 2 includes the 132H2224 (160 A, MCD6-0160C), the 132H2225 (215 A), the 132H2226 (275 A, MCD60275C), the 132H2227 (343 A) and the 132H2229 (448 A). Within this group the 132H2225 is the second smallest; always size it against the AC-53a table for the real start duty rather than by motor kW alone. Bypassed B-series starters and higher current C-series starters up to 1134 A complete the range.

Selection and ordering checklist

  • Motor full-load current at the start duty and supply voltage, to be matched or exceeded by the 215 A rating.
  • Start current multiple and start time of the load, plus the number of starts per hour.
  • Whether the inside-delta (six-wire) connection will be used, which raises the usable motor current as shown in the table.
  • Enclosure cooling for the continuous heat load, and IP00 protection by the panel.
  • Control voltage 110 to 120 V AC, 220 to 240 V AC or 24 V; this code is the CV2 version.
  • Fieldbus card (Modbus, PROFINET, EtherNet/IP, DeviceNet and others are separate options) and remote LCP.
  • Fuses: semiconductor fuses for type 2 coordination.

Installation and commissioning of the 132H2225

Mount vertically with the clearances shown in the Operating Guide, on a rigid plate, and run motor cables separately from control wiring using shielded cable to avoid induced voltages. Fit an isolating switch and a circuit-breaking device that can be opened from an external safety system, and press Off/Reset on the LCP before changing parameters, because the motor can start at any time while the starter is connected to mains. Use the Set-up Tools for first start and check the motor current limit, start ramp, stop mode and thermistor input before running under load.

Applications of the 132H2225 in Oman and the GCC

Typical applications are water-injection and seawater lift pumps, cooling-water pumps at power and desalination plants, fire-water jockey and main pumps, ventilation and process fans, and compressors at oil and gas sites. A non-bypassed starter such as the 132H2225 is easier to specify when the cabinet is air-conditioned and when contactor wear from frequent starts is a concern.

Information to send with an RFQ for 132H2225

  • Code 132H2225 and quantity.
  • Motor kW or hp, voltage, full-load current and starting torque requirement.
  • Load type and starts per hour.
  • Preferred fieldbus and any remote LCP requirement.
  • Enclosure and ambient data.

Documents and quotation

The Danfoss MCD 600 Operating Guide is attached on this page. It includes the type code, rating tables, specifications, wiring, parameter list and troubleshooting.

Send the code 132H2225 with your motor and duty data and we will confirm availability and a quotation for Oman and the GCC.

Other Models in the Danfoss Mcd600 Range

Seven Star LLC supplies models from the Danfoss Mcd600 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Danfoss 132H2225 VLT MCD 600 Soft Starter, 215 AMotor Soft StartersYou are viewing this model
Danfoss 132H2227 VLT MCD 600 Soft Starter, 343 AMotor Soft StartersView details
Datasheets & Documents
  • PDF Manual Danfoss 132H2225 Operating Guide Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.

Danfoss company profile

Founded 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966)
First product Thermostatic expansion valve for refrigeration
Headquarters Nordborg, Denmark
Ownership Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family
Size About 42,000 employees (2023)
Business segments Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics)
Brands in the group VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls

Milestones

  • 1932–1933: First expansion valve; the company is founded in Nordborg.
  • 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
  • 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
  • 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
  • 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
  • 2021: Acquisition of Eaton's hydraulics business.

Choosing Danfoss products

For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.

Where Danfoss products are used

In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.

Danfoss products we list

Family Examples
Variable speed drives and soft starters VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter
Solenoid valves and coils EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil
Pressure switches and thermostats KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101
Pressure transmitters MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2
HVAC and refrigeration valves AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element

Ordering Danfoss products: what we need

Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.

Frequently requested Danfoss models: Danfoss 132B0101 VLT Control Panel LCP 12.

Facts checked against Danfoss's company history pages and published company data, October 2026.

FAQ

Questions about the Danfoss 132H2225 VLT MCD 600 Soft Starter, 215 A

Answers from our engineering team on installation, compatibility and integration.

01What current rating does the Danfoss 132H2225 have?
It is an MCD 600 rated 215 A, model code MCD60215CT5S2X00CV2, non-bypassed, for 200 to 525 V AC mains.
02Does the 132H2225 have an internal bypass?
No. The C in the model code means non-bypassed, so the thyristors carry current continuously and dissipate about 4.5 W per ampere.
03What control voltage does it use?
CV2: 110 to 120 V AC or 220 to 240 V AC, 600 mA.
04What protection class is it?
IP00, an open-frame unit that must be mounted in a panel.
05What is the weight?
The product page gives a net weight of 12.7 kg.