Brand: Lovato Electric
Lovato ADXL0075600 Soft Starter 75 A with Bypass
Description
Lovato ADXL0075600 soft starter, 75 A with built-in bypass
The Lovato ADXL0075600 is a soft starter with a rated current of 75 A for three-phase asynchronous motors on 208 to 600 V AC supplies. It controls two phases, includes an internal bypass contactor, and offers torque-ramp, voltage-ramp and constant-torque starting with current limit. For a 400 V motor it corresponds to 37 kW, and at 500 V to 45 kW. Seven Star LLC supplies the ADXL0075600 in Oman and the GCC as an independent supplier in Muscat.
The code reads ADXL (family), 0075 (rated current in amperes) and 600 (maximum line voltage class). The catalogue also lists a code with 024 appended, ADXL007560024, so confirm the auxiliary supply voltage when ordering; the part here takes 100 to 240 V AC.
ADXL0075600 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Lovato / ADXL0075600 |
| Rated supply voltage | 208 to 600 V AC, 50/60 Hz, three-phase |
| Auxiliary supply | 100 to 240 V AC |
| Rated starter current Ie | 75 A |
| Motor power IEC (40 °C) | 22 kW at 230 V; 37 kW at 400 V; 45 kW at 500 V |
| Motor power UL (40 °C) | 25 HP at 220-240 V; 40 HP at 380-415 V; 50 HP at 440-480 V; 60 HP at 550-600 V |
| Controlled phases | 2 |
| Bypass | Built in |
| Start methods | Torque ramp, voltage ramp, constant torque, each with current limit |
| Stop methods | Torque ramp, voltage ramp, free-wheel |
| Interface | Backlit LCD, NFC programming, optical port, 6 languages |
| Digital inputs | 3 (2 dry contact, 1 dry contact or PTC) |
| Digital outputs | 2 x NO 3 A 250 V AC plus 1 changeover 5 A 250 V AC |
| Operating temperature | -20 to +60 °C, derate 0.5%/°C above 40 °C |
| Altitude | 1000 m without derating, 0.5%/100 m above |
| Degree of protection | IP00 |
| Dimensions and weight | 95 x 226 x 182 mm; 2.9 kg |
How the ADXL0075600 starts a motor
Instead of applying full voltage, the starter uses phase-controlled thyristors in two phases to ramp torque or voltage, while limiting current to a set value. This lowers mechanical shock on couplings and the pressure surge in pipelines, and reduces the starting current drawn from the generator or weak feeder. When the motor reaches speed the internal bypass closes and takes over the current, so the thyristors stop dissipating heat and the unit can be mounted in a compact enclosure.
The torque-control start suits centrifugal pumps, where the stop ramp prevents water hammer. The display and a kick-start function help with loads that need a short burst to break away, and dynamic braking is available for loads that need to stop faster than free-wheel.
Protections of the ADXL0075600
The starter protects the motor with an electronic overload that has trip classes 2, 10A, 10, 15, 20, 25, 30, 35 and 40 at start and 2 to 30 in run, plus locked rotor, current asymmetry, and minimum torque (dry-run) detection. It also monitors the supply for phase loss, phase sequence, frequency and voltage, and itself for overcurrent, overtemperature, bypass failure and shorted phase. A PTC input reads the motor thermistors, and an event log, hour counter and clock support maintenance.
Where the ADXL0075600 fits in the family
The starter sits in the ADXL range between the ADXL0045600 (45 A class) and the ADXL0135600 (135 A with forced cooling), and it relies on natural cooling, with forced cooling an option. It can be fixed by screws or on 35 mm DIN rail using the optional EXP8003 accessory. The 75 A size is a typical choice for 37 kW pumps.
ADXL0075600 selection and ordering checklist
- Motor nameplate current and voltage, compared with 75 A starter rating
- Start duty: starts per hour, load type and expected ramp time
- Control supply: 100 to 240 V AC for this code
- Altitude and ambient temperature, with derating from 40 °C
- Need for extra I/O, fieldbus or external keypad via expansion modules
- Back-up fuses or breaker per local code
Installation and commissioning of the ADXL0075600
The IP00 body means all live parts are open, so the starter must be installed inside a suitable enclosure with clearances for airflow. Use screw fixing or the DIN rail accessory. Program the motor current and ramp through the display, the optical port or NFC from a smartphone, then run the motor unloaded where possible. Check that the line contactor output from the starter is wired when a main contactor is used.
Typical ADXL0075600 applications in Oman and the GCC
37 kW motors drive process water pumps, sea-water lift pumps, fans, screw compressors and conveyors. Soft starting is valuable where long cable runs and weak grids make direct-on-line starts disturb other loads, and in hot enclosures the 0.5%/°C derating above 40 °C needs to be built into the design.
Weight and size are modest for a 37 kW starter: 2.9 kg and 95 x 226 x 182 mm. That makes it easy to retrofit into an existing motor control centre bucket where a star-delta starter once sat, provided the wiring is changed from six motor leads to three. Always size the upstream protection to the starter manual, and keep the auxiliary supply separate from the motor circuit so that the display and fault memory survive a voltage dip on the main feeder.
Information to send with an RFQ for the ADXL0075600
- Part number ADXL0075600 and quantity
- Motor kW, voltage and full-load current
- Load type and duty cycle
- Control voltage and I/O needs
- Panel ambient temperature and altitude
- Approval requirements
Site conditions in Oman for the ADXL0075600
Low-voltage switching and protection devices in Oman often sit in motor control centres and outdoor panels where internal temperatures are high for much of the year. When you select the ADXL0075600, check its rated values at your real ambient temperature, as stated in the manufacturer documentation, and confirm the coordination with upstream protection and with the motor or load it serves. Short-circuit levels differ from site to site, so verify the breaking capacity required at the point of installation.
Standardising ratings and coil voltages across a project reduces the number of spare part numbers that need to be stocked. Keeping a small stock of the ADXL0075600 and recording settings such as trip ranges or ramp times shortens repair work during a breakdown.
Documents and quotation
Send the part number ADXL0075600 and we will confirm the documents available for it, such as the technical data sheet, wiring diagram and instruction sheet, together with availability and lead time.
Seven Star LLC is an independent supplier in Muscat and is not an official channel of the manufacturer. Share the quantity, delivery location and project reference with the request and we will answer with a formal quotation.
Other Models in the Lovato Adxl Softstarter Range
Seven Star LLC supplies models from the Lovato Adxl Softstarter range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Lovato ADXL0075600 Soft Starter 75 A with Bypass | Motor Soft Starters | You are viewing this model |
| Lovato ADXL0060600 Soft Starter 60 A with Built-in Bypass | Motor Soft Starters | View details |
| Lovato ADXL0115600 Soft Starter 115 A with Built-in Bypass | Motor Soft Starters | View details |
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.
Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.
Lovato Electric at a glance
| Established | 1922, Bergamo, Italy |
|---|---|
| Headquarters | Gorle (Bergamo), Italy |
| Ownership | Private, family-run for four generations |
| Product families | Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs |
Lovato products we list
| Family | Models | Typical use |
|---|---|---|
| Contactors | BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing | Switching motors, heaters, lighting and capacitor banks |
| Motor protection and starters | SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay | Short-circuit and overload protection and direct starting of motors |
| Soft starters | ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 | Reducing starting current and mechanical shock on pumps, fans and compressors |
| Variable speed drives | VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 | Speed control of pumps, fans and conveyors to save energy |
| Power management and control | DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC | Power factor correction, mains/generator changeover and energy monitoring |
Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.
Where Lovato products are used
In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.
Ordering Lovato products: what we need
Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.
Facts checked against Lovato Electric company profile brochures, October 2026.
Browse Lovato Electric products by category: Motor Soft Starters, Automation Accessories, Controllers & Data Acquisition, PLC & I/O Cards, Circuit Breakers, Diesel Generator Spare Parts.
FAQ
Questions about the Lovato ADXL0075600 Soft Starter 75 A with Bypass
Answers from our engineering team on installation, compatibility and integration.
01What motor power does the ADXL0075600 handle?
It is rated for 75 A, which gives 22 kW at 230 V, 37 kW at 400 V and 45 kW at 500 V in the IEC table.
02Does the ADXL0075600 have a bypass?
Yes, an internal bypass is built in, so the unit does not dissipate thyristor heat once the motor is at speed.
03How is the ADXL0075600 programmed?
Through the backlit LCD and keypad, an optical port or by NFC; six languages are available.
04What start methods does it offer?
Torque ramp, voltage ramp and constant torque, each with current limit; stop by torque ramp, voltage ramp or free-wheel.
05What is its degree of protection?
IP00, so it must be installed in an enclosure.