Lovato ADXL0045600 45 A Soft Starter with Built-in Bypass

Description

ADXL0045600 soft starter: decoded part number

The ADXL0045600 is a 45 A soft starter from the Lovato Electric ADXL series with built-in bypass relay. It brings three-phase induction motors up to speed with a controlled ramp of torque or voltage, which reduces starting current and mechanical shock on pumps, fans, compressors and conveyors.

Decoded: ADXL is the soft starter series with a display and built-in bypass, 0045 is the rated current of 45 A and 600 is the voltage class for supplies up to 600 V AC. Sister models in the catalogue include ADXL0060600 for 60 A.

Technical specifications of the ADXL0045600

Parameter Specification
Manufacturer / part number Lovato Electric / ADXL0045600
Type Soft starter with integrated bypass, 2 controlled phases
Rated operational current Ie 45 A
Rated supply voltage 208 to 600 V AC, three-phase, 50 / 60 Hz
Auxiliary supply 100 to 240 V AC
Motor power in-line (IEC, 40 °C) 11 kW at 230 V; 22 kW at 400 V; 30 kW at 500 V
Motor power (UL) 15 HP at 220-240 V; 25 HP at 380-415 V; 30 HP at 440-480 V; 40 HP at 550-600 V
Starting methods Torque ramp, voltage ramp, constant torque, each with current limit
Stopping methods Torque ramp, voltage ramp, free-wheel stop
Digital inputs / outputs 3 inputs (one configurable as PTC) / 3 outputs (2 NO and 1 changeover)
Interface Backlit icon LCD, 6 languages, NFC, optical port
Functions Kick start, dynamic braking, torque control, event log, hour counter, start counter, clock-calendar
Operating temperature -20 °C to +60 °C; derate 0.5 % per °C above +40 °C
Altitude 1000 m without derating; derate 0.5 % per 100 m above
Protection class IP00
Dimensions (W x H x D) 75 mm x 218 mm x 171.5 mm
Weight 2.1 kg

Values are taken from the Lovato Electric catalogue entry for ADXL0045600. IP00 means the unit must be installed in an enclosure.

How the ADXL0045600 works

A soft starter uses thyristors to apply a gradually rising voltage to the motor. In the ADXL the ramp can be torque based, which gives smoother acceleration of loads such as centrifugal pumps, and the current limit protects the supply from large inrush. Two phases are controlled with thyristors; once the motor is at speed, the internal bypass relay shorts the thyristors, so heat loss and fan wear are small.

The protections include motor overload with selectable trip classes at start and in run, locked rotor, current asymmetry, minimum torque (dry-run), supply faults such as phase loss or sequence error, and starter faults such as overtemperature, bypass failure and fan failure. A PTC input is available for motor thermistors.

Because the device offers a kick-start for stiff loads and dynamic braking for fast stops, one starter can cover varied duties; the display and NFC speed up parameter copying between units.

Fit in the system and related Lovato Electric parts

The ADXL sits between the basic ADXT line of soft starters and the larger frame drives, and shares its accessories such as the DIN-rail adapter EXP8003.

  • ADXL0060600 and other ADXL ratings
  • ADXL0085600 and ADXL0135600 for larger motors
  • ADXT0034, ADXT0084 for simpler duties
  • Optional accessory EXP8003 for DIN-rail mounting

Selection and ordering checklist for the ADXL0045600

Before ordering the ADXL0045600, settle the following points so that the right variant is quoted:

  • Motor power and full-load current; 45 A at 400 V gives 22 kW in-line
  • Supply voltage between 208 and 600 V AC and available control supply of 100 to 240 V AC
  • Starting duty: pump, fan, compressor, crusher
  • Ambient temperature and altitude, with derating above +40 °C
  • Enclosure space for the unit and ventilation

Installation, commissioning and maintenance of the ADXL0045600

Mount vertically in a ventilated enclosure; the dimensions are 75 mm x 218 mm x 171.5 mm, and the mounting is by screws or on DIN rail with the optional adapter. Connect the control supply, power and the motor with correct phase order, then program the motor current, start ramp and protections.

At commissioning, run the motor at no load or with a light load, check the ramp, then confirm bypass operation and verify that overload class matches the motor.

  • Clean the heatsink and fan area
  • Check terminals for tightness
  • Review the event log and counters
  • Update parameters through NFC after any change

Typical applications in Oman and the GCC

Soft starters of this size are common on water-transfer pumps, cooling-water pumps, ventilation fans and screw compressors. In Gulf plants the main benefits are reduced inrush on weak supplies and less water hammer in long pipelines.

Where the enclosure temperature can exceed +40 °C, apply the stated derating of 0.5 % per °C so that the motor is not undersized.

Variants related to the ADXL0045600

Ratings from the ADXL series referenced in the catalogue:

Code Rated current Voltage class
ADXL0045600 45 A 208-600 V – this variant
ADXL0060600 60 A 208-600 V
ADXL0085600 85 A 208-600 V
ADXL0135600 135 A 208-600 V

Information to send with an RFQ for the ADXL0045600

To quote the ADXL0045600 quickly, please send:

  • Part number ADXL0045600
  • Quantity
  • Motor nameplate data and application
  • Supply and control voltage
  • Ambient temperature and enclosure ventilation
  • Delivery destination and date

Site conditions in Oman for the ADXL0045600

Low-voltage switching and protection devices in Oman often sit in motor control centres and outdoor panels where internal temperatures are high for much of the year. When you select the ADXL0045600, check its rated values at your real ambient temperature, as stated in the manufacturer documentation, and confirm the coordination with upstream protection and with the motor or load it serves. Short-circuit levels differ from site to site, so verify the breaking capacity required at the point of installation.

Standardising ratings and coil voltages across a project reduces the number of spare part numbers that need to be stocked. Keeping a small stock of the ADXL0045600 and recording settings such as trip ranges or ramp times shortens repair work during a breakdown.

Documents and quotation

No datasheet file is attached to this page. Send us the part number and we will confirm which official documents are available for your application.

For a quotation on the ADXL0045600, send the part number or article number, quantity and the delivery destination in Oman or the GCC. Seven Star LLC is an independent supplier based in Muscat and confirms availability and lead time per request.

Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

FAQ

Questions about the Lovato ADXL0045600 45 A Soft Starter with Built-in

Answers from our engineering team on installation, compatibility and integration.

01What motor power does the ADXL0045600 handle?
The rated starter current is 45 A, which corresponds to 11 kW at 230 V, 22 kW at 400 V and 30 kW at 500 V in-line, or 25 HP at 380-415 V and 30 HP at 440-480 V by the UL table.
02Does it include a bypass contactor?
Yes, a built-in bypass relay is fitted, so the thyristors are bypassed after the ramp and heat dissipation is low.
03How is it programmed?
Through a backlit icon LCD with keypad in six languages, through NFC technology and through an optical port on the front.
04What starting methods are available?
Torque ramp with current limit, voltage ramp with current limit and constant torque with current limit. Stop methods are torque ramp, voltage ramp or free-wheel stop.
05What is the control supply?
An auxiliary supply of 100 to 240 V AC is required for the control section, separate from the power supply of 208 to 600 V AC.