Brand:

ABB CR-M230AC2 Interface Relay 230 V AC 2 c/o 12 A

Description

CR-M230AC2: mains-coil interface relay with two 12 A changeover contacts

CR-M230AC2 is the 230 V AC-coil version of the two-contact CR-M relay. Its output is two changeover (SPDT) contacts rated 12 A at 250 V, and it has no LED. It is used where a 230 V control signal, for example from a thermostat or a pilot switch, must switch another circuit with electrical separation.

The relay mounts on a CR-M socket and is 27 mm wide on the socket. The test button for this AC version is orange, which shows at a glance that the coil is an AC type.

Technical specifications

Parameter Specification
Type designation / order code CR-M230AC2 / 1SVR405611R3000
Relay type Pluggable interface relay, 2 c/o (SPDT) contacts, without LED
Coil voltage Us 230 V AC, 50/60 Hz; pick-up from 184 V, maximum 253 V at 55 C; drop-out at 0.2 Us or more
Coil power / resistance 1.6 VA / 16,100 ohm (plus or minus 10 %)
Thermal current Ith 12 A; AC12 230 V 12 A; DC12 24 V 12 A
Inductive ratings AC15 230 V 1.5 A, 120 V 3 A; DC13 24 V 2.5 A
Inrush / AC1 power 24 A / 3000 VA
Life / switching times Mechanical above 20 million cycles; electrical above 100,000 cycles at 12 A 250 V; typical pick-up 10 ms, release 8 ms (AC)
Ambient temperature Operation -40 to +55 C for AC coils; storage -40 to +85 C
Isolation 250 V AC; impulse 2.5 kV coil to contacts; overvoltage category III, pollution degree 3
Contact material / rated voltage AgNi / Ue 250 V; max switching 250 V AC/DC; minimum 10 V and 5 mA
Test button Integrated manual actuation and locking button (blue for DC, orange for AC coils)
Dimensions on socket / weight 21.2 x 27.5 x 35.6 mm (W x H x D) / 35 g; width on socket 27 mm
Protection / mounting IP40 / on a CR-M socket, any mounting position
Approvals and standards UL 508, CSA C22.2 No. 14, VDE, GOST, CCC, CE; EN 61810-1

Coil details for the AC version

The coil is rated 1.6 VA at 50/60 Hz, with a resistance of 16,100 ohm. It pulls in at 184 V AC at 20 C and tolerates 253 V AC at 55 C, and drop-out is at 20 percent of the rated voltage or more. Typical pick-up time is 10 ms and release is 8 ms, slower than the DC type on release.

The AC coil version is rated for ambient temperatures of -40 to +55 C, lower than the +70 C allowed for DC coils. In a hot cabinet this difference is worth checking against the real temperature.

Protecting contacts and coil

For a 230 V AC coil ABB lists the CR-P/M 82 varistor module (1SVR405656R2000) for overvoltage protection and the CR-P/M 52C RC element (1SVR405653R1000, 110 to 230 V AC) for arc suppression. These plug into the socket together with the relay.

The contacts follow the same table as the DC version: 12 A resistive, 1.5 A inductive at 230 V AC (AC15). If the load is a contactor coil or small motor, check the inductive rating and not only the thermal current.

Documents and quotation

The linked file is the ABB CR-M pluggable interface relays data sheet 2CDC117002D0205. Seven Star LLC supplies the CR-M230AC2 on request from Muscat as an independent supplier; availability and lead time are given in the quotation. More products of this kind are in the Automation Accessories category, and a related item is the ABB CR-M024DC4L interface relay.

Confirm before ordering: the coil voltage on site (AC or DC), the load current and type (resistive or inductive), the number of changeover contacts needed and the socket type.

Datasheets & Documents
  • PDF Datasheet ABB CR-M pluggable interface relays data sheet 2CDC117002D0205 Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

Frequently Asked Questions

What is the coil voltage of the CR-M230AC2?
230 V AC, 50/60 Hz; pick-up at 184 V and maximum 253 V at 55 C.
What is the contact rating?
Two changeover contacts, 12 A at 250 V resistive.
What is the coil power?
1.6 VA, with 16,100 ohm coil resistance.
What is the maximum ambient temperature?
+55 C for AC coils, per the ABB data sheet.
Which module protects the coil from overvoltage?