Schneider Electric LRE10 EasyPact TVS 4-6 A Overload Relay
Description
LRE10 overload relay, 4 to 6 A: what it does
The LRE10 is a Schneider Electric product listed in its datasheet as: EasyPact TVS differential thermal overload relay 4…6 A – class 10A. It is the thermal overload part of a motor starter: it follows the current drawn by the motor and opens a signalling contact when an overload or a lost phase would otherwise overheat the windings. Seven Star LLC supplies the LRE10 in Oman and the GCC as an independent supplier based in Muscat.
The reference tells you the family and the band. LRE is the device short name given in the datasheet, the range is Easy TeSys Protect, and the title states the adjustable window, 4 to 6 A, together with trip class 10A. The two or three digits after LRE are the range code of that band. The LRE10 is built on the compact body (45 mm wide) for LC1E contactors up to the LC1E38 size. The 4 to 6 A window serves motors a size above the small auxiliaries: modest pumps, fans and compressors that draw several amperes.
Setting the LRE10 correctly
The dial of the LRE10 spans 4 to 6 A. The datasheet states a tripping threshold of 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1, so the relay is designed to act when the motor current reaches about 1.14 times the dialled value, with a tolerance of 0.06 times. At the top of the scale that is roughly 6.84 A and at the bottom roughly 4.56 A.
It is a differential relay, which matters on a three-phase motor. The datasheet gives a tripping current of 130 % of Ir on two phases while the third phase is at zero, conforming to IEC 60947-4-1; at the top of the dial 6 A that corresponds to about 7.8 A in each of the two live phases. A broken fuse or loose terminal therefore does not leave the motor running single-phased unnoticed.
Class 10A is the fast characteristic for motors that start quickly; the class number is the longest tripping time in seconds at 7.2 times the setting current under IEC 60947-4-1. Temperature compensation is listed over -20 to 60 °C, so the setting does not wander with panel temperature inside that band.
LRE10 datasheet values at a glance
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / LRE10 |
| Description | EasyPact TVS differential thermal overload relay 4…6 A – class 10A |
| Range | Easy TeSys; Easy TeSys Protect |
| Relay application | Motor protection |
| Thermal overload class | Class 10A conforming to IEC 60947-4-1 |
| Thermal protection adjustment range | 4 to 6 A |
| Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
| Phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 conforming to IEC 60947-4-1 |
| Network / frequency | AC / 50…60 Hz |
| Rated operational voltage [Ue] | ≤ 690 V AC |
| Rated insulation voltage [Ui] | 690 V conforming to IEC 60947-4-1 |
| Auxiliary contacts | 1 NO + 1 NC |
| Signalling circuit thermal current [Ith] | 5 A for signalling circuit |
| Associated fuses | 16 A gG or 8 A aM (power circuit); 5 A gG (signalling circuit) |
| Product compatibility | LC1E06 to LC1E38 |
| Mounting | Under contactor; Plate, with specific accessories; Rail, with specific accessories |
| Power terminals | Screw clamp, flexible cable without ferrule 1.5 to 6 mm² |
| Tightening torque | Power circuit: 1.7 N.m – on screw clamp terminals; Signalling circuit: 1.7 N.m – on screw clamp terminals |
| Dimensions (W x H x D) | 45 mm x 44.5 mm x 70 mm |
| Net weight | 0.13 kg |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient temperature, operation | -20 to 60 °C without derating conforming to IEC 60947-4-1; -20 to 70 °C with derating |
| Ambient temperature, storage | -60 to 80 °C |
| Product certifications | CB Scheme; CCC; CE; EAC |
Wiring the LRE10: power side and signalling side
On the power side the datasheet lists screw clamp terminals; for flexible cable without ferrule the capacity is 1.5 to 6 mm², and the recommended torque is 1.7 N.m. On the signalling side two screw clamp terminals take 1 to 2.5 mm² conductors at 1.7 N.m. Use a torque screwdriver, because heat cycling loosens starter terminals over time.
The auxiliary contact set is 1 NO + 1 NC. Wire the normally closed contact (95-96) in series with the contactor coil so a trip drops the starter, and use the normally open contact (97-98) for a fault lamp or PLC input. The datasheet gives a conventional thermal current of 5 A for signalling circuit and names a 5 A gG fuse for that circuit.
For the power circuit the datasheet names 16 A gG or 8 A aM fuses. That is about 2.67 times the top of the dial, a reminder that the fuse is for short circuits, while the relay deals with overloads.
Where the LRE10 sits in an LC1E starter
The datasheet lists the compatible contactors for the LRE10 as LC1E06 to LC1E38. Mounting options are listed as under contactor; plate, with specific accessories; rail, with specific accessories. In a normal starter the relay plugs directly under the contactor, which keeps the power wiring short and gives a compact direct-on-line starter without extra links.
The body measures 45 mm wide, 44.5 mm high and 70 mm deep with a net weight of 0.13 kg; the packed unit weighs 145 g. It is the last relay in the group that the datasheet lists from LC1E06 upward, so it can sit under the smallest contactors in the LC1E family.
Environment, standards and approvals for the LRE10
The datasheet gives an operating range of -20 to 60 °C without derating conforming to IEC 60947-4-1; -20 to 70 °C with derating and a storage range of -60 to 80 °C, with IP20 protection, fire resistance of 850 °C and mechanical robustness of 6 Gn shocks and 3 Gn vibrations. The standards named include EN/IEC 60947-1, 60947-4-1 and 60947-5-1.
Certifications listed for this exact reference are CB Scheme; CCC; CE; EAC. Do not assume any other approval; if the project needs a specific marine or hazardous-area certificate, tell us and we will check it against the datasheet before quoting.
Before you order the LRE10
- Motor nameplate current inside 4 to 6 A, ideally near the middle of the dial.
- Contactor in the starter must be one of LC1E06 to LC1E38.
- Class 10A: confirm that the load starts quickly enough for this characteristic.
- Upstream short-circuit device: 16 A gG or 8 A aM, per the datasheet.
- Space: allow 45 mm x 44.5 mm x 70 mm and 0.13 kg.
- Say whether the relay is for a new starter or replaces one that has tripped out of service.
Commissioning and spares for the LRE10
Set the dial of the LRE10 to the nameplate current of the motor, not to the contactor rating. Use the red stop push-button to confirm the contactor drops and the green reset push-button to restore the relay afterwards. After any short-circuit event inspect the relay and starter, because the overload relay does not replace the upstream fuse or breaker.
For spares keep the same reference instead of choosing by range alone, since the compatible contactor list differs from band to band (LC1E06 to LC1E38 for the LRE10). If you are unsure, send the contactor reference and the motor nameplate current and we will confirm the matching member of the family.
Information to send with an RFQ for the LRE10
- Full reference LRE10 and the quantity required
- Motor nameplate current, voltage and power
- Contactor reference the relay will be fitted to
- Delivery location and timing
- New starter, replacement or spare
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it is the document to check against your own drawings.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Lre Compact Range
Seven Star LLC supplies models from the Se Lre Compact range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric LRE01 EasyPact TVS 0.1-0.16 A Overload Relay | Contactors & Overload Relays | View details |
| Schneider Electric LRE10 EasyPact TVS 4-6 A Overload Relay | Contactors & Overload Relays | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric LRE10 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric LRE10 EasyPact TVS 4-6 A
Answers from our engineering team on installation, compatibility and integration.
01What current range does the LRE10 cover?
The datasheet gives a thermal protection adjustment range of 4 to 6 A with class 10A tripping. The motor nameplate current should fall inside that window.
02Which contactors can the LRE10 be mounted on?
The datasheet lists LC1E06 to LC1E38. The relay mounts under the contactor, and it can also be used on a plate or rail with specific accessories.
03How does the LRE10 react to a lost phase?
It is a differential relay. The datasheet states a tripping current of 130 % of Ir on two phases with the third at zero, in addition to the 1.14 +/- 0.06 Ir overload threshold.
04Which fuses does the datasheet associate with the LRE10?
For the power circuit it names 16 A gG or 8 A aM, and for the signalling circuit 5 A gG. These protect against short circuits; the relay itself handles overload.
05What are the size and contact arrangement of the LRE10?
The datasheet gives 45 mm wide, 44.5 mm high, 70 mm deep and a net weight of 0.13 kg, with one normally open and one normally closed auxiliary contact.