- Automation & ControlView all 1,803 products
- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Safety Switches & Guard Locking
- Isolator & Barrier
- Encoders
- HMI Displays
- Industrial Computers
- Servo Drives
- Motor Soft Starters
- Pneumatic Cylinders
- Machine Vision
- Automation Software
- Robotics
Brand: Schneider Electric
Schneider Electric LC1D32BD TeSys Deca 32 A Contactor 24 V DC
Description
LC1D32BD 32 A contactor for pump and compressor motors
The LC1D32BD is a Schneider Electric product listed in the datasheet as: IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style. The LC1D32BD is a 32 A TeSys Deca contactor with a 24 V DC coil, large enough for pump, compressor and fan motors in the 15 kW class at 400 V. Compared with the small frames, it is where contact heating, terminal torque and cable size start to matter in panel design. Seven Star LLC supplies the LC1D32BD in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference: LC1D32 gives the 32 A AC-3 rating, BD the 24 V DC coil. The datasheet states 20 hp at 480 V AC, three NO poles, up to 100 kA SCCR with suitable protection and an open style, so it is intended to be mounted inside an enclosure.
Technical specifications of the LC1D32BD
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / LC1D32BD |
| Description | IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style |
| Range of Product | TeSys Deca Advanced |
| Product or Component Type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit <= 690 V AC 25 to 400 Hz; Power circuit <= 300 V DC |
| [Ie] rated operational current | 32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
| [Uc] control circuit voltage | 24 V DC |
| Motor power kW | 7.5 kW at 220/230 V AC 50/60 Hz (AC-3); 15 kW at 380/400 V AC 50/60 Hz (AC-3); 15 kW at 415/440 V AC 50/60 Hz (AC-3) |
| Maximum Horse Power Rating | 2 hp at 115 V AC 50/60 Hz for 1 phase motors; 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal | 10 A (at 60 °C) for signalling circuit |
| current | 430 A 40 °C – 1 s for power circuit; 60 A 40 °C – 10 min for power circuit; 138 A 40 °C – 1 min for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 550 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand | 260 A 40 °C – 10 s for power circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at <= 690 V coordination type 1 for power circuit |
| Average impedance | 2 mOhm – Ith 50 A 50 Hz for power circuit |
| Power dissipation per pole | 2 W AC-3; 5 W AC-1; 2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit 690 V IEC 60947-4-1; Power circuit 600 V CSA; Power circuit 600 V UL; Signalling circuit 690 V IEC 60947-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand | 6 kV IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 30 Mcycles |
| Electrical durability | 1.65 Mcycles 32 A AC-3 <= 440 V; 1.4 Mcycles 50 A AC-1 <= 440 V; 1.65 Mcycles 32 A AC-3e <= 440 V |
| Control circuit type | DC standard |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.1 to 0.25 Uc (-40 to 70 °C):drop-out DC; 0.7 to 1.25 Uc (-40 to 60 °C):operational DC; 1 to 1.25 Uc (60 to 70 °C):operational DC |
| Inrush power in W | 5.4 W 20 °C |
| Hold-in power consumption in W | 5.4 W 20 °C |
| Operating time | 63 ±15 % ms closing; 20 ±20 % ms opening |
| Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections – terminals | Control circuit: screw clamp terminals 1 1 to 4 mm² – cable stiffness: flexible without cable end |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1 |
Duty, coil and thermal data of the LC1D32BD
Rated motor power: 7.5 kW at 220/230 V AC 50/60 Hz (AC-3); 15 kW at 380/400 V AC 50/60 Hz (AC-3); 15 kW at 415/440 V AC 50/60 Hz (AC-3). Rated operational voltage: Power circuit <= 690 V AC 25 to 400 Hz; Power circuit <= 300 V DC. Rated operational current: 32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit. Utilisation categories: AC-3; AC-3e; AC-1; AC-4. Motor power ratings: 7.5 kW at 220/230 V AC 50/60 Hz (AC-3); 15 kW at 380/400 V AC 50/60 Hz (AC-3); 15 kW at 415/440 V AC 50/60 Hz (AC-3). Coil or control voltage: 24 V DC. Mechanical durability: 30 Mcycles. Electrical durability: 1.65 Mcycles 32 A AC-3 <= 440 V; 1.4 Mcycles 50 A AC-1 <= 440 V; 1.65 Mcycles 32 A AC-3e <= 440 V.
At 32 A the contactor dissipates noticeably more heat than the 9 A or 18 A frames; use the power dissipation per pole value of the datasheet when sizing cabinet ventilation. The DC coil is designed for control circuits at 24 V DC and its consumption is listed in the table.
Panel design around the LC1D32BD
A 32 A starter normally consists of the contactor, a GV2 or GV3 breaker upstream and a thermal overload relay such as an LRD22 or LRD32. Choose the combination from the coordination table in the product literature so that the type of coordination meets the project requirement.
Where soft starting or variable speed is required, the contactor may serve as the bypass or line contactor of an Altivar or Altistart.
Selection checklist for the LC1D32BD
- Motor full-load current and the hp or kW class (20 hp at 480 V for this reference).
- 24 V DC control supply and coil consumption.
- Upstream protection and coordination.
- Thermal relay and its setting range.
- Number of operations per hour for the duty.
- Cabinet heat load and ventilation.
Terminals, torque and maintenance of the LC1D32BD
Use cable of the cross-section recommended for 32 A and tighten the power terminals with the torque listed. Loose terminals at this current rapidly produce heat, so retighten after the first weeks of operation and at each shutdown.
Inspect the contacts for pitting and keep the arc chambers clear of dust.
Typical applications of the LC1D32BD in Oman and the GCC
In Oman and the GCC the 32 A contactor class starts irrigation pumps, booster pumps, chillers and process fans. High ambient temperature calls for checking derating and the clearances inside the enclosure.
Dimensions, environment and approvals of the LC1D32BD
For the LC1D32BD, plan the mounting space from the datasheet: 45 mm (W) x 85 mm (H) x 101 mm (D). The LC1D32BD weighs 0.535 kg. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.
Ingress protection: IP20 front face IEC 60529. Operating altitude: 0 to 3000 m. Standards listed: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ. Certifications listed for this reference: UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme.
Information to send with an RFQ for the LC1D32BD
- Full reference and quantity required
- Existing equipment, panel or rack it must fit
- Supply voltage, load or signal details of the application
- Required delivery location and timing
- Whether a spare, a replacement or a new installation
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.
Other Models in the Se Lc1d Dc Range
Seven Star LLC supplies models from the Se Lc1d Dc range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric LC1D18BD TeSys Deca 18 A Contactor 24 V DC | Contactors & Overload Relays | View details |
| Schneider Electric LC1D32BD TeSys Deca 32 A Contactor 24 V DC | Contactors & Overload Relays | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric LC1D32BD Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric LC1D32BD TeSys Deca 32 A
Answers from our engineering team on installation, compatibility and integration.
01What is the net weight of the LC1D32BD?
The datasheet gives 0.535 kg.
02What ingress protection does the LC1D32BD list?
Stated as IP20 front face IEC 60529.
03Which standards does the LC1D32BD list?
Listed: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1.
04Which product range does the LC1D32BD belong to?
The datasheet lists the range as TeSys Deca Advanced.
05What is the device short name of the LC1D32BD?
The datasheet gives LC1D.


















Reviews