Brand: Schneider Electric
Schneider Electric RXM2AB1B7 Harmony RXM Relay 24 V AC
Description
RXM2AB1B7: RXM2 miniature relay, 24 V AC coil
The RXM2AB1B7 is an RXM-series miniature plug-in relay with 2 changeover contacts rated 12 A, a 24 V AC coil, no status LED and a lockable test button. It belongs to the Schneider Electric Harmony electromechanical relay range and is built for panel and marshalling-cabinet duty, where it plugs into a socket instead of being wired directly. Seven Star LLC supplies the RXM2AB1B7 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference as our own pattern across the RXM2A group, and not as a published ordering table: RXM2 gives the contact count, AB the high-rating body, the digit 1 (without an LED) and the closing code B7 the coil, here 24 V AC.
RXM2AB1B7 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / RXM2AB1B7 |
| Range / series | Harmony Electromechanical Relays / RXM series |
| Relay type | Miniature plug-in relay |
| Contacts | 2 C/O |
| Control circuit voltage [Uc] | 24 V AC 50/60 Hz |
| Operating voltage limits | 19.2–26.4 V AC |
| Drop-out threshold | ≥ 0.15 Uc |
| Average coil resistance | 180 Ohm at 20 °C ± 15 % |
| Average coil consumption | 1.2 VA at 60 Hz |
| Status LED | Without |
| Control / test | Lockable test button |
| Load current | 12 A at 250 V AC; 12 A at 28 V DC |
| Maximum switching capacity | 3000 VA/336 W |
| Contact material | AgNi |
| Mechanical durability | 10000000 cycles |
| Electrical durability | 100000 cycles for resistive load |
| Operating temperature | -40–55 |
| Storage temperature | -40–85 |
| Protection class | IP40 conforming to IEC 60529 |
| Net weight | 0.037 kg |
| Standards | IEC 61810-1, CSA C22.2 No 14, UL 508 |
| Certifications listed | UL, Lloyd’s, CE, CSA, GOST, IECEE CB Scheme |
All figures above come from the Schneider Electric product datasheet for the RXM2AB1B7, which carries the print date 8 Nov 2026. The sheet shows no discontinuation notice for this reference.
Contact capability of the RXM2AB1B7 relay
The 2 changeover contacts carry a load current of 12 A at 250 V AC; 12 A at 28 V DC, with a maximum switching capacity of 3000 VA/336 W and a continuous output current of 10 A. The contact material is AgNi. The normally closed side is rated lower than the normally open side, at 6 A on IEC duty, so check which contact your load uses.
Rated operational currents on the datasheet include 12 A at 28 V (DC) NO conforming to IEC ; 12 A at 250 V (AC) NO conforming to IEC ; 6 A at 28 V (DC) NC conforming to IEC ; 6 A at 250 V (AC) NC conforming to IEC. Mechanical durability is 10000000 cycles cycles and electrical durability for a resistive load is 100000 cycles for resistive load. Operating rate is up to 1200 cycles per hour under load.
The dielectric strength is 1300 V AC between contacts with micro disconnection; 2000 V AC between coil and contact with basic insulation; 2000 V AC between poles with basic insulation.
Comparing this relay with related references
The table below lists the RXM2AB1B7 next to the closest references from the same group, ordered by coil voltage, so that you can check that you are specifying the right coil and indicator combination.
| Part number | Coil voltage | Indicator LED | Test button | Coil resistance |
|---|---|---|---|---|
| RXM2AB1B7 (this page) | 24 V AC | Without | Lockable | 180 Ω |
| RXM2AB2B7 | 24 V AC | With | Lockable | 180 Ω |
| RXM2AB1E7 | 48 V AC | Without | Lockable | 710 Ω |
| RXM2AB1F7 | 120 V AC | Without | Lockable | 4430 Ω |
| RXM2AB1P7 | 230 V AC | Without | Lockable | 15000 Ω |
| RXM2AB2P7 | 230 V AC | With | Lockable | 15000 Ω |
| RXM2AB1BD | 24 V DC | Without | Lockable | 650 Ω |
Coil data and operating range of the RXM2AB1B7
A 24 V AC coil is fed from a small control transformer inside the panel, a practice that persists in older HVAC and machine-control cabinets and in panels built around transformer-fed pilot circuits.
The datasheet gives operating voltage limits of 19.2–26.4 V AC, with a drop-out threshold of ≥ 0.15 Uc. The average coil resistance is 180 Ohm at 20 °C ± 15 % and the average consumption is 1.2 VA at 60 Hz. Those numbers matter more than the nominal voltage: a supply that sags under load, or that sits at the top of its tolerance, should still fall inside the stated window for RXM2AB1B7 to pick up and release cleanly.
Because this is an AC coil, the contacts follow the supply frequency of 50/60 Hz; the relay is not meant for a rectified or unsmoothed DC feed, and an AC coil must not be fitted where a DC coil was specified.
Typical applications in Oman and the GCC
Two changeover contacts at 12 A cover contactor-coil duty, small solenoid valves, alarm horns and the interposing of a PLC output toward heavier loads, across pumps, fans and valve packages. Panels in Oman and the wider Gulf see high ambient temperatures, dust and humidity, so relays should be installed in ventilated, sealed cabinets and the temperature limits (operation -40–55 °C) kept in mind when panels sit in the sun. Seven Star LLC supplies the RXM2AB1B7 for panel builders, maintenance teams and projects in oil and gas, power, desalination and general industry.
Selection checklist for this relay
- Coil voltage and type: 24 V AC. Match both the voltage and AC or DC to the supply that actually feeds the coil.
- Contact count and load: 2 changeover contacts, 12 A at 250 V AC; 12 A at 28 V DC; confirm the NC contact rating if the load is on the NC side.
- Indication: no LED, so status must be read from the controller or by a lamp elsewhere in the circuit.
- Test facility: lockable test button fitted.
- Socket: the relay has Flat (faston type) pins, so choose a matching socket from the same Harmony range and confirm its reference with your supplier.
- Environment: operating temperature -40–55 °C and IP40 conforming to IEC 60529; as a plug-in relay it belongs inside a panel, not on an open plant floor.
Installation, commissioning and maintenance
Seat the relay squarely so that all flat pins engage and, if the socket has a retaining clip, fit the clip before the panel goes into service. Group mounting is permitted at the test level shown in the datasheet, but leave air around relays that are continuously energised, because the permitted ambient is -40–55 °C. The net weight is 0.037 kg.
Use the lockable test button during commissioning to prove the downstream circuit, then release it and note that in the commissioning record. A relay is a wear item: keep spare relays of the same coil voltage and replace them on a schedule defined by the duty, not only after a failure.
Information to send with an RFQ
- The exact part number RXM2AB1B7 and the quantity, remembering the pack quantity of the reference.
- The coil voltage on site, 24 V AC here, and the supply tolerance.
- The socket reference or the existing relay being replaced.
- The load type and current on each contact.
- The delivery location and whether the relays are for a project or maintenance stock.
Documents and quotation
The Schneider Electric datasheet for the RXM2AB1B7 is attached on this page, and the figures above come from it. Always check the latest revision before final design.
To obtain a quotation, send us the part number RXM2AB1B7 with the quantity and delivery location, and we will respond with availability and lead time. Seven Star LLC is an independent supplier and does not claim any official status with the manufacturer.
Datasheets & Documents
- Datasheet Schneider Electric RXM2AB1B7 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric RXM2AB1B7 Harmony RXM Relay 24 V
Answers from our engineering team on installation, compatibility and integration.
01What coil voltage does the RXM2AB1B7 use?
The RXM2AB1B7 has a 24 V AC control coil. The datasheet gives operating limits of 19.2–26.4 V AC and a drop-out threshold of ≥ 0.15 Uc, and an average coil resistance of 180 Ohm at 20 °C ± 15 %.
02How many contacts and what current does the RXM2AB1B7 switch?
It has 2 changeover contacts with a load current of 12 A at 250 V AC; 12 A at 28 V DC and a maximum switching capacity of 3000 VA/336 W. The contact material is AgNi.
03Does the RXM2AB1B7 have an LED or a test button?
It has no status LED and a lockable test button, according to the datasheet.
04What temperature range applies to the RXM2AB1B7?
The datasheet lists operation at -40–55 °C and storage at -40–85 °C. The relay is rated IP40 conforming to IEC 60529, so it is intended for installation inside a panel.
05Can I request a quotation for the RXM2AB1B7 in Oman?
Yes. Send the part number RXM2AB1B7, the quantity and the delivery location, and Seven Star LLC will confirm availability and lead time as an independent supplier in Muscat.