Schneider Electric LA1KN02 TeSys K 2 NC Front Contact Block
Description
LA1KN02: two normally closed contacts on the front of a TeSys K contactor
The LA1KN02 is a Schneider Electric TeSys K auxiliary contact block with two normally closed contacts, mounted on the front of the contactor and wired by screw clamp terminals. It is the simplest way to add an interlock or a feedback path to a small contactor. Seven Star LLC supplies the LA1KN02 in Oman and the GCC as an independent supplier based in Muscat.
In the reference, LA1K belongs to the TeSys K auxiliary block series, and the closing digits 02 read as zero normally open and two normally closed contacts. The sibling references use the same rule: 04 is four NC, 13 is one NO plus three NC, 20 is two NO and 40 is four NO.
Technical specifications of the LA1KN02
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / LA1KN02 |
| Description | Product datasheet Auxiliary contact block, TeSys K, 2NC,front mounting, screw clamp terminals |
| Range | TeSys |
| Product name | TeSys K |
| Product or component type | Auxiliary contact block |
| Device short name | LA1 |
| Range compatibility | TeSys K LC1K; TeSys K CA2K; TeSys K CA3K; TeSys K CA4K |
| Mounting location | Front |
| Pole contact composition | 2 NC |
| Contacts operation | Instantaneous |
| [Ue] rated operational voltage | 690 V AC 25 to 400 Hz |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-5-1; 600 V conforming to UL 60947-5-1; 600 V conforming to CSA C22.2 No 60947-5-1 |
| [Ith] conventional free air thermal | 10 A (at 50 °C) |
| Standards | EN/IEC 60947-5-1; UL 60947-5-1; CSA C22.2 No 60947-5-1; GB/T 14048.5; JIS C8201-5-1; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; UL; CSA; CE; UKCA |
| Irms rated making capacity | 110 A at <= 690 V AC conforming to IEC 60947 |
| Permissible short-time rating | 80 A 1 s; 60 A 500 ms; 110 A 100 ms |
| Associated fuse rating | 10 A gG at <= 690 V conforming to IEC 60947 |
| Minimum switching current | 5 mA |
| Minimum switching voltage | 17 V |
| Non overlap distance | 0.5 mm |
| Insulation resistance | > 10 MOhm; are subject to change – check with your local distributor. |
| Connections – terminals | Screw clamp terminals 1 cable(s) 0.34 to 1.5 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 0.75 to 4 mm²flexible without cable end |
| Height | 30 mm |
| Width | 38 mm |
| Depth | 35 mm |
| Net weight | 0.045 kg |
| Environmental characteristic | Normal environment |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature (operation, as listed) | -25 to 50 °C |
| Operating altitude | 2000 m |
What the LA1KN02 attaches to
The datasheet range compatibility lists TeSys K contactors LC1K and the relay series CA2K, CA3K and CA4K. Notice that this two-contact block adds CA4K to the list, which the four-contact blocks do not show.
Mounting is on the front face, so the block sits above the coil terminals and below the power terminals depending on the contactor, and it can be removed without taking the contactor off the rail.
The datasheet describes a front-mounting block with screw clamp terminals, 30 mm high, 38 mm wide and 35 mm deep, weighing 0.045 kg. Rated operational voltage is 690 V AC at 25 to 400 Hz, conventional thermal current is 10 A at 50 °C, and the associated fuse is 10 A gG up to 690 V. Rated making capacity is 110 A, with short-time ratings of 80 A for 1 s, 60 A for 500 ms and 110 A for 100 ms. Minimum switching is 5 mA at 17 V, and the non-overlap distance between NC and NO contacts is 0.5 mm.
Using two NC contacts of the LA1KN02 for interlocking
Two normally closed contacts are the building blocks of electrical interlocking. Wired in the coil circuit of a second contactor they ensure that the second cannot be energised while the first is closed, which is the classic reversing and changeover interlock. Because the contacts are normally closed they also form a series chain of permissives or an emergency-stop feedback.
The datasheet gives a non-overlap distance of 0.5 mm between NC and NO contacts, which is a design feature in blocks with mixed contacts. For a pure NC block like this one, the figure matters when the block is stacked with an NO unit on the same contactor.
LA1KN02 specification checklist
- Two NC contacts, no NO.
- Switching of control signals: 690 V AC at 25 to 400 Hz, 10 A thermal.
- Minimum load 5 mA at 17 V for dry-circuit reliability.
- Protect with a 10 A gG fuse as in the datasheet.
- Compatible with LC1K, CA2K, CA3K and CA4K.
- If a signal lamp is needed too, add an NO block such as LA1KN20.
LA1KN contact block family compared with the LA1KN02
The five TeSys K references below differ only in the arrangement of contacts. The highlighted row is the page you are reading.
| Reference | Contacts | Compatible with |
|---|---|---|
| LA1KN02 | 2 NC | LC1K; CA2K; CA3K; CA4K |
| LA1KN04 | 4 NC | LC1K; CA2K; CA3K |
| LA1KN13 | 1 NO + 3 NC | LC1K; CA2K; CA3K |
| LA1KN20 | 2 NO | LC1K; CA2K; CA3K; CA4K |
| LA1KN40 | 4 NO | LC1K; CA2K; CA3K |
Fitting and wiring the LA1KN02
Clip the block into the front seat, tighten the screw clamp terminals at 1.3 N.m using a Philips No 2 or Pozidriv No 2 screwdriver and use conductors of 0.34 to 1.5 mm² with ferrules or 0.75 to 4 mm² without. Two cables per terminal are allowed within the ranges of the datasheet.
Mark the terminals with the numbers used in the drawing. For interlocks, test the function by closing each contactor by hand and measuring that the other coil circuit opens.
LA1KN02 in Oman and the GCC
Small contactors of the TeSys K range appear in compact starters, heating control and HVAC panels. NC contacts are used for interlocking between the forward and reverse contactors of gate or shutter motors, and as feedback to PLC inputs.
The ambient range of -25 to 50 °C in the datasheet is narrower than for some TeSys D accessories, so mount the block where the cabinet air does not exceed 50 °C in the summer.
Information to send with an RFQ for the LA1KN02
- Full reference and quantity required
- Contactor or relay model the block mounts on
- Contact arrangement needed (NO and NC count)
- Control voltage and load of each circuit
- Delivery location and timing
Documents and quotation
A datasheet for the LA1KN02 is attached on this page. It carries the electrical, mechanical and environmental data summarised above, so the figures can be checked against your drawings.
Send the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Datasheets & Documents
- Datasheet Schneider Electric LA1KN02 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric LA1KN02 TeSys K 2 NC Front
Answers from our engineering team on installation, compatibility and integration.
01How many contacts does the LA1KN02 have?
Two normally closed contacts. Check that this arrangement matches your control circuit before ordering.
02Which contactors accept the LA1KN02?
The datasheet lists TeSys K LC1K and CA2K, CA3K and CA4K.
03What is the thermal current of the LA1KN02?
10 A at 50 degrees C. See the datasheet linked on this page for the full figures.
04What torque is specified for the LA1KN02 terminals?
1.3 N.m. See the datasheet linked on this page for the full figures.
05What ambient temperature is listed for the LA1KN02?
-25 to 50 degrees C, with an altitude limit of 2000 m.