Brand: Schneider Electric
Schneider Electric BMEH582040 M580 Redundant Processor 8 MB
Description
BMEH582040 M580 redundant processor for hot standby systems
The BMEH582040 is a Schneider Electric product listed in the datasheet as: redundant processor, Modicon M580, 8MB, 61 Ethernet devices, 8 local racks, 8 remote IO racks [TAA]. The BMEH582040 is the redundant processor of the Modicon M580 platform. Two identical processors run in a hot-standby pair, so that the control task continues when one unit or its power supply fails. It is meant for plants where an outage is costly. Seven Star LLC supplies the BMEH582040 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference: BME is the M580 platform and H58 the hot-standby processor series; the title in the datasheet states 8 MB memory, 61 Ethernet devices and 8 remote I/O drops. The same number repeats in each processor of the pair.
Technical specifications of the BMEH582040
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / BMEH582040 |
| Description | redundant processor, Modicon M580, 8MB, 61 Ethernet devices, 8 local racks, 8 remote IO racks [TAA] |
| Range of Product | Modicon M580 |
| Product or Component Type | Redundant processor module |
| Number of racks | 1 |
| Application specific I/O | Counter; Accurate time stamping; Serial link; HART; Motion control; SSI encoder |
| Checks | Process control |
| Control channels | Programmable loops |
| Integrated connection type | 1 Ethernet TCP/IP service port; 2 Ethernet TCP/IP device network; USB type mini B; 1 Ethernet HSBY port |
| Number of remote I/O station | 8 – 2 X80 remote drop |
| Number of distributed equipment | 64 |
| Communication module | 2 Ethernet communication module |
| processor capacity | 16 AS-Interface module |
| Communication Service | DIO scanner; RIO scanner |
| Memory description | Expandable flash, 4 GB data storage; Integrated RAM, 10 kB system memory; Integrated RAM, 8 MB program; Integrated RAM, 768 kB data |
| Application structure | 1 periodic fast task; 1 cyclic/periodic master task |
| Cybersecurity | DoS prevention; IPSec; SNMP logging; Syslog protocol support; Transport layer security; Audit trail; Embedded firewall; Firmware signature |
| Number of instructions per ms | 30 Kinst/ms 65 % Boolean + 35 % fixed arithmetic; 40 Kinst/ms 100 % Boolean |
| Current consumption | 270 mA 24 V DC |
| MTBF reliability | 650000 H |
| Vibration resistance | 3 gn |
| Shock resistance | 30 gn |
| Ambient air temperature (operation or storage, as listed) | -40 to 85 °C |
| Operating altitude | 0 to 2000 m; 2000 to 5000 m with derating factor |
| Relative humidity | 5 to 95 % 55 °C without condensation |
| IP Degree of Protection | IP20 |
| Product certifications | CE; UL; CSA; RCM; EAC; Merchant Navy; UKCA |
| Standards | IEC 61131-2; IEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201; IACS E10; EN/IEC 61000-6-5, interface type 1 and type 2 |
| Supply | Internal power supply via rack |
| Status LED | 1 LED (Green) processor running (RUN); 1 LED (Red) processor or system fault (ERR); 1 LED (Red) I/O module fault (I/O) |
| Net Weight | 0.849 kg |
How a redundant pair behaves and what the BMEH582040 provides
Racks: 1. Remote I/O stations: 8 – 2 X80 remote drop. Distributed devices: 64. Memory: Expandable flash, 4 GB data storage; Integrated RAM, 10 kB system memory; Integrated RAM, 8 MB program; Integrated RAM, 768 kB data. Services: DIO scanner; RIO scanner. Cybersecurity: DoS prevention; IPSec; SNMP logging; Syslog protocol support; Transport layer security; Audit trail; Embedded firewall; Firmware signature. Reliability: 650000 H.
In a hot-standby system the primary processor runs the logic while the standby copy follows through a dedicated link. On a failure of the primary, the standby takes control with a bumpless transfer that depends on the scan time and the process variable handling. Retained variables and system bits move across the link.
Sync link, rack and I/O architecture of the BMEH582040
A redundant system needs two racks with identical modules, a synchronisation link between the processors and Ethernet remote I/O drops, since local racks are not redundant. The datasheet lists remote I/O stations, distributed devices and the communication services.
Design the network as a ring or dual network so that a single cable failure does not defeat the redundancy. Document what is redundant and what is not before the project is accepted.
Selection and ordering checklist for the BMEH582040
- Two processors are needed for one redundant pair, ordered with identical firmware.
- Number of remote I/O drops required.
- Ethernet architecture: rings and switches.
- Engineering software with redundancy support.
- Need for high-availability rack power supplies.
- Plan for online firmware upgrade procedure.
Commissioning and testing the BMEH582040
Install both processors, connect the sync link, configure the redundancy in the engineering software and download. Perform a switchover test under controlled conditions, then simulate the loss of a processor power supply.
Include the switchover test in the factory acceptance test and repeat it at site acceptance. Keep both processors at the same firmware level and keep a documented procedure for replacing one half without stopping the process.
Typical applications of the BMEH582040 in Oman and the GCC
Typical use is on critical utilities: power-plant auxiliaries, gas-compression control, water-treatment trains and pumping stations where trips are expensive. A redundant PLC adds hardware but not by itself a safety function, so do not use it as a substitute for a safety system.
Dimensions, environment and approvals of the BMEH582040
The BMEH582040 weighs 0.849 kg. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.
Ambient temperature limits in the datasheet: -40 to 85 °C. Relative humidity: 5 to 95 % 55 °C without condensation. Ingress protection: IP20. Operating altitude: 0 to 2000 m; 2000 to 5000 m with derating factor. Vibration resistance: 3 gn. Shock resistance: 30 gn. Standards listed: IEC 61131-2; IEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201; IACS E10; EN/IEC 61000-6-5, interface type 1 and type 2. Certifications listed for this reference: CE; UL; CSA; RCM; EAC; Merchant Navy; UKCA.
Information to send with an RFQ for the BMEH582040
- Full reference and quantity required
- Existing equipment, panel or rack it must fit
- Supply voltage, load or signal details of the application
- Required delivery location and timing
- Whether a spare, a replacement or a new installation
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.
Datasheets & Documents
- Datasheet Schneider Electric BMEH582040 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric BMEH582040 M580 Redundant
Answers from our engineering team on installation, compatibility and integration.
01What does the BMEH582040 provide?
The datasheet lists services: DIO scanner; RIO scanner.
02How much memory has the BMEH582040?
Memory: Expandable flash, 4 GB data storage; Integrated RAM, 10 kB system memory; Integrated RAM, 8 MB program; Integrated RAM, 768 kB data.
03How many remote drops does it support?
The datasheet states 8 – 2 X80 remote drop.
04What security services does it have?
Listed: DoS prevention; IPSec; SNMP logging; Syslog protocol support; Transport layer security; Audit trail; Embedded firewall; Firmware signature; Password protection; Port hardening.
05What is the processor MTBF?
The datasheet lists 650000 H.


















Reviews