The Endress+Hauser FMB70 is the Deltapilot S, the higher-grade hydrostatic level and pressure transmitter in the Endress+Hauser Deltapilot line. It uses the same condensate-resistant CONTITE measuring cell as the Deltapilot M, but adds a tighter accuracy class of up to 0.075 % of the set span, a replaceable HistoROM/M-DAT memory for the electronics, functional safety capability up to SIL 3 and a wide choice of hygienic process fittings. The FMB70 mounts at the vessel connection and measures liquids, gases and paste-like media.

Seven Star LLC supplies the FMB70 in Oman and the GCC as an independent supplier in Muscat. This page covers what sets the FMB70 apart, its main data and what we need to quote the correct version.

FMB70 technical specifications

Parameter Specification
Manufacturer / part number Endress+Hauser / FMB70 (Deltapilot S)
Measuring cells (URL) 100 mbar, 400 mbar, 1.2 bar, 4 bar or 10 bar (1.5 to 150 psi)
Smallest calibratable span 0.025, 0.04, 0.1, 0.1 and 0.1 bar for the five cells respectively
Overpressure limit (OPL) 4, 8, 24, 24 and 40 bar (maximum 40 bar / 600 psi)
Reference accuracy, standard ±0.15 % on the 100 and 400 mbar cells; ±0.1 % on the 1.2, 4 and 10 bar cells (low turn down)
Reference accuracy, platinum ±0.1 % on the 100 and 400 mbar cells; ±0.075 % on the 1.2, 4 and 10 bar cells
Turn down Accuracy specified up to 4:1 (100 mbar), 10:1 (400 mbar), 12:1 (1.2 bar) and 40:1 (4 and 10 bar)
Long-term stability ±0.05 % of URL per year on 4 and 10 bar cells; ±0.18 % on the 100 mbar cell
Process temperature –10 to +100 °C; up to +135 °C for 30 minutes at most (cleaning)
Ambient temperature –40 to +85 °C without display; –20 to +70 °C with display; separate housing –20 to +60 °C
Process diaphragm Alloy C276 (2.4819), 35.8 mm, optional gold-rhodium coating
Output / communication 4 to 20 mA HART, PROFIBUS PA or FOUNDATION Fieldbus
Supply voltage HART 10.5 to 45 V DC (10.5 to 30 V DC for Ex ia); PA and FF 9 to 32 V DC (non-hazardous)
Dynamic behaviour (HART current output) Dead time up to 40 ms, T63 30 ms, T90 69 ms; warm-up under 10 s
Housings T14 aluminium (display on side), T15 (display on top) or T17 stainless hygienic; the housing can be rotated up to 380 degrees

These specifications come from the Endress+Hauser technical information for the Deltapilot S FMB70. Limits depend on the cell, connection and options chosen.

How the FMB70 measures

A liquid column produces a pressure that depends on its height and density. The FMB70 reads that pressure on a metal diaphragm and transmits it through oil to a silicon element that sits between the process diaphragm and a rear isolating membrane. This construction seals the element from the air reference, so condensation and aggressive gases cannot reach it. The sensor also measures its own temperature with a resistance bridge, and the electronics use that value to remove temperature error. A 32-point linearization table converts pressure to volume in tanks of irregular shape.

The result is a stable signal: the datasheet total performance is ±0.15 % of the upper range limit with the standard class and ±0.12 % with the platinum class on the 1.2 to 10 bar cells, from –10 to +60 °C. Two FMB70 devices and a PLC can give differential level in a closed tank, or density from a known vertical spacing.

FMB70 process connections and safety options

The FMB70 accepts a G 1½ A thread (316L, or with an Alloy C276 bottom section), a 1½ MNPT thread, EN, ASME and JIS flanges and flush hygienic connections such as DIN 11851 DN 40 and DN 50, DIN 11864-1 A DN 50, Tri-Clamp, DRD DN 50 (65 mm) and Anderson adapters. Options include a gold-rhodium coated diaphragm for hydrogen diffusion, 3.1 inspection certificates, cleaning for paint-wetting-free service, a separate housing and 3-A and EHEDG approvals for the adapters. For safety loops, the 4 to 20 mA version supports use up to SIL 3 under IEC 61508, with overfill protection to WHG, a GL marine approval and an NSF 61 drinking-water approval available as order options.

Where the FMB70 fits and related Deltapilot models

Use the FMB70 when accuracy, long-term stability or SIL 3 are decisive, when the media is hygienic and the fitting must be flush, or when you want the replaceable memory to simplify electronics swaps. For cable, rod or well installations, the Deltapilot M family with the FMB51, FMB52 and FMB53 is built for that, and the FMB50 is the compact Deltapilot M counterpart with fewer high-accuracy options. The optional HistoROM/M-DAT memory chip makes the electronics easy to replace.

Selecting and ordering an FMB70

  • Cell range: select the cell for the maximum head plus top pressure, and keep the turn down within the accuracy limit for that cell.
  • Accuracy class: standard or platinum. The 4 and 10 bar cells have the highest turn-down range.
  • Process connection: thread, flange or hygienic fitting; a lower pressure rating on the connection reduces the overpressure limit of the whole device.
  • Output and housing: HART, PROFIBUS PA or FOUNDATION Fieldbus with T14, T15 or T17, display, and cable entry or plug.
  • Safety and approvals: SIL declaration, WHG overfill, marine, drinking water and the Ex family (ATEX, FM, CSA, NEPSI, IECEx, TIIS) as required.
  • Hazardous-area ambient: certified devices can be ordered for ambient temperatures down to –50 °C with the correct test certificate option.

FMB70 installation, commissioning and maintenance

When measuring media with solids, add a separator and a drain valve at the tapping point so sediment can be flushed out. Position the housing for the best display view and use the 380 degree rotation to align the cable entry down. Correct any position-dependent zero shift with the keys on the device, which can be done also in a hazardous area with external operation. For steam or hot cleaning, observe the 135 °C limit of 30 minutes.

In service the FMB70 needs little attention. At shutdowns, check the diaphragm area for coating, check the cover seal and the cable entry, and verify the zero. For SIL loops, follow the functional safety manual and keep proof-test records.

Typical FMB70 applications in Oman and the GCC

In Oman and the GCC, the FMB70 is used where an accurate reading matters: tank inventory in chemical and petrochemical storage, boiler feedwater and condensate vessels at power plants, chemical dosing tanks at desalination and water treatment plants, and hygienic lines in food, dairy and pharmaceutical factories. The stainless T17 housing suits washdown areas, and the ambient range of –40 to +85 °C without display suits outdoor sites.

Information to send with an FMB70 RFQ

  • Part number FMB70 and the full order code of any existing unit.
  • Medium, density, process temperature and the pressure or level span with top pressure if any.
  • Accuracy class, output and housing type (T14, T15 or T17).
  • Process connection type and size, and hygienic standard where relevant.
  • Safety and approval needs (SIL, WHG, marine, drinking water, Ex) and the quantity.

Documents and quotation

A copy of the Endress+Hauser technical information for the Deltapilot S FMB70 is attached on this page, with ranges, accuracy tables, connections and approvals.

Send us the FMB70 information above and Seven Star LLC will prepare a quotation for Oman and the GCC.

Datasheets & Documents
  • PDF Datasheet Endress+Hauser FMB70 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Endress+Hauser makes process measurement instruments for flow, level, pressure, temperature and liquid analysis. Georg H. Endress and Ludwig Hauser started the business in Lörrach, Germany, on 1 February 1953, first selling level meters, and the Endress+Hauser name has been used since 1957. The group is headquartered in Reinach, Switzerland, and has been wholly owned by the Endress family since 1975.

Seven Star LLC is an independent supplier listing Endress+Hauser flowmeters, level and pressure transmitters, temperature assemblies and liquid analysis products for buyers in Oman and the GCC. Instruments are matched from the full order code on the nameplate.

Endress+Hauser company profile

Origin Founded in Lörrach, Germany, on 1 February 1953 by the Swiss engineer Georg H. Endress and Ludwig Hauser
Headquarters Endress+Hauser AG, Reinach (Basel-Landschaft), Switzerland
Ownership Family owned; the Endress family has been the sole shareholder since 1975, and a family charter commits the company to stay family owned
Size About 16,500 employees and sales of about EUR 3.7 billion (2023, as reported by the company)
Product families Proline flowmeters, Micropilot and Levelflex radar, Liquiphant switches, Cerabar and Deltabar pressure, iTEMP and iTHERM temperature, Liquiline and Memosens liquid analysis

Milestones

  • 1953: Georg H. Endress and Ludwig Hauser start the business in Lörrach on 1 February, first selling level meters.
  • 1957: The Endress+Hauser name comes into use.
  • 1975: The Endress family becomes sole shareholder.
  • 2023: About 16,500 employees and sales of about EUR 3.7 billion, as reported by the company.

Endress+Hauser product lines

Line Measuring principle Typical use
Promass F 300, Promass 80F, 83F/84F Coriolis mass flow Direct mass flow and density of liquids and gases, hydrocarbon transfer and chemical dosing
Promag P 300, P 500, H 300, W 400, W 10, 50P Electromagnetic flow Water, wastewater, slurries and other conductive liquids
Prowirl F 200, 72F Vortex flow Steam, gas and low-viscosity liquids
Prosonic Flow 92F, t-mass 65F Ultrasonic and thermal mass flow Water lines; compressed air and industrial gases
Micropilot FMR62, FMR67, FMR60, FMR10B, FMR20, FMR50, FMR52 Free-space radar level, 80 GHz and 26 GHz Tanks, process vessels, silos and open water channels
Levelflex FMP51, FMP50, FMP54, FMP55 Guided wave radar level Level and interface in vessels, separators and bypass chambers
Liquiphant FTL51, Prosonic S FMU90 Vibronic point level; ultrasonic level High and low level alarms, pump protection, open channel flow
Cerabar PMC71B, PMP51B, PMP71, Deltabar PMD78B, PMD75 Pressure and differential pressure Process pressure, hydrostatic level and DP flow
iTEMP TMT82, TMT162, iTHERM TM101, TR66, TR10 Temperature transmitters and thermometers RTD and thermocouple points with thermowells
Liquiline CM444, CM442, Memosens CPS11E, Stamolys reagents Liquid analysis pH, ORP, conductivity, dissolved oxygen and nutrient analysis in water treatment and process

Where Endress+Hauser instruments are used

In Oman and the GCC, Endress+Hauser instruments are common in oil and gas production and processing, refineries and petrochemicals, desalination and water networks, wastewater treatment, power plants and food and beverage plants. Coriolis meters measure hydrocarbon and chemical flows, electromagnetic meters cover water and wastewater, radar transmitters handle tank and silo level, and Liquiline analysers monitor water quality. Proline 300 and 500 flowmeters include Heartbeat Technology for in-situ verification, which reduces the need to remove a meter for checks.

Ordering Endress+Hauser instruments: what we need

The order code on the nameplate (for example PMP71-1QA1S11RDADU) defines every option: measuring range, process connection, materials, output, approvals and display. Send it with the serial number; Endress+Hauser can retrieve the original configuration from the serial number. For a new instrument add the medium, operating and design pressure and temperature, range, line size or tank geometry, process connection, wetted materials, output or protocol (4-20 mA HART, PROFIBUS, FOUNDATION Fieldbus, Modbus) and the hazardous-area approval required. Older models such as Promass 80/83 or Micropilot M are replaced by current Proline or 80 GHz Micropilot devices.

Facts checked against Endress+Hauser company history and product information, October 2026.

FAQ

Questions about the Endress+Hauser FMB70 Deltapilot S Hydrostatic

Answers from our engineering team on installation, compatibility and integration.

01What is the Endress+Hauser FMB70?
The FMB70 is the Deltapilot S, a high-accuracy hydrostatic level and pressure transmitter. It uses a condensate-resistant CONTITE cell and has a wide choice of thread, flange and hygienic process connections.
02What accuracy does the FMB70 achieve?
Reference accuracy is ±0.1 % of the set span as standard on the 1.2 bar and larger cells, and ±0.075 % with the platinum option. The 100 and 400 mbar cells are ±0.15 % standard and ±0.1 % platinum.
03Is the FMB70 suitable for SIL applications?
The 4 to 20 mA version has been developed to IEC 61508 and can be used for level and pressure monitoring up to SIL 3. The functional safety manual SD00213P describes the safety functions and settings.
04Which outputs and housings does the FMB70 offer?
Outputs are 4 to 20 mA HART, PROFIBUS PA and FOUNDATION Fieldbus. Housings are T14 aluminium, T15 and the hygienic T17 stainless steel, with optional display and a separate housing version.
05What process temperature does the FMB70 allow?
The process temperature is –10 to +100 °C, and up to +135 °C for a maximum of 30 minutes for cleaning. Ambient limits are –40 to +85 °C without display.