- Automation & ControlView all 1,920 products
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- HMI Displays
- Industrial Computers
- Motor Soft Starters
- Servo Drives
- Pneumatic Cylinders
- Machine Vision
- Automation Software
- Robotics
Brand: ABB
ABB ACS580-07-0430A-4 Cabinet Drive 250 kW 430 A
Description
430 A in frame R9
ACS580-07-0430A-4 is the finished cabinet version of the ACS580 that ABB rates at 250 kW and 400 V. Frame R9 holds the 430 A, 250 kW power stage. Typical jobs are main pumps in water and wastewater plants and heavy process drives. Safe Torque Off and the intuitive control panel with its mounting platform are standard in the cabinet.
Technical specifications
| Parameter | Specification |
|---|---|
| Type designation | ACS580-07-0430A-4 |
| Product family | ACS580-07, cabinet-built general purpose drive |
| Supply voltage | 3-phase 380 to 415 V (400 V table) |
| Typical motor power / nominal current | 250 kW / 430 A |
| Light-overload use | 200 kW, 400 A |
| Heavy-duty use | 200 kW, 363 A (125% overload) |
| Maximum output current | 617 A |
| Frame size | R9 |
| Cabinet height, width, depth | 2145 mm, 530 mm, 673 mm |
| Cabinet weight | 275 kg |
| UL rating at 460 to 480 V | 414 A light-overload, 350 Hp |
| UL heavy duty at 480 V | 361 A, 300 Hp |
| Power loss | 6589 W |
| Input fuses | 700 (170M6411), UL 700 A (170M6411) |
| Safety | Safe Torque Off (SIL 3) |
Duty classes, protection and cooling
The catalogue lists 400 A (200 kW) for light-overload use and 363 A (200 kW) for heavy duty, with a nominal 430 A and a peak of 617 A. The overload definitions are 110% (light) and 125% (heavy duty) for one minute every ten minutes at 40 degrees C. At 440 to 480 V the ratings become 414 A / 350 Hp and 361 A / 300 Hp. Variable-torque loads such as pumps and fans normally use the light-overload column.
Fuse selection: IEC 700 A (170M6411); UL 700 A (170M6411). The cabinet loses 6589 W and reaches 68 dBA. Ratings apply at +40 degrees C, with IP21 to IP54 cabinet options described in the catalogue.
Frame R9 cabinet dimensions are 2145 x 530 x 673 mm and 275 kg. Because the cabinet is pre-engineered, the buyer avoids panel design and gets a tested unit for installation on a plinth.
Filters, fieldbus and options
Read ACS580-07-0430A-4 as series ACS580, construction 7 (cabinet-built drive), size 0430A-4 where the digits are the nominal current, and voltage code 4 for 380 to 480 V. Fieldbus and I/O options include +K457 for FCAN-01 CANopen, +K458 for FSCA-01 Modbus RTU, +K462 for FCNA-01 ControlNet. EMC: C2 for wall-mounted drives and cabinets up to frame R9, C3 for modules and the R10 to R11 cabinets. Chopper and resistor are external for frame R9.
Related ABB products: ABB ACH580-01-430A-4 HVAC AC Drive 250 kW 430 A, ABB ACQ580-01-490A-4 Water Drive 250 kW 490 A, ABB ACS580-01-033A-4 AC Drive 15 kW 32 A, ABB ACS580-01-046A-4 AC Drive 22 kW 45 A, ABB ACS580-01-039A-4 AC Drive 18.5 kW 38 A and ABB ACS580-01-073A-4 AC Drive 37 kW 73 A.
Documentation and ordering
This page follows the linked ACS580 catalogue (3AUA0000145061, Rev G) and the ABB product page for the ACS580-07-0430A-4. Seven Star LLC quotes the ACS580-07-0430A-4 from Muscat after receiving the motor nameplate, supply voltage and option list. Confirm before ordering: the full type code, plus options, motor current, enclosure, braking, fuses and derating for temperature and altitude, using the hardware manuals 3AXD50000018826 and 3AXD50000015497. Send the motor nameplate, supply data, control interface and fieldbus requirement for the ACS580-07-0430A-4 so that the offer lists exactly the plus codes that are needed. More sizes sit in AC drives, and the ABB ACS580 page introduces the family.
Datasheets & Documents
- Catalog ABB general purpose drives ACS580 catalog 3AUA0000145061 (Rev G) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB ACS580-07-0430A-4 Cabinet Drive 250 kW 430 A
Answers from our engineering team on installation, compatibility and integration.
01What are the duty ratings of the ACS580-07-0430A-4?
ABB lists 430 A nominal (250 kW), 400 A (200 kW) light overload, 363 A (200 kW) heavy duty and 617 A maximum output current.
02What construction is the ACS580-07-0430A-4?
It is the ACS580-07 cabinet-built drive in frame R9, a ready-made cabinet 2145 mm high.
03How much heat does the ACS580-07-0430A-4 produce?
The catalogue gives 6589 W of heat dissipation and 68 dBA of noise.
04Does the ACS580-07-0430A-4 include Safe Torque Off?
Yes. Safe Torque Off (SIL 3) is part of the standard drive according to the ACS580 catalogue.
05Which fieldbus options fit the ACS580-07-0430A-4?
The catalogue lists FDNA-01, FPBA-01, FCAN-01, FSCA-01, FCNA-01, FECA-01, FEPL-02, FENA-11 and FENA-21 adapters; Modbus RTU is built in.