Endress+Hauser FMD77 Deltabar S Diaphragm Seal DP Transmitter

Description

Endress+Hauser FMD77 Deltabar S diaphragm seal transmitter

The Endress+Hauser FMD77 is a Deltabar S differential pressure transmitter in which a diaphragm seal is flanged directly to the high-pressure side while a capillary carries the pressure of the low-pressure side. It is described in Technical Information TI00382P (issue 35.24), which also covers the PMD75 and FMD78. The front page lists flow measurement in conjunction with primary devices, level, volume and mass in liquids, differential pressure monitoring of filters and pumps, and process temperatures up to 400 degrees Celsius with diaphragm seal mounting.

Endress+Hauser points out that this arrangement gives a cost-effective installation: with the FMD77 the capillary runs only to the low-pressure side, so you do not need two seals and two capillaries to measure the level in a vessel.

FMD77 benefits

  • Reference accuracy up to 0.035 percent and turn down up to 100 to 1.
  • Used for flow and differential pressure monitoring up to SIL 3, certified to IEC 61508 by TUEV SUED.
  • Patented TempC process membrane reduces errors from ambient and process temperature.
  • Function monitoring from the measuring cell to the electronics, HistoROM/M-DAT for electronics replacement.
  • Membranes in 316L, 316L TempC, Alloy C276, tantalum, Monel and PTFE, plus gold-coated 316L.
  • HART, PROFIBUS PA and FOUNDATION Fieldbus communication.

FMD77 technical overview

Parameter Value
Output 4 to 20 mA HART; PROFIBUS PA; FOUNDATION Fieldbus
Supply, HART 11.5 to 45 V DC (10.5 to 45 V DC without test jumper); Ex i 11.5 to 30 V DC
Cells 100 mbar, 500 mbar, 3 bar, 16 bar, 40 bar (10 and 30 mbar cells are for PMD75 only)
Smallest calibratable span 5 mbar (0.075 psi) for FMD77 and FMD78
Minimum static pressure 50 mbar absolute for silicone oil
Maximum working pressure 160 bar standard; option PN 420 for PMD75
Process temperature minus 70 to plus 400 degrees Celsius, depending on seal and fill fluid
Tantalum membrane seal minus 70 to plus 300 degrees Celsius
Membrane material AISI 316L (1.4435) and the options above
Long-term stability, 100 mbar 0.08 percent 1 year; 0.14 percent 5 years; 0.27 percent 10 years
Long-term stability, 10 and 30 mbar 0.20 percent 1 year; 0.28 percent 5 years; 0.31 percent 10 years
Ambient, without LCD minus 50 to plus 85 degrees Celsius; minus 54 optional
Ambient, with LCD minus 20 to plus 70 degrees Celsius
Ingress protection of cell with FEP cable IP 69, IP 66 and IP 68 (1.83 m water column for 24 hours)

How FMD77 differs from FMD78 and PMD75

The three devices share the electronics and the measuring cell family, but they differ in how the two pressure sides reach the cell. The PMD75 has the cell on the process flange and uses impulse lines or manifold connections. The FMD77 has one diaphragm seal on the high-pressure side with the capillary on the low-pressure side. The FMD78 has diaphragm seals with capillaries on both sides. The datasheet therefore recommends the PMD75 and FMD77 for level in open vessels, and the PMD75 and FMD78 for differential pressure measurement.

In closed vessels all Deltabar S devices are suitable, but the negative side must then always be connected above the maximum level through pressure piping, with a condensate trap if a vapour layer is present.

Using the FMD77 in Oman and the GCC

The FMD77 is selected for level in vessels containing hot, viscous, crystallising or toxic media, such as bitumen tanks, polymer reactors, heat-transfer oil expansion vessels and sulphur pits, where impulse lines would block or freeze. Mounting the seal directly on the vessel nozzle removes one impulse line, so installation cost and leak points drop.

Ordering the FMD77 correctly

The FMD77 order code combines a cell, a diaphragm seal and a capillary, so the base name alone is not enough for a quotation. The datasheet has a separate section on selecting the process connection and capillary for the FMD77, with flange or sanitary seals on the high-pressure side. The required information is: the nominal differential range (for example 500 mbar or 3 bar), the nominal pressure rating of the flange, the seal membrane material, the fill fluid, the capillary length on the low-pressure side, the housing and the display, and the approvals.

Vessel level calculations need the density of the medium and the distance between the high-pressure seal and the point where the low-pressure capillary is connected. If you are replacing an older FMD77, send the nameplate so we can match nominal range, flange and capillary length, and tell us whether the old unit had the TempC membrane.

Installing the FMD77

Mount the device directly on the vessel with the negative side open to atmosphere for open tanks. For closed tanks, run the negative capillary above the maximum level. Support the capillary with clips, avoid sharp bends and keep it away from heat sources. Follow the vacuum application instructions in the datasheet because the minimum static pressure is 50 mbar absolute and the fill-fluid limit is lower in vacuum. Zero the device after mounting to cancel the offset from the fill fluid.

Maintaining the FMD77

Never open or shorten a capillary. Inspect the seal face at shutdowns for build-up and compare the level reading with a dipstick or a reference during the first operation. Keep HistoROM data available when electronics are replaced. Because level readings derive from a density-dependent hydrostatic head, update the configured density if the product changes, and compare against a manual measurement after any recipe change.

Documents and quotation

The Technical Information TI00382P for FMD77 is attached as the datasheet. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Please send FMD77, the quantity and your seal and capillary needs with your RFQ.

Selection Notes for the Endress+Hauser FMD77

When comparing the Endress+Hauser FMD77 with alternatives, start from the duty it must perform: the measured or controlled variable, the range and accuracy you need, the environment at the mounting point and the interface to your control system. Check the electrical and mechanical connections against the installed equipment, and confirm any hazardous-area or ingress-protection requirements for the location. If any point is unclear, send a photo of the nameplate and a short description of the application, and we will compare it with the Endress+Hauser (E & H) pressure transmitters range and confirm the correct order code before you commit.

Datasheets & Documents
  • PDF Datasheet Endress+Hauser FMD77 Deltabar S Diaphragm Seal DP Transmitter Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Endress+Hauser makes process measurement instruments for flow, level, pressure, temperature and liquid analysis. Georg H. Endress and Ludwig Hauser started the business in Lörrach, Germany, on 1 February 1953, first selling level meters, and the Endress+Hauser name has been used since 1957. The group is headquartered in Reinach, Switzerland, and has been wholly owned by the Endress family since 1975.

Seven Star LLC is an independent supplier listing Endress+Hauser flowmeters, level and pressure transmitters, temperature assemblies and liquid analysis products for buyers in Oman and the GCC. Instruments are matched from the full order code on the nameplate.

Endress+Hauser company profile

Origin Founded in Lörrach, Germany, on 1 February 1953 by the Swiss engineer Georg H. Endress and Ludwig Hauser
Headquarters Endress+Hauser AG, Reinach (Basel-Landschaft), Switzerland
Ownership Family owned; the Endress family has been the sole shareholder since 1975, and a family charter commits the company to stay family owned
Size About 16,500 employees and sales of about EUR 3.7 billion (2023, as reported by the company)
Product families Proline flowmeters, Micropilot and Levelflex radar, Liquiphant switches, Cerabar and Deltabar pressure, iTEMP and iTHERM temperature, Liquiline and Memosens liquid analysis

Milestones

  • 1953: Georg H. Endress and Ludwig Hauser start the business in Lörrach on 1 February, first selling level meters.
  • 1957: The Endress+Hauser name comes into use.
  • 1975: The Endress family becomes sole shareholder.
  • 2023: About 16,500 employees and sales of about EUR 3.7 billion, as reported by the company.

Endress+Hauser product lines

Line Measuring principle Typical use
Promass F 300, Promass 80F, 83F/84F Coriolis mass flow Direct mass flow and density of liquids and gases, hydrocarbon transfer and chemical dosing
Promag P 300, P 500, H 300, W 400, W 10, 50P Electromagnetic flow Water, wastewater, slurries and other conductive liquids
Prowirl F 200, 72F Vortex flow Steam, gas and low-viscosity liquids
Prosonic Flow 92F, t-mass 65F Ultrasonic and thermal mass flow Water lines; compressed air and industrial gases
Micropilot FMR62, FMR67, FMR60, FMR10B, FMR20, FMR50, FMR52 Free-space radar level, 80 GHz and 26 GHz Tanks, process vessels, silos and open water channels
Levelflex FMP51, FMP50, FMP54, FMP55 Guided wave radar level Level and interface in vessels, separators and bypass chambers
Liquiphant FTL51, Prosonic S FMU90 Vibronic point level; ultrasonic level High and low level alarms, pump protection, open channel flow
Cerabar PMC71B, PMP51B, PMP71, Deltabar PMD78B, PMD75 Pressure and differential pressure Process pressure, hydrostatic level and DP flow
iTEMP TMT82, TMT162, iTHERM TM101, TR66, TR10 Temperature transmitters and thermometers RTD and thermocouple points with thermowells
Liquiline CM444, CM442, Memosens CPS11E, Stamolys reagents Liquid analysis pH, ORP, conductivity, dissolved oxygen and nutrient analysis in water treatment and process

Where Endress+Hauser instruments are used

In Oman and the GCC, Endress+Hauser instruments are common in oil and gas production and processing, refineries and petrochemicals, desalination and water networks, wastewater treatment, power plants and food and beverage plants. Coriolis meters measure hydrocarbon and chemical flows, electromagnetic meters cover water and wastewater, radar transmitters handle tank and silo level, and Liquiline analysers monitor water quality. Proline 300 and 500 flowmeters include Heartbeat Technology for in-situ verification, which reduces the need to remove a meter for checks.

Ordering Endress+Hauser instruments: what we need

The order code on the nameplate (for example PMP71-1QA1S11RDADU) defines every option: measuring range, process connection, materials, output, approvals and display. Send it with the serial number; Endress+Hauser can retrieve the original configuration from the serial number. For a new instrument add the medium, operating and design pressure and temperature, range, line size or tank geometry, process connection, wetted materials, output or protocol (4-20 mA HART, PROFIBUS, FOUNDATION Fieldbus, Modbus) and the hazardous-area approval required. Older models such as Promass 80/83 or Micropilot M are replaced by current Proline or 80 GHz Micropilot devices.

Facts checked against Endress+Hauser company history and product information, October 2026.

FAQ

Questions about the Endress+Hauser FMD77 Deltabar S Diaphragm Seal DP

Answers from our engineering team on installation, compatibility and integration.

01How is the FMD77 built?
It is a Deltabar S with a diaphragm seal on the high-pressure side mounted directly on the vessel, and a capillary on the low-pressure side, so it is cost-effective for level measurement.
02Which vessels suit the FMD77?
The datasheet says the PMD75 and FMD77 are best suited to level measurement in open vessels, while all Deltabar S devices suit closed vessels when the negative side is connected above the maximum level.
03What temperature range can the FMD77 handle?
Depending on the diaphragm seal and fill fluid, minus 70 to plus 400 degrees Celsius, and tantalum membrane seals cover minus 70 to plus 300 degrees Celsius.
04What is the minimum static pressure of the FMD77?
The minimum static pressure is 50 mbar absolute for FMD77 and FMD78 with silicone oil, and the smallest calibratable span is 5 mbar.
05How do I request an FMD77 quote?
Send FMD77 with the differential range, high-side seal type and size, capillary length for the low side, fill fluid, protocol and quantity in your RFQ.