Brand: Endress+Hauser (E & H)
Endress+Hauser PMD50 Deltabar HART DP Transmitter
Description
Endress+Hauser PMD50 Deltabar HART differential pressure transmitter
The Endress+Hauser PMD50 is a HART differential pressure transmitter with a metallic process membrane for monitoring differential pressure, level and flow in liquids and gases. It is the straightforward, standard-industry member of the Deltabar family: one communication protocol (4 to 20 mA with HART 7), a colour display with a magnetic button, wizard-guided commissioning and write protection that can be set by hardware or software. Seven Star LLC supplies the PMD50 in Oman and the GCC as an independent supplier based in Muscat.
Measuring cells run from 100 mbar to 40 bar (1.5 to 600 psi) with static pressure up to 250 bar (3 626 psi), and the Platinum version reaches ±0.05 % reference accuracy. The datasheet quotes a response time below 100 ms in its summary, with the detailed dynamic data given per cell in the performance section.
PMD50 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Endress+Hauser PMD50 (Deltabar) |
| Measured variable | Differential pressure; level, volume, mass and flow by calculation |
| Measuring cells | 100, 500 mbar and 3, 16, 40 bar (1.5 to 600 psi), bidirectional around zero |
| Static pressure (MWP) | PN 160: 160 bar (2 400 psi); PN 250: 250 bar (3 626 psi) with pressure on both sides; 100 bar if only the negative side of the 40 bar cell is loaded |
| Reference accuracy | Standard: ±0.065 %; Platinum: ±0.05 % up to 5:1 turn down |
| Turn down | Up to 100:1 standard; 5:1 for Platinum; larger on request |
| Long-term stability | 500 mbar and above: ±0.05 % of URL in 1 year, ±0.25 % over 10 years; 100 mbar cell: ±0.07 % in 1 year |
| Dynamic behaviour (HART) | Dead time max. 50 ms; T63 max. 85 ms and T90 max. 150 ms on cells above 100 mbar; warm-up 5 s or less |
| Process temperature at transmitter | –40 to +85 °C; at a manifold up to 110 °C |
| Ambient temperature | –40 to +85 °C; inert-oil devices not below –20 °C |
| Output | 4 to 20 mA with HART 7 (device type ID 0x11E1) |
| Supply voltage | 10.5 to 35 V DC (10.5 to 30 V DC Ex i); maximum supply current limited to 500 mA |
| Damping | 0 to 999 s, factory setting 1 s |
| Wetted materials | 316L (1.4435) or Alloy C276 membrane, optional 25 µm gold coating; 316L cell body; PTFE, FKM, EPDM or FFKM seals |
| Housing | Dual-compartment, aluminium (about 1.4 kg) or stainless steel (about 3.3 kg), IP66/68 Type 4X/6P |
| Functional safety | 4 to 20 mA devices developed to IEC 61508 for monitoring up to SIL 3 (Functional Safety Manual) |
Values are from the Endress+Hauser Technical Information for the Deltabar PMD50 (HART). Pressure limits depend on the ordered process connection and seal.
How the PMD50 works
Each process pressure deflects its own metallic membrane. A fill fluid, silicone oil or inert oil, passes the pressures to the two sides of a silicon measuring element with a middle diaphragm. The net deflection follows the difference between p1 and p2, and a semiconductor resistance bridge converts it into an electrical signal that the electronics scale, linearise and output as 4 to 20 mA with HART. The primary variable is pressure, the secondary variable is sensor temperature and the tertiary variable is electronics temperature.
The linearisation function converts measured pressure into height or volume using user tables of up to 32 point pairs. In flow applications the low flow cut-off parameter suppresses small flows that would otherwise produce a noisy measured value; it is preset to 5 % when the square root output transfer function is used.
PMD50 compared with the other Deltabar models
| Model | Communication | Range and accuracy | Typical role |
|---|---|---|---|
| PMD50 | HART 7, 4 to 20 mA | 100 mbar to 40 bar; up to ±0.05 % | Standard industry DP, level and flow |
| PMD55B | HART or PROFINET over Ethernet-APL; Bluetooth; Heartbeat | 10 mbar to 40 bar; up to ±0.055 % | High-performance DP with digital options |
| PMD63B | HART, PROFIBUS PA or APL; Bluetooth; Heartbeat | 100 mbar to 40 bar with diaphragm seals | Hot, sticky or remote points with capillaries |
The PMD50 shares its measuring cell technology with the established Deltabar line, so existing knowledge of orientation codes, manifolds and impulse piping carries over. If you only need a gauge pressure measurement, the single-sided counterpart in the Cerabar range is the PMP63B or the diaphragm seal PMP55.
PMD50 selection and ordering checklist
- Differential range: choose the cell whose upper limit covers the maximum expected differential pressure; do not oversize, because turn down above 5:1 reduces the Platinum accuracy.
- Static pressure class: PN 160 or PN 250, noting the negative-side limit for the 40 bar cell.
- Membrane and seals: 316L or Alloy C276 membrane with PTFE, FKM, EPDM or FFKM seals matching the medium.
- Fill fluid: silicone oil as the general choice, or inert oil, which must not be used below –20 °C.
- Process connection: 1/4-18 NPT side flanges with the mounting thread you need (UNF 7/16-20, M10 or M12) and cast 316L or other flange material.
- Housing and approvals: aluminium or stainless dual-compartment housing, and the Ex protection type required.
- Marine: the datasheet lists ABS marine approval for the family; check the code if class approval matters.
PMD50 installation, commissioning and maintenance
Mount the transmitter to suit the medium: above the tapping points for gas so condensate drains away, below them for steam with condensate pots, and below the lowest tapping for liquid. Use a manifold so zeroing is possible while the process stays online. Where process temperature exceeds 85 °C, apply the reduced ambient temperature rule and insulate impulse lines sensibly.
Commissioning is wizard-driven: set the units, range and damping, then trim zero with equal pressure on both sides. The magnetic button on the housing lets you operate the colour display through the closed cover, which is handy in Ex d enclosures. For maintenance, keep a record of the zero drift: the datasheet gives ±0.05 % of URL in the first year on most cells. Use maximum, not nominal, response values when the transmitter acts in a control or safety circuit.
Typical PMD50 applications in Oman and the GCC
The PMD50 is used across Oman and the GCC for differential pressure on strainers, coalescers and cartridge filters, orifice-plate flow on cooling water, fuel gas, air and steam headers, and level in closed tanks in power, water and process plants. In desalination units it monitors membrane and cartridge filter pressure drop, and in oil and gas facilities it supports pump and compressor protection. In very hot sites avoid direct sun on the housing, route impulse lines away from hot surfaces, and use the stainless housing in coastal environments with salt-laden air.
Information to send with a PMD50 RFQ
- Part number PMD50 and the complete order code if you are replacing an installed unit.
- Differential pressure range, static pressure and process temperature.
- Medium (gas, steam or liquid) and measurement task: flow, level or filter monitoring.
- Wetted material, seal material, fill fluid and process connection.
- Ex approval, housing material, manifold requirement and quantity.
Documents and quotation
The Endress+Hauser Technical Information for the Deltabar PMD50 is attached on this page, with the ranges, performance tables and ordering structure.
Send us the PMD50 details above and Seven Star LLC will prepare a quotation for Oman and the GCC.
Other Models in the Eh Deltabar Dp Range
Seven Star LLC supplies models from the Eh Deltabar Dp range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Endress+Hauser PMD55B Deltabar Differential Pressure Transmitter | Pressure Instrumentation | View details |
| Endress+Hauser PMD50 Deltabar HART DP Transmitter | Pressure Instrumentation | You are viewing this model |
Datasheets & Documents
- Datasheet Endress+Hauser PMD50 Technical Information Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Endress+Hauser makes process measurement instruments for flow, level, pressure, temperature and liquid analysis. Georg H. Endress and Ludwig Hauser started the business in Lörrach, Germany, on 1 February 1953, first selling level meters, and the Endress+Hauser name has been used since 1957. The group is headquartered in Reinach, Switzerland, and has been wholly owned by the Endress family since 1975.
Seven Star LLC is an independent supplier listing Endress+Hauser flowmeters, level and pressure transmitters, temperature assemblies and liquid analysis products for buyers in Oman and the GCC. Instruments are matched from the full order code on the nameplate.
Endress+Hauser company profile
| Origin | Founded in Lörrach, Germany, on 1 February 1953 by the Swiss engineer Georg H. Endress and Ludwig Hauser |
|---|---|
| Headquarters | Endress+Hauser AG, Reinach (Basel-Landschaft), Switzerland |
| Ownership | Family owned; the Endress family has been the sole shareholder since 1975, and a family charter commits the company to stay family owned |
| Size | About 16,500 employees and sales of about EUR 3.7 billion (2023, as reported by the company) |
| Product families | Proline flowmeters, Micropilot and Levelflex radar, Liquiphant switches, Cerabar and Deltabar pressure, iTEMP and iTHERM temperature, Liquiline and Memosens liquid analysis |
Milestones
- 1953: Georg H. Endress and Ludwig Hauser start the business in Lörrach on 1 February, first selling level meters.
- 1957: The Endress+Hauser name comes into use.
- 1975: The Endress family becomes sole shareholder.
- 2023: About 16,500 employees and sales of about EUR 3.7 billion, as reported by the company.
Endress+Hauser product lines
| Line | Measuring principle | Typical use |
|---|---|---|
| Promass F 300, Promass 80F, 83F/84F | Coriolis mass flow | Direct mass flow and density of liquids and gases, hydrocarbon transfer and chemical dosing |
| Promag P 300, P 500, H 300, W 400, W 10, 50P | Electromagnetic flow | Water, wastewater, slurries and other conductive liquids |
| Prowirl F 200, 72F | Vortex flow | Steam, gas and low-viscosity liquids |
| Prosonic Flow 92F, t-mass 65F | Ultrasonic and thermal mass flow | Water lines; compressed air and industrial gases |
| Micropilot FMR62, FMR67, FMR60, FMR10B, FMR20, FMR50, FMR52 | Free-space radar level, 80 GHz and 26 GHz | Tanks, process vessels, silos and open water channels |
| Levelflex FMP51, FMP50, FMP54, FMP55 | Guided wave radar level | Level and interface in vessels, separators and bypass chambers |
| Liquiphant FTL51, Prosonic S FMU90 | Vibronic point level; ultrasonic level | High and low level alarms, pump protection, open channel flow |
| Cerabar PMC71B, PMP51B, PMP71, Deltabar PMD78B, PMD75 | Pressure and differential pressure | Process pressure, hydrostatic level and DP flow |
| iTEMP TMT82, TMT162, iTHERM TM101, TR66, TR10 | Temperature transmitters and thermometers | RTD and thermocouple points with thermowells |
| Liquiline CM444, CM442, Memosens CPS11E, Stamolys reagents | Liquid analysis | pH, ORP, conductivity, dissolved oxygen and nutrient analysis in water treatment and process |
Where Endress+Hauser instruments are used
In Oman and the GCC, Endress+Hauser instruments are common in oil and gas production and processing, refineries and petrochemicals, desalination and water networks, wastewater treatment, power plants and food and beverage plants. Coriolis meters measure hydrocarbon and chemical flows, electromagnetic meters cover water and wastewater, radar transmitters handle tank and silo level, and Liquiline analysers monitor water quality. Proline 300 and 500 flowmeters include Heartbeat Technology for in-situ verification, which reduces the need to remove a meter for checks.
Ordering Endress+Hauser instruments: what we need
The order code on the nameplate (for example PMP71-1QA1S11RDADU) defines every option: measuring range, process connection, materials, output, approvals and display. Send it with the serial number; Endress+Hauser can retrieve the original configuration from the serial number. For a new instrument add the medium, operating and design pressure and temperature, range, line size or tank geometry, process connection, wetted materials, output or protocol (4-20 mA HART, PROFIBUS, FOUNDATION Fieldbus, Modbus) and the hazardous-area approval required. Older models such as Promass 80/83 or Micropilot M are replaced by current Proline or 80 GHz Micropilot devices.
Facts checked against Endress+Hauser company history and product information, October 2026.
Browse Endress+Hauser products by category: Flowmeters, Level Transmitter, Pressure Instrumentation, Temperature, Liquid Analysis Sensors, Liquid Analytical Systems.
FAQ
Questions about the Endress+Hauser PMD50 Deltabar HART DP Transmitter
Answers from our engineering team on installation, compatibility and integration.
01What is the PMD50 used for?
The PMD50 is a HART differential pressure transmitter with a metallic membrane for filter or strainer monitoring, orifice flow measurement and level measurement in pressurised vessels with liquids or gases.
02What ranges and accuracy does the PMD50 offer?
There are five cells from 100 mbar up to 40 bar. Standard accuracy is ±0.065 % and Platinum is ±0.05 % up to a 5:1 turn down. Standard turn down reaches 100:1, with larger values on request.
03What static pressure can the PMD50 withstand?
The PN 160 version has a maximum working pressure of 160 bar and the PN 250 version 250 bar when both sides are loaded. For the 40 bar cell with only the negative side pressurised the limit is 100 bar.
04Does the PMD50 have a display?
Yes. It has a colour display that can be operated through the cover with a magnetic button, in a dual-compartment aluminium or stainless steel housing with IP66/68 Type 4X/6P protection.
05Can the PMD50 be used in a safety function?
The datasheet states that devices with the 4 to 20 mA output were developed to IEC 61508 and can be used to monitor pressure and level up to SIL 3. The Functional Safety Manual and your exact order code define the permitted use.