Brand: Endress+Hauser (E & H)
Endress+Hauser FMX11 Waterpilot Compact Level Probe
Description
Endress+Hauser FMX11 Waterpilot overview
The Endress+Hauser FMX11 Waterpilot is a very compact pressure sensor for hydrostatic level measurement in fresh water, described in Technical Information TI01524P (issue 08.2020). The datasheet lists groundwater wells (suitable for narrow 1 inch pipes), surface water monitoring in rivers and lakes, and drinking-water extraction as typical uses. The sensor is easy to install and commission, and its materials are suitable for drinking water. The output is a two-wire 4 to 20 mA analog signal with a signal range of 2 to 22 mA.
Inside, a metal isolating diaphragm transfers pressure through filling oil to a semiconductor Wheatstone bridge. A pressure compensation tube inside the extension cable provides the atmospheric reference, so the reading is the pure hydrostatic pressure.
FMX11 features
- Compact probe for narrow 1 inch pipes and small boreholes.
- Five fixed ranges from 0.2 bar (2 mH2O) to 2 bar (20 mH2O), plus customer-specific calibration.
- Integrated overvoltage protection to EN 61000-4-5 at 2 kV asymmetrical.
- Reverse polarity protection integrated, T90 time 15 ms or less, warm-up 10 s or less.
- Protection cap on the measuring cell and TPE cable for water and drinking water.
- IP68, permanently hermetically sealed up to 10 bar.
FMX11 specification
| Parameter | Value |
|---|---|
| Ranges (bar / level) | 0.2 bar / 2 mH2O; 0.4 / 4; 0.6 / 6; 1.0 / 10; 2.0 / 20 |
| Overload OPL | 1, 2, 5, 5 and 10 bar absolute for the five ranges |
| Burst pressure at least | 1.5, 3, 7.5, 7.5 and 10 bar absolute |
| Negative pressure | minus 0.7 to minus 1 bar absolute depending on range (unrestricted vacuum resistance) |
| Output | 4 to 20 mA, 2-wire, signal range 2 to 22 mA |
| Current consumption | at least 2 mA, at most 22 mA |
| Maximum load | (supply voltage minus 8 V) divided by 22 mA, less cable resistance of 0.09 ohm per metre and wire |
| Reference accuracy | 0.35 percent for 400 mbar and above; 0.5 percent below 400 mbar |
| Long-term stability | 0.1 percent of URL per year |
| Temperature coefficient | 0.15 percent per 10 K of URL, 0 to 70 degrees Celsius |
| Medium temperature | 0 to plus 70 degrees Celsius; limit minus 10 to plus 70 |
| Response | T90 15 ms or less; warm-up 10 s or less |
| Extension cable | 2 x 0.22 square millimetre shielded with pressure compensation tube, 6 mm outer diameter |
| Cable length tolerance | less than 50 mm |
How FMX11 differs from FMX167
The FMX11 is the compact, economical fresh-water probe: five ranges up to 20 mH2O, 0.35 percent accuracy, a TPE cable and no hazardous-area versions. The FMX167 has a ceramic cell, nine fixed ranges up to 200 mH2O, 0.2 percent accuracy, three housing versions (22 mm, 42 mm and 29 mm plastic), PE, PUR or FEP cables, an optional Pt100 and a large selection of approvals including ATEX II 2 G, FM and CSA. In other words, the FMX11 suits clean water at a lower cost, while the FMX167 covers wastewater, seawater and hazardous areas.
FMX11 duties in Oman and the GCC
The FMX11 is a natural fit for water-supply boreholes, observation wells, reservoir and water-tower level, river or wadi gauging, and irrigation storage. Its small diameter allows installation in tubes where bigger probes will not enter, which is common in groundwater monitoring.
Choosing an FMX11 range
The five fixed ranges correspond to simple water depths: 0.2 bar is 2 m, 0.4 bar is 4 m, 0.6 bar is 6 m, 1 bar is 10 m and 2 bar is 20 m of water column. The datasheet gives overload limits of 1, 2, 5, 5 and 10 bar absolute and burst pressures of at least 1.5, 3, 7.5, 7.5 and 10 bar absolute, so a pump surge or a water hammer in a pressurised main is more likely to exceed the lowest range than the higher ones. Choose the nominal range slightly above the highest expected water column, because accuracy is quoted as 0.35 percent for ranges from 400 mbar upward but 0.5 percent below that.
Customer-specific calibrations are also possible when you know the depth of the well; give us the zero level, the maximum level and the water density, and we will check it against the standard ranges. Remember that the temperature coefficient is 0.15 percent per 10 K of the upper range limit between 0 and 70 degrees Celsius, so a cold deep well is not a problem, but a sun-heated shallow tank may add measurable error.
Installing the FMX11
Suspend the probe on its extension cable at a point free from flow and turbulence or in a guide tube; the datasheet advises that a guide tube inner diameter be at least 1 mm larger than the probe. Keep the cable bending radius generous and end the cable in a dry room or in the suitable terminal box (IP66/IP67). Because the length of the cable sets the zero point, define the level zero before ordering.
Maintaining the FMX11
Lift the probe occasionally and rinse it in clean water, keeping the protection cap in place. Check the 4 mA zero in air and compare readings with a dip tape. Use the overvoltage protection recommended in the datasheet upstream and downstream of the display in lightning-prone areas, for example an HAW unit from the manufacturer, and keep the cable ending in a dry room or a closed terminal box. Never pull the probe by the cable alone when it is stuck in a narrow pipe.
Documents and quotation
Technical Information TI01524P for FMX11 is attached as the datasheet. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Please send FMX11, range, cable length and quantity with your RFQ.
What to Include in Your Endress+Hauser FMX11 Enquiry
An accurate quotation for the Endress+Hauser FMX11 depends on a few details. Please share the complete part number, any suffix codes for options or approvals, the operating conditions at the installation point, and whether certificates of conformity or test reports must ship with the goods. It also helps to know whether the unit is for planned maintenance, a shutdown or an urgent breakdown, because that decides how it is sourced and shipped. With this information our team can check compatibility with your existing pressure transmitters and reply with availability and a realistic delivery estimate.
Spares and Lifecycle Considerations
For critical service, many plants hold one Endress+Hauser FMX11 as an operational spare rather than waiting for a failure. When you plan spares, look at how many identical pressure transmitters units are installed, how long a replacement would take to arrive, and the cost of an unplanned stop. Store spare units in their original packaging in a dry, temperature-controlled area and record the part number and serial number in your maintenance system. We can quote single units or a small spares package and confirm the lead time for each item in writing.
Other Models in the Eh Waterpilot Range
Seven Star LLC supplies models from the Eh Waterpilot range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Endress+Hauser FMX21 Waterpilot Hydrostatic Level Probe | Hydrostatic & DP Level Transmitters | View details |
| Endress+Hauser FMX11 Waterpilot Compact Level Probe | Pressure Transmitters | You are viewing this model |
| Endress+Hauser FMX167 Waterpilot Ceramic Level Probe | Pressure Transmitters | View details |
Datasheets & Documents
- Datasheet Endress+Hauser FMX11 Waterpilot Compact Level Probe Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Endress+Hauser makes process measurement instruments for flow, level, pressure, temperature and liquid analysis. Georg H. Endress and Ludwig Hauser started the business in Lörrach, Germany, on 1 February 1953, first selling level meters, and the Endress+Hauser name has been used since 1957. The group is headquartered in Reinach, Switzerland, and has been wholly owned by the Endress family since 1975.
Seven Star LLC is an independent supplier listing Endress+Hauser flowmeters, level and pressure transmitters, temperature assemblies and liquid analysis products for buyers in Oman and the GCC. Instruments are matched from the full order code on the nameplate.
Endress+Hauser company profile
| Origin | Founded in Lörrach, Germany, on 1 February 1953 by the Swiss engineer Georg H. Endress and Ludwig Hauser |
|---|---|
| Headquarters | Endress+Hauser AG, Reinach (Basel-Landschaft), Switzerland |
| Ownership | Family owned; the Endress family has been the sole shareholder since 1975, and a family charter commits the company to stay family owned |
| Size | About 16,500 employees and sales of about EUR 3.7 billion (2023, as reported by the company) |
| Product families | Proline flowmeters, Micropilot and Levelflex radar, Liquiphant switches, Cerabar and Deltabar pressure, iTEMP and iTHERM temperature, Liquiline and Memosens liquid analysis |
Milestones
- 1953: Georg H. Endress and Ludwig Hauser start the business in Lörrach on 1 February, first selling level meters.
- 1957: The Endress+Hauser name comes into use.
- 1975: The Endress family becomes sole shareholder.
- 2023: About 16,500 employees and sales of about EUR 3.7 billion, as reported by the company.
Endress+Hauser product lines
| Line | Measuring principle | Typical use |
|---|---|---|
| Promass F 300, Promass 80F, 83F/84F | Coriolis mass flow | Direct mass flow and density of liquids and gases, hydrocarbon transfer and chemical dosing |
| Promag P 300, P 500, H 300, W 400, W 10, 50P | Electromagnetic flow | Water, wastewater, slurries and other conductive liquids |
| Prowirl F 200, 72F | Vortex flow | Steam, gas and low-viscosity liquids |
| Prosonic Flow 92F, t-mass 65F | Ultrasonic and thermal mass flow | Water lines; compressed air and industrial gases |
| Micropilot FMR62, FMR67, FMR60, FMR10B, FMR20, FMR50, FMR52 | Free-space radar level, 80 GHz and 26 GHz | Tanks, process vessels, silos and open water channels |
| Levelflex FMP51, FMP50, FMP54, FMP55 | Guided wave radar level | Level and interface in vessels, separators and bypass chambers |
| Liquiphant FTL51, Prosonic S FMU90 | Vibronic point level; ultrasonic level | High and low level alarms, pump protection, open channel flow |
| Cerabar PMC71B, PMP51B, PMP71, Deltabar PMD78B, PMD75 | Pressure and differential pressure | Process pressure, hydrostatic level and DP flow |
| iTEMP TMT82, TMT162, iTHERM TM101, TR66, TR10 | Temperature transmitters and thermometers | RTD and thermocouple points with thermowells |
| Liquiline CM444, CM442, Memosens CPS11E, Stamolys reagents | Liquid analysis | pH, ORP, conductivity, dissolved oxygen and nutrient analysis in water treatment and process |
Where Endress+Hauser instruments are used
In Oman and the GCC, Endress+Hauser instruments are common in oil and gas production and processing, refineries and petrochemicals, desalination and water networks, wastewater treatment, power plants and food and beverage plants. Coriolis meters measure hydrocarbon and chemical flows, electromagnetic meters cover water and wastewater, radar transmitters handle tank and silo level, and Liquiline analysers monitor water quality. Proline 300 and 500 flowmeters include Heartbeat Technology for in-situ verification, which reduces the need to remove a meter for checks.
Ordering Endress+Hauser instruments: what we need
The order code on the nameplate (for example PMP71-1QA1S11RDADU) defines every option: measuring range, process connection, materials, output, approvals and display. Send it with the serial number; Endress+Hauser can retrieve the original configuration from the serial number. For a new instrument add the medium, operating and design pressure and temperature, range, line size or tank geometry, process connection, wetted materials, output or protocol (4-20 mA HART, PROFIBUS, FOUNDATION Fieldbus, Modbus) and the hazardous-area approval required. Older models such as Promass 80/83 or Micropilot M are replaced by current Proline or 80 GHz Micropilot devices.
Facts checked against Endress+Hauser company history and product information, October 2026.
Browse Endress+Hauser products by category: Flowmeters, Level Transmitter, Pressure Instrumentation, Temperature, Liquid Analysis Sensors, Liquid Analytical Systems.
FAQ
Questions about the Endress+Hauser FMX11 Waterpilot Compact Level Probe
Answers from our engineering team on installation, compatibility and integration.
01What is the FMX11 for?
It is a compact pressure sensor for hydrostatic level measurement in fresh water, such as groundwater wells (suitable for narrow 1 inch pipes), rivers, lakes and drinking water extraction.
02Which ranges does the FMX11 have?
Relative nominal pressures of 0.2, 0.4, 0.6, 1.0 and 2.0 bar, equal to 2, 4, 6, 10 and 20 metres of water column, plus customer-specific calibrations.
03What accuracy is quoted for the FMX11?
Maximum plus or minus 0.35 percent for sensor ranges of 400 mbar and above and 0.5 percent below 400 mbar, with long-term stability of 0.1 percent of URL per year.
04How fast does the FMX11 respond?
The T90 time is 15 ms or less and the warm-up period is 10 seconds or less.
05What do I need for an FMX11 quotation?
Send FMX11 with the nominal range, extension cable length and the quantity in your RFQ, and say whether you need a terminal box or overvoltage protection.


















Reviews
There are no reviews yet.