- Automation & ControlView all 1,608 products
- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Industrial Computers
- Servo Drives
- Motor Soft Starters
- HMI Displays
- Pneumatic Cylinders
- Isolator & Barrier
- Automation Software
- Machine Vision
- Robotics
Brand: ABB
ABB ACS880-01-105A-3 Wall-Mounted Drive 55 kW 105 A
Description
105 A from a wall-mounted ACS880
ACS880-01-105A-3 is the 400 V wall-mounted ACS880 type with 105 A nominal output. The power stage delivers 105 A (55 kW typical motor power) in frame R6. Typical jobs are shredders and crushers and test stands with high inertia. The ACS880 platform brings direct torque control, built-in Safe Torque Off and a choke for harmonic filtering, so a cabinet needs little else around the power part.
Technical specifications
| Parameter | Specification |
|---|---|
| Type designation | ACS880-01-105A-3 |
| Series | ACS880-01, wall-mounted single drive, ACS880 industrial drive platform |
| Nominal rating | 55 kW, 105 A |
| Light-overload rating | 100 A = 55 kW |
| Heavy-duty rating | 87 A = 45 kW |
| Maximum output current | 148 A |
| Frame size | R6 |
| IP21 height, width, depth, weight | 726 mm with cable box (569 mm without), 251 mm, 357 mm, 42.2 kg |
| IP55 size (H x W x D) | 726 x 251 x 421 mm; 42.9 kg |
| Noise level | 68 dB(A) |
| Heat dissipation | 1215 W |
| Air flow | 435 m3/h |
| Brake chopper | A selectable internal option, order code +D150 |
| Standard brake resistor | SAFUR80F500 (6 ohm, 2400 kJ, 6 kW continuous) |
| Minimum brake resistance | 5.4 ohm for 55 kW braking power |
| Sine filter type | B84143V0130S230 (rated 91 A) |
Sizing and installing the ACS880-01-105A-3
From the ratings table: nominal 105 A / 55 kW, light overload 100 A / 55 kW, heavy duty 87 A / 45 kW, IMAX 148 A. Variable-torque loads normally use the light overload column; constant-torque machinery should be sized from the heavy-duty column. Match the motor current and check ambient temperature and altitude derating in the manual.
Frame R6 in IP21: height 726 mm including the cable box and 569 mm without, width 251 mm, depth 357 mm, mass 42.2 kg. The IP55 version for dusty and wet places is 726 x 251 x 421 mm and 42.9 kg. Allow 1215 W of heat loss, 435 m3/h of air flow and a sound level of 68 dB(A) in cabinet and room planning.
What can be added to the ACS880-01-105A-3
Dynamic braking: chopper a selectable internal option, order code +D150; resistor SAFUR80F500 (6 ohm, 2400 kJ, 6 kW continuous); minimum 5.4 ohm at 55 kW. Order +E202 for a C2 filter, +E200 for C3 or +E201 for IT networks; the standard drive meets C4 on grounded networks. For long cables, submersible pumps or noise reduction, ABB lists the B84143V0130S230 sine filter (91 A, 45 kW).
Standard I/O is 6 digital inputs, 2 DIO, 2 analog inputs, 2 analog outputs and 3 relay outputs, plus STO and the RS485 link. Three option slots take fieldbus adapters, I/O extensions, feedback modules and a safety functions module.
Related ABB products: ABB ACS580-01-106A-4 AC Drive 55 kW 106 A, ABB ACQ580-01-145A-4 Water Drive 75 kW 145 A, ABB ACS580-01-145A-4 AC Drive 75 kW 145 A, ABB ACQ580-01-12A7-4 Water Drive 5.5 kW 12.6 A, ABB ACQ580-01-018A-4 Water Drive 7.5 kW 17 A and ABB ACQ580-01-05A7-4 Water Drive 2.2 kW 5.6 A.
Documents and quotation
All values above come from ABB’s ACS880 single drives catalogue 3AUA0000098111 (linked here) and the ABB product page for the ACS880-01-105A-3. Seven Star LLC quotes the ACS880-01-105A-3 from Muscat once it has the motor nameplate, supply voltage and option list. Please confirm the type code, options, motor data and ambient conditions before you order; the catalogue revision may be newer than the linked copy. Browse neighbouring ratings in AC drives; for a lighter general purpose range see the ABB ACS580 drive.
Datasheets & Documents
- Catalog ABB ACS880 single drives catalog (3AUA0000098111) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
Related products
Frequently Asked Questions
ABB lists 105 A nominal (55 kW), 100 A (55 kW) for light overload, 87 A (45 kW) for heavy duty and 148 A maximum output current.
It is frame R6: 726 mm high with cable entry box, 251 mm wide, 357 mm deep and 42.2 kg; the IP55 version is 726 x 251 x 421 mm and 42.9 kg.
The brake chopper is a selectable internal option, order code +D150; the catalogue lists SAFUR80F500 (6 ohm) and a minimum resistance of 5.4 ohm.
The catalogue gives 1215 W of heat dissipation, 435 m3/h of air flow and 68 dB(A) noise.
The catalogue lists +E202 for C2, +E200 for C3 and +E201 for ungrounded networks; category C4 is standard on 380 to 500 V ACS880-01 drives.