Schneider Electric 15335 Acti9 IH 24 h Mechanical Time Switch

Description

15335 Acti9 IH 24 h mechanical time switch, without memory

The 15335 is a single-channel mechanical time switch from the Schneider Electric Acti9 IH family, built around a 24 h cycle and supplied for 230 V AC at 50 Hz. It is 18 mm wide (2 modules of 9 mm) and mounts on DIN rail, which makes it a simple way to automate a lighting or small-load circuit in a distribution board without any programming menus. Seven Star LLC supplies the 15335 in Oman and the GCC as an independent supplier based in Muscat.

This page reads the official datasheet of the 15335 and sets out what it can switch, how finely it can be set, and how it differs from the other IH time switches. The product is described on the datasheet as without memory, and the practical consequences of that are covered in the power-reserve section below.

15335 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / 15335
Range / product name Acti9 IH
Product type Mechanical time switch
Channels 1
Setting Manual time changeover
Application Building
Cycle duration 24 h
Maximum number of switchings 48 on – 48 off
Minimum interval 15 min
Accuracy ± 1 s/day 20 °C
Rated operational voltage 230 V AC at 50 Hz
Power consumption 0.5 W
Maximum switching current 16 A – 250 V AC pf = 1; 4 A – 250 V AC pf = 0.6
Mounting DIN rail
Width in 9 mm pitches 2
Terminals Screw terminals
Dimensions 90 mm x 18 mm x 66 mm (H x W x D)
Net weight 0.097 kg
Colour White (RAL 9003)
Operating temperature -25–50 °C
Protection Terminals: IP20 B
Warranty 18 months

How the 15335 is set and what its limits are

The IH family is set by hand: the datasheet gives the type of setting as manual time changeover, with a cycle of 24 h, a maximum of 48 on – 48 off switchings per cycle and a minimum interval of 15 min between them. Accuracy is ± 1 s/day 20 °C, which is more than adequate for street, facade or signage lighting but not a replacement for a networked clock.

Because the same program repeats every day, a mechanical switch like this unit is best where the daily pattern is constant. If your site needs different schedules on weekdays and at weekends, or holiday exceptions, look at the programmable IHP and IC Astro models instead; the table in this page’s family section shows the neighbouring options.

Power reserve and supply on the 15335

The datasheet lists no battery life and no backup time for this version, which matches its designation as the variant without memory: if the supply is lost, the clock cannot be expected to keep time through the outage.

Rated operational voltage is 230 V AC at 50 Hz, and the device draws 0.5 W itself. Connections are screw terminals. Check the supply voltage and frequency of the board before ordering, because the three IH versions on this page do not share the same supply range.

Loads the 15335 can switch

The contact is rated 16 A – 250 V AC pf = 1 and 4 A – 250 V AC pf = 0.6. The datasheet also lists lamp-type limits, shown below. Capacitive and electronic loads are listed separately because inrush current, not the steady load, usually decides the choice.

  • Parallel-corrected fluorescent tube 5 × 58 W 4.7 µF
  • Parallel-corrected fluorescent tube 7 × 40 W 7 µF
  • Parallel-corrected fluorescent tube 2 × 100 W 18 µF
  • 230 V AC halogen lamp 1000 W
  • 230 V AC incandescent lamp 1000 W
  • Fluocompact lamp 700 VA
  • Compact fluorescent lamp 150 W
  • LED lamp < 2 W 30 W
  • LED lamp ≥ 2 W 300 W

For motors, heaters or anything near the contact rating, switch through a contactor and use the time switch only as the control element.

15335 compared with the other IH time switches

The three IH references covered here share the 24 h mechanical principle but differ in supply, reserve and housing. The comparison uses the datasheet values.

Part number Cycle Supply Backup Width Terminals
15335 (this page) 24 h 230 V AC at 50 Hz none listed 18 mm Screw terminals
15336 24 h 230–240 V AC at 50–60 Hz 150 h time and program saving 18 mm Screw terminals
CCT15365 24 h 110–230 V AC at 50–60 Hz 150 h time and program saving 230 V AC; 75 h time and program saving 110 V AC 54 mm Screwless terminals

Selection checklist for the 15335

  • Supply: 230 V AC at 50 Hz.
  • Housing: 18 mm wide (2 modules of 9 mm), screw terminals.
  • Daily pattern: one repeating 24 h program is enough.
  • Load: within the lamp or load table above, or through a contactor.
  • Ambient: -25 to 50 °C operating range suits the board location.
  • Power reserve: matches how often supply interruptions are expected.

Installation and commissioning of the 15335

Snap this unit onto the DIN rail in the final-distribution board, wire the supply and load circuits with the terminal type listed above, and set the clock and the on-off segments against a known time reference. Terminals are rated IP20 B, so the unit belongs inside a closed enclosure.

After setting, run the circuit through a full on-off cycle before leaving site. Re-check the clock after the first supply interruption, and plan a battery check at the interval stated on the datasheet if the version has a battery.

Where the 15335 fits in Oman and the GCC

Typical uses are exterior and landscape lighting, car-park and corridor lighting, shop-window and signage circuits, and scheduled operation of small fans or pumps. In hot, dusty switchrooms the limit is the board temperature: compare the operating range on the datasheet with the actual temperature inside the enclosure, not the room, and ventilate or shade the board where needed.

Documents and quotation

The official Schneider Electric datasheet of this unit is attached on this page for download, so every figure above can be checked against the source.

To request a quotation, send us the part number 15335, the quantity and the delivery location through the RFQ form. Seven Star LLC replies with availability and lead time.

Datasheets & Documents
  • PDF Datasheet Schneider Electric 15335 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric 15335 Acti9 IH 24 h Mechanical

Answers from our engineering team on installation, compatibility and integration.

01What is the 15335?
It is a single-channel mechanical time switch from the Schneider Electric Acti9 IH family with a 24 h cycle, set manually, for DIN-rail mounting. It is 18 mm wide (2 modules of 9 mm).
02What supply does the 15335 need?
The datasheet gives 230 V AC at 50 Hz. The power consumption of the device itself is 0.5 W.
03How many switchings does the 15335 allow?
The datasheet states a maximum of 48 on - 48 off per cycle, with a minimum interval of 15 min between switchings.
04What contact rating does the 15335 have?
The maximum switching current is 16 A - 250 V AC pf = 1; 4 A - 250 V AC pf = 0.6. Load-type limits for lamps are listed in the datasheet and on this page.
05Does the 15335 keep time during a power cut?
The datasheet lists no battery life and no backup time for this version, which matches its designation as the variant without memory: if the supply is lost, the clock cannot be expected to keep time through the outage.