Brand: Yokogawa
Yokogawa EJA120E-DES4G-812DJ Draft Range DP, BRAIN
Description
A BRAIN draft transmitter with connectors: EJA120E-DES4G-812DJ
Where the base EJA120E uses bare 1/4 NPT ports, Yokogawa EJA120E-DES4G-812DJ comes with 1/2 NPT female process connectors fitted to the cover flanges, so impulse tubing or pipe of half-inch size can be attached directly. Stainless 316L bolts and nuts replace carbon steel, the installation is horizontal with the high-pressure side on the right (-8), the output is BRAIN, and a digital indicator and a 316 SST flat bracket complete the unit.
Positions in the code EJA120E-DES4G-812DJ
| Code position | Meaning |
|---|---|
| -D | 4 to 20 mA DC with BRAIN digital communication |
| E | Capsule: 0.1 to 1 kPa span (0.4 to 4 inH2O) |
| S | Wetted parts: ASTM CF-8M cover flange and connector, Hastelloy C-276 diaphragm, PTFE gasket, 316 SST vent/drain plug |
| 4 | Process connection: 1/2 NPT female process connector |
| G | Bolts and nuts: 316L SST |
| -8 | Installation: horizontal piping, right side high pressure |
| 1 | Amplifier housing: cast aluminum alloy |
| 2 | Electrical: 1/2 NPT female, two electrical connections, no blind plugs |
| D | Integral indicator: digital indicator |
| J | Mounting bracket: 316 SST 2-inch pipe bracket, flat type (horizontal piping) |
Comparison with the base 120E
Relative to a plain EJA120E, this code changes five items: protocol (D for BRAIN), process connectors (4 for 1/2 NPT female connectors), bolts (G, 316L SST), orientation (-8) and indicator and bracket (D and J). The measuring capsule E remains the same: span 0.1 to 1 kPa, accuracy plus or minus 0.2 percent of span, response 150 ms, stability plus or minus 0.3 percent of URL per year. Where a plant mounts the transmitter in a humid or coastal location, the 316L bolting avoids the weeping rust that carbon steel B7 bolts develop.
EJA120E-DES4G-812DJ figures
| Item | Value |
|---|---|
| Output | 4 to 20 mA with BRAIN |
| Capsule | E, 0.1 to 1 kPa span |
| Connectors | 1/2 NPT female |
| Bolts | 316L SST |
| Orientation | Horizontal piping, high pressure on the right |
| Indicator | D, digital |
| Bracket | J, 316 SST flat type |
| Ambient limit | Minus 25 to 80 degrees C |
| Working pressure | Minus 50 to 50 kPa |
| Weight | 3.7 kg before indicator and bracket |
Low-pressure installations that use it
Large ducts and stacks, scrubber differential pressure, ventilated enclosure purge verification and filter monitoring at water treatment plants. The half-inch connectors make it simple to land existing 1/2 inch lines. The LCD helps maintenance staff see a reading without a terminal.
Practical notes on EJA120E-DES4G-812DJ
BRAIN is read through a BRAIN terminal at up to 2 km on CEV cable with a 250 to 600 ohm load. The LCD limits the ambient lower limit and the transmitter should be shaded from direct sun. As with all low-range capsules, trim zero at the final mounting position because tilting shifts it.
Blow clear and flush impulse lines to keep dust out of the connectors, then recheck zero.
Electrical data, safety and options for EJA120E-DES4G-812DJ
BRAIN output rides on a two-wire 4 to 20 mA loop. Supply is 10.5 to 42 V DC for general use and flameproof types, and at least 16.6 V DC is needed for digital communication; the loop can carry 0 to 1290 ohm in operation. Communication distance is up to 2 km with CEV polyethylene-insulated PVC-sheathed cable, load capacitance 0.22 microfarad or less and load inductance 3.3 mH or less. The output range is 3.6 to 21.6 mA with an up-scale failure alarm of 110 percent as standard. In its standard configuration the EJA-E series is certified SIL 2 capable for single use and SIL 3 for dual use under IEC 61508. Environmental protection is IP66/IP67 and Type 4X. Compliance includes EN 61326-1 Class A for EMC and the PED 2014/68/EU under sound engineering practice.
Because the E capsule sits at the very bottom of the pressure scale, the ambient temperature effect of plus or minus (0.15 percent span plus 0.2 percent URL) per 28 degrees C is relatively important. Shade the unit and keep impulse lines at the same temperature to avoid false draft readings caused by thermal gradients.
Ordering notes for EJA120E-DES4G-812DJ
Part numbers within the EJA120E family differ by a single digit or letter. A -7 or -9 instead of -8 reverses which side is high pressure; a 5 instead of 4 removes the connectors and exposes 1/4 NPT cover flange threads; a J instead of G switches to B7 bolting. For a spare, match the nameplate exactly, especially the orientation digit. EJA120E-DES4G-812DJ is quoted in its base form with no slash options unless you request them.
Quick answers about EJA120E-DES4G-812DJ
- What changes in EJA120E-DES4G-812DJ compared with the base unit? It has 1/2 NPT female process connectors, 316L bolts, a different orientation, BRAIN output, an LCD and a 316 SST bracket.
- What orientation does -8 mean? Horizontal piping with the right side of the transmitter as the high-pressure side.
- Which output code is D? A 4 to 20 mA DC output with BRAIN digital communication; HART would be J.
- Does it measure positive and negative pressure? Yes, the range is minus 1 to 1 kPa within the 0.1 to 1 kPa span limit.
- How heavy is it? About 3.7 kg without indicator and bracket, according to the datasheet physical specifications.
Documents and quotation
Tell us if your impulse lines are 1/2 inch NPT or another size.
The datasheet for this model, Yokogawa GS 01C31B03-01EN, is attached as a PDF to the listing. In the RFQ please give the full part number EJA120E-DES4G-812DJ, quantity, tag numbers and the draft or low differential pressure you need to measure. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Stock status and lead time are confirmed per request.
Typical Questions From Maintenance Teams
Maintenance engineers replacing a Yokogawa EJA120E-DES4G-812DJ usually ask whether the new unit is a direct fit, whether settings can be copied from the old one, and whether any accessories must be ordered separately. The answer depends on the exact order code and the generation of the installed pressure transmitters, so the nameplate details are the best starting point. Send them with your request and we will check the match, point out any differences in connections or options, and list the parts needed so that the job can be finished in one visit.
Other Models in the EJA120E Range
Seven Star LLC supplies models from the EJA120E range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Yokogawa EJA120E-JES5J-912NB Draft Range DP Transmitter | Pressure Transmitters | View details |
| Yokogawa EJA120E-DES4G-812DJ Draft Range DP, BRAIN | Pressure Transmitters | You are viewing this model |
| Yokogawa EJA120E-JES1C-U22EK Draft Range DP, Universal Flange | Pressure Transmitters | View details |
Datasheets & Documents
- Datasheet Yokogawa EJA120E-DES4G-812DJ Draft Range DP, BRAIN Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa EJA120E-DES4G-812DJ Draft Range DP, BRAIN
Answers from our engineering team on installation, compatibility and integration.
01What changes in EJA120E-DES4G-812DJ compared with the base unit?
It has 1/2 NPT female process connectors, 316L bolts, a different orientation, BRAIN output, an LCD and a 316 SST bracket.
02What orientation does -8 mean?
Horizontal piping with the right side of the transmitter as the high-pressure side.
03Which output code is D?
A 4 to 20 mA DC output with BRAIN digital communication; HART would be J.
04Does it measure positive and negative pressure?
Yes, the range is minus 1 to 1 kPa within the 0.1 to 1 kPa span limit.
05How heavy is it?
About 3.7 kg without indicator and bracket, according to the datasheet physical specifications.