Yokogawa EJX530A-DAS4N-012NN Gauge Pressure Transmitter
Description
How EJX530A-DAS4N-012NN is defined
The EJX530A datasheet prints one example of a complete code, and it is EJX530A-DAS4N-012NN. It describes a DPharp in-line gauge pressure transmitter with BRAIN communication, an A capsule spanning 8 to 200 kPa, a 316L stainless connector with Hastelloy C-276 diaphragm, a 1/2 NPT female thread, a cast aluminum housing, two 1/2 NPT conduit entries, no indicator and no bracket. For anyone searching old purchase orders or maintenance files, this is the typical EJX530A.
The suffix of EJX530A-DAS4N-012NN in plain words
| Code position | Meaning |
|---|---|
| -D | 4 to 20 mA DC with BRAIN digital communication |
| A | Capsule: span 8 to 200 kPa |
| S | 316L SST process connector, Hastelloy C-276 diaphragm, 316L SST or F316L SST other wetted parts |
| 4 | Process connection: 1/2 NPT female |
| 1 | Amplifier housing: cast aluminum alloy |
| 2 | Electrical: 1/2 NPT female, two electrical connections, no blind plugs |
| N | Integral indicator: none |
| N | Mounting bracket: none |
Performance of the A capsule
For the EJX530A, reference accuracy is plus or minus 0.04 percent of span for spans of 20 kPa and above, with the datasheet formula of 0.004 times URL over span below that. Stability is plus or minus 0.1 percent of URL over fifteen years, response time is 90 ms with a 45 ms update period, and the range reaches from minus 100 kPa to 200 kPa gauge. Over-pressure is 4 MPa and burst pressure is 30 MPa. The ambient temperature effect is plus or minus (0.15 percent of span plus 0.15 percent of URL) per 28 degrees C.
Electrical and communication data of EJX530A-DAS4N-012NN
Supply voltage is 10.5 to 42 V DC for general use, with 10.5 to 30 V DC for intrinsically safe or type n versions, and at least 16.6 V DC is needed at the terminals for BRAIN communication. The loop can carry 0 to 1290 ohm in operation and 250 to 600 ohm for digital communication, and with a 24 V DC supply up to 550 ohm of load is permitted. BRAIN signals reach up to 2 km on CEV polyethylene-insulated PVC-sheathed cable. Output range is 3.6 to 21.6 mA, with a failure alarm that can be set up-scale at 110 percent or down-scale at minus 5 percent; options C2 and C3 preset NAMUR NE43 limits. Load capacitance of 0.22 microfarad or less and load inductance of 3.3 mH or less apply to the communication cable.
Table: facts for EJX530A-DAS4N-012NN
| Item | Value |
|---|---|
| Capsule | A, 8 to 200 kPa gauge |
| Range | Minus 100 to 200 kPa |
| Output | 4 to 20 mA with BRAIN |
| Wetted | 316L SST, Hastelloy C-276 diaphragm |
| Connection | 1/2 NPT female |
| Housing | Cast aluminum, IP66/IP67, Type 4X |
| Weight | 1.2 kg without indicator or bracket |
| Supply | 10.5 to 42 V DC |
| Load | 0 to 1290 ohm in operation |
| Update period | 45 ms |
| Fill fluid | Silicone oil |
Where an A-capsule gauge unit works
Boiler draught and furnace pressure, combustion-air blowers, low-pressure steam, storage tank pressure, biogas lines, and building ventilation for plant control rooms. The BRAIN output is useful for plants where Yokogawa BRAIN terminals remain the standard configuration tool. The 8 kPa minimum span gives finer resolution than the 10 kPa of the EJA-E version.
EJX530A compared with EJA530E
The EJX version has a reference accuracy of 0.04 percent against 0.055 percent, a minimum span of 8 kPa against 10 kPa, a stability period of fifteen years against ten, and for the D capsule an over-pressure rating of 75 MPa against 60 MPa. The EJX series also offers the optional multi-sensing diagnostics and status output. If those figures are not needed, the EJA530E is a simpler selection; but when the loop was documented around an EJX530A, matching the model avoids requalification.
Fitting EJX530A-DAS4N-012NN
With no bracket included, mount the transmitter directly on a rigid pipe or stand. Seal the 1/2 NPT female thread with tape or paste suited to the fluid, close the unused conduit entry with a rated plug and trim zero with the external screw. Because the capsule is sensitive at 8 kPa, mounting angle matters: allow for the zero shift when tilted and trim after final mounting.
Do not apply compressed air to the port for cleaning; a pulse above 4 MPa would exceed the over-pressure rating of this capsule. Keep covers tight and O-rings in good condition. Record zero at shutdowns.
Changing one letter changes the product: B or C capsule for higher spans, 7 for male thread, J for HART, D or E in the indicator position for an LCD, L for a bracket. Slash options such as /AL status output or /DG6 diagnostics are separate quotations. The absolute-pressure twin is the EJX510A.
Quick answers about EJX530A-DAS4N-012NN
- Why is this the typical EJX530A code? The datasheet cites EJX530A-DAS4N-012NN as the example model code, and the arrow-marked typical choices are used in each position.
- Does EJX530A-DAS4N-012NN support HART? No. D selects 4 to 20 mA with BRAIN digital communication. HART is code E or J.
- What span does the A capsule give? 8 to 200 kPa, with a range from minus 100 to 200 kPa gauge.
- Is this a gauge or absolute transmitter? It is a gauge pressure transmitter. The EJX510A is the absolute-pressure version of the same series.
- What is the stability specification? Plus or minus 0.1 percent of the upper range limit over 15 years for the EJX530A, per the datasheet.
Documents and quotation
The base code is quoted without options.
The Yokogawa general specification GS 01C25F01-01EN, which covers the EJX510A and EJX530A, is supplied as the datasheet PDF with this listing. To request a quotation, send the part number EJX530A-DAS4N-012NN, the quantity, tag numbers, process fluid and the approval you need if the area is classified. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Availability and lead time are confirmed per RFQ.
Other Models in the EJX530A Range
Seven Star LLC supplies models from the EJX530A range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Yokogawa EJX530A-DAS4N-012NN Gauge Pressure Transmitter | Pressure Transmitters | You are viewing this model |
| Yokogawa EJX530A-JBS8N-012DL Gauge Pressure, G1/2 Male | Pressure Transmitters | View details |
| Yokogawa EJX530A-JCH4N-032EL Hastelloy Gauge Pressure | Pressure Transmitters | View details |
Datasheets & Documents
- Datasheet Yokogawa EJX530A-DAS4N-012NN Gauge Pressure Transmitter Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa EJX530A-DAS4N-012NN Gauge Pressure
Answers from our engineering team on installation, compatibility and integration.
01Why is this the typical EJX530A code?
The datasheet cites EJX530A-DAS4N-012NN as the example model code, and the arrow-marked typical choices are used in each position.
02Does EJX530A-DAS4N-012NN support HART?
No. D selects 4 to 20 mA with BRAIN digital communication. HART is code E or J.
03What span does the A capsule give?
8 to 200 kPa, with a range from minus 100 to 200 kPa gauge.
04Is this a gauge or absolute transmitter?
It is a gauge pressure transmitter. The EJX510A is the absolute-pressure version of the same series.
05What is the stability specification?
Plus or minus 0.1 percent of the upper range limit over 15 years for the EJX530A, per the datasheet.


















Reviews
There are no reviews yet.