Xtralis VLC-505 Aspirating Smoke Detector

Description

Overview

The Xtralis VLC-505 is a VESDA LaserCOMPACT aspirating smoke detector purpose-built for very early warning smoke detection in single and smaller protected environments where space is at a premium. Combining VESDA laser detection technology with a modified aspirator design in a compact enclosure, the Xtralis VLC-505 provides absolute smoke detection across coverage of up to 800 m² (8,000 sq ft), with a wide sensitivity range of 0.005 to 20% obscuration per meter that lets a single detector protect archives, production machinery enclosures, ceiling voids, prison cells, wet benches, and critical process tool cabinets.

With fast quotation turnaround and technical support, Seven Star LLC proudly supplies the Xtralis VLC-505 aspirating smoke detector to fire protection contractors, data centers, and industrial facilities across the Sultanate of Oman, Muscat, and the wider GCC region.

Operating Principle of the Xtralis VLC-505

The Xtralis VLC-505 draws air continuously through a single pipe inlet network using an integral aspirator, pulling samples from the protected space into a laser-based detection chamber. Inside the chamber, VESDA laser detection technology analyzes the sampled air for combustion particles at concentrations far below the threshold visible to conventional point smoke detectors, allowing the Xtralis VLC-505 to identify a developing fire condition at the earliest possible incipient stage — often before visible smoke or measurable heat is present at the protected area.

Clean air barrier optics protection keeps the detection chamber free of contamination during continuous sampling, sustaining measurement accuracy over long service intervals in dusty or industrial environments. The Xtralis VLC-505 continuously monitors air flow through the sampling pipe network and uses its AutoLearn capability to establish a baseline for normal environmental conditions, reducing nuisance alarms while maintaining the sensitivity needed to detect a genuine incipient fire condition across three configurable alarm levels.

Engineering Design of the Xtralis VLC-505

Xtralis designed the VLC-505 around a simplified display and a compact enclosure suited to installation in confined ceiling voids, equipment cabinets, and utility spaces where a full-size aspirating detector will not fit. Five status LEDs give technicians an at-a-glance view of detector condition, alarm state, and fault status without connecting a separate monitoring terminal, while the single pipe inlet design simplifies pipe network layout for smaller protected zones compared to multi-pipe aspirating systems intended for large open areas.

The VLC-505 variant communicates over VESDAnet, Xtralis’ proprietary detector networking protocol, allowing multiple VESDA detectors — including VLC, VLP, and VESDA-E units — to be integrated into a single site-wide very early warning fire detection network with centralized monitoring and configuration. The detector provides three programmable relays for direct interface with fire alarm control panels, along with optional remote display and relay capability for installations where the detector itself is not readily visible or accessible to facility personnel.

Key Features

The Xtralis VLC-505 aspirating smoke detector combines laser-based early warning detection with a compact, space-efficient design. Core capabilities include:

  • Absolute smoke detection coverage of up to 800 m² (8,000 sq ft) per detector.
  • Wide sensitivity range of 0.005 to 20% obscuration/m for both very early warning and standard alarm thresholds.
  • VESDAnet communication for integration into a networked, site-wide detection system.
  • Single pipe inlet design simplifying pipe network layout in space-constrained protected areas.
  • Five status LEDs providing immediate local visibility of detector and alarm condition.
  • Clean air barrier optics protection that sustains detection accuracy in continuous operation.
  • Three programmable relays and three alarm levels for direct fire alarm panel interface.
  • AutoLearn capability and continuous air flow monitoring to reduce nuisance alarms.

Industrial Applications

Facilities across the region deploy the Xtralis VLC-505 wherever early warning fire detection is required in a compact, cost-effective footprint. Data centers and telecommunications rooms throughout Muscat use the Xtralis VLC-505 to protect server cabinets and cable risers, while correctional facilities specify it for cell and corridor protection where tamper resistance and low-profile installation matter. Industrial plants across Oman deploy the VLC-505 to protect production machinery enclosures, wet benches, and critical process tool cabinets in semiconductor and precision manufacturing environments, and archives, museums, and heritage sites in Sohar and Salalah rely on its very early warning sensitivity to protect irreplaceable assets without the false-alarm risk of conventional point detectors.

With engineering support in Muscat, Seven Star LLC distributes the Xtralis VLC-505 to fire protection engineering firms, systems integrators, and facility management teams operating within the Sohar and Salalah economic zones, as well as to industrial clients throughout Muscat and the broader Sultanate of Oman.Seven Star LLC supplies this item on request with the manufacturer documentation, and availability and lead time are confirmed at quotation.

Technical Specifications

Key technical parameters for the Xtralis VLC-505 aspirating smoke detector:

Parameter Specification
Model Xtralis VLC-505
Detection Technology VESDA laser-based aspirating smoke detection
Coverage Area Up to 800 m² (8,000 sq ft) per detector
Sensitivity Range 0.005 – 20% obscuration/m (0.0015 – 6% obscuration/ft)
Pipe Configuration Single pipe inlet
Communication VESDAnet (VN)
Alarm Levels 3 configurable alarm levels
Relays 3 programmable relays
Status Indication 5 status LEDs, optional remote display
Special Functions AutoLearn, air flow monitoring, clean air barrier optics
Certifications UL, ULC, FM, LPCB, VdS, CE, EN 54-20, FM Class I Division 2
Typical Applications Data centers, correctional facilities, archives, industrial cabinets

Request a Quote for Xtralis VLC-505 Aspirating Smoke Detector

To submit a formal Request for Quote (RFQ), confirm current availability and lead time, or download the complete technical datasheet for the Xtralis VLC-505 aspirating smoke detector, contact the fire and gas detection division at Seven Star LLC today.

Related Products

Datasheets & Documents
  • PDF Brochure Xtralis VLC-505 Aspirating Smoke Detector Catalog Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

VESDA is the name most fire engineers use for aspirating smoke detection, and Xtralis is the company behind it. An aspirating detector draws air through a pipe network to a detection chamber and can report smoke at a very early stage. Seven Star LLC supplies Xtralis VESDA detectors and spare parts to facility and fire system teams in Oman, including filter cartridges, detection chambers, power supplies and remote displays.

Xtralis VESDA detectors and spares listed here

Two generations appear in the listing. From the earlier VESDA range come the VLC-505, a compact detector for single areas with VESDAnet communication, and the VESDA VLI, built for dusty industrial environments. The current generation is VESDA-E, represented by the VEP detector.

Spare parts follow VSP numbers:

  • VSP-962 filter cartridge for VESDA-E detectors
  • VSP-972 filter cartridge for the VESDA-E VEA
  • VSP-964-03 smoke detection chamber (MK3) for VESDA-E

System accessories listed include the VPS-215-E power supply and the VRT-J00 remote display and relay unit.

Where VESDA aspirating detection is used

Aspirating detection is chosen where point detectors respond too late or cannot be reached for testing: data halls and telecom rooms, switchgear and control rooms, clean rooms, cold stores, warehouses with high racking, cable tunnels and heritage buildings. The VLI extends this to dirty areas such as conveyors and process buildings. Such sites are common in the GCC, where data centers and utility substations are expanding.

Ordering VESDA parts: what we need

Send the detector model and part number from the detector label, for example VLC-505 or the VEP variant code, with the serial number. VESDA-E detectors are made in several variants by pipe count and display type, so the complete code is needed. For filters and chambers, give the VSP number and the detector it serves. For a new detector, the pipe network design has to exist first: tell us the model selected by your designer and the fire panel interface required. We check each number against Xtralis documentation.

Frequently Asked Questions

What coverage area and sensitivity does the Xtralis VLC-505 provide?
The Xtralis VLC-505 delivers absolute smoke detection coverage of up to 800 m² (8,000 sq ft) per detector, with a wide sensitivity range of 0.005 to 20% obscuration/m suitable for both very early warning and conventional alarm thresholds.
How does the Xtralis VLC-505 reduce installation cost in small protected spaces?
The Xtralis VLC-505 uses a single pipe inlet design and a compact enclosure, simplifying pipe network layout and reducing installation time compared to multi-pipe aspirating systems designed for large open areas.
What environments is the Xtralis VLC-505 compatible with?
The Xtralis VLC-505 is designed for single and smaller environments such as archives, production machinery enclosures, ceiling voids, prison cells, wet benches, and critical process tool cabinets where space is limited.
Can the Xtralis VLC-505 integrate with existing VESDA and fire alarm systems?
Yes. The Xtralis VLC-505 communicates over VESDAnet, allowing it to join a networked site-wide VESDA detection system, and its three programmable relays interface directly with all major fire alarm control panels.
Is Seven Star LLC an experienced supply partner for Xtralis products?
Yes, Seven Star LLC is an experienced supply partner for Xtralis. Seven Star LLC supplies Xtralis products to customers in Oman and the GCC and can provide the manufacturer documentation and technical support on request.