Brand:

MTL MTL7728+ Zener Safety Barrier, 28 V 300 ohm 93 mA

Description

MTL7728+ overview

The MTL7728+ is a single-channel shunt-diode (zener) safety barrier from the MTL7700 range. It limits the voltage and current that can reach a hazardous area from a safe-area circuit, using two stages of pulse-tested zener diodes, a fuse and an infallible terminating resistor. The safety description is 28 V, 300 ohm and 93 mA, and the positive-polarity version is the barrier the manufacturer recommends for most analogue controller outputs, such as I/P converter signals, as well as digital outputs to solenoids, alarms and LEDs.

The MTL7728+ is a basic, passive barrier: it contains no active output-current limiting circuitry, so its behaviour is simple and predictable. In normal operation the diodes do not conduct. If a fault in the safe area raises the voltage above the diode breakdown level, the diodes clamp the voltage, the resistor limits the current, and the fuse removes the fault. A reliable intrinsic safety earth is therefore essential, and the unit achieves this through its connection to the DIN rail. The MTL7728+ is certified ia for all zones and IIC for all explosive atmospheres.

Key features of the MTL MTL7728+

  • Single channel, positive polarity, 28 V, 300 ohm, 93 mA safety description
  • Maximum end-to-end resistance 333 ohm and a voltage drop of 6.66 V at 20 mA, suitable for 4-20 mA controller outputs
  • Working voltage 25.9 V at 10 microamperes leakage, with 26.5 V maximum voltage and a 50 mA fuse
  • Certified ia, IIC for all zones, with IECEx/ATEX and North American approvals listed by the manufacturer
  • Compact 12.6 mm wide polycarbonate housing that clips onto 35 mm top-hat DIN rail
  • Removable black PBT terminals for conductors up to 2.5 square mm, with blue labels marking hazardous-area terminals
  • Red label colour code identifies positive polarity
  • Operating range from -20 to +60 degrees C continuous, IP20 case

MTL7728+ technical specifications

Data below come from the manufacturer’s MTL7700 range datasheet and catalogue page for the MTL7728+.

Parameter Value
Model MTL7728+ shunt-diode (zener) safety barrier, single channel
Safety description 28 V, 300 ohm, 93 mA
Polarity Positive (+); red label
Typical application Controller outputs, solenoids; analogue and digital
Maximum end-to-end resistance 333 ohm
Working voltage (10 microamperes) 25.9 V
Maximum voltage Vmax 26.5 V
Fuse rating 50 mA
Protection ia, IIC for all zones
Hazardous-area ratings listed Zone 0 and Zone 2; NEC Class I, Division 2 and Zone 2; IECEx/ATEX
Ambient temperature -20 to +60 degrees C continuous; storage -40 to +80 degrees C
Humidity 5 to 90 percent RH, non-condensing
Ingress protection IP20
Terminals Removable black PBT, up to 2.5 square mm (13 AWG); torque 0.4 to 0.6 Nm
Housing material Polycarbonate
Dimensions (catalogue) 105 x 90 x 12.6 mm
Weight Approximately 140 g
Mounting 35 mm top-hat DIN rail with integral earthing

Terminal 3 and 4 are the hazardous-area side and 1 and 2 the safe-area side in the manufacturer’s wiring diagrams. The datasheet states that safety and entity parameters are given in the individual agency certificates, which should be consulted for each model; the cable parameter tables in the range literature give the permitted capacitance and inductance for each gas group.

Typical applications in oil and gas, utilities, water and manufacturing

The MTL7728+ is widely used where a control-room output must drive an intrinsically safe device in a hazardous area. In Omani oil and gas plants, that typically means 4-20 mA signals from a DCS or PLC analogue output card to an I/P converter or valve positioner on a wellhead, separator or tank-farm valve, and 24 V digital outputs to intrinsically safe solenoid valves and beacons. Its 6.66 V drop at 20 mA must be considered together with the available compliance voltage of the output card.

Utilities and water treatment plants use the same barrier for solenoid-operated dosing and sampling valves in biogas, chlorine and fuel areas, while manufacturers in the GCC use it on classified process lines for lamps, buzzers and small actuators. The shunt-diode design is economical, uses no power supply of its own and has very low heat dissipation, which makes it attractive for large multi-channel marshalling cabinets.

Selection and compatibility notes for MTL7728+

Check that the load voltage requirement of the field device is compatible with the barrier. With a 6.66 V drop at 20 mA and 333 ohm end-to-end resistance, an I/P converter, solenoid or alarm needs to operate within the remaining compliance voltage of the controller. If more drive is needed, the range includes higher-power versions in the same family such as the MTL7728P+ and, for IIB gases, the MTL7729P+; the MTL7787+ offers two channels where the return path must be handled as well.

The MTL7728+ must be connected to a clean intrinsic safety earth with a resistance low enough for the installation. Verify the safe-area equipment supply cannot exceed the Vmax of 26.5 V, because the barrier does not provide galvanic isolation. If the connected controller cannot tolerate a shunt-diode barrier, an isolating interface from the MTL4000 or MTL5000 range may be preferable.

Installation and commissioning

Before mounting the MTL7728+, confirm the hazardous-area apparatus and the cable parameters against the entity values on the nameplate and in the manufacturer certificate, and decide where the intrinsic safety earth will be taken. Mount the unit on the 35 mm top-hat DIN rail in a clean enclosure or cabinet in the safe area, keeping hazardous-area and safe-area wiring physically separated and clearly labelled. Insert the unit onto the rail with its earthing foot engaged, and make sure the rail has a low-resistance link to the plant intrinsic safety earth. Use the terminal torque range of 0.4 to 0.6 Nm quoted by the manufacturer and keep the blue-labelled hazardous-area terminals separate from safe-area wiring.

Wire the MTL7728+ strictly to the terminal table in the datasheet, tighten the terminal screws to the specified torque and check that no strands are left outside the clamp. Where the unit carries a certificate, the earth connection and the rail must meet the requirements stated there. After wiring, apply the supply, check the power indication, and simulate the field signal to prove the end-to-end loop before the plant is declared ready. Record the as-found readings for future loop checks of the MTL7728+.

Maintenance and service life

The MTL7728+ has no user-serviceable parts, so maintenance is mainly periodic inspection. During planned shutdowns, inspect terminals for corrosion and looseness, verify the supply voltage at the unit, and repeat the loop check recorded at commissioning. In coastal or humid locations around Muscat, Sohar and Duqm, a sealed or purged cabinet with a clean, dry interior greatly extends the life of any electronic interface such as the MTL7728+.

If a loop drifts outside its tolerance or the unit shows no power indication with a healthy supply, replace the module rather than attempting repair, and keep the replacement documentation with the loop folder. Because certified intrinsically safe equipment must not be modified, any change in cabling, load or hazardous-area device should be re-assessed against the MTL7728+ entity parameters before it is put into service.

For shunt-diode barriers, periodic checks should include the earth connection resistance, because a degraded earth removes the protection that the MTL7728+ provides. If the fuse has operated after a safe-area overvoltage, the module must be replaced and the cause of the overvoltage investigated.

Related products and ordering notes

Customers who enquire about the MTL7728+ often also need matching accessories and neighbouring models from the same family, such as the MTL7728P+, MTL7729P+, MTL7787+ and MTL7706+ barriers, the MTL7799 dummy barrier and the MTL7798 power feed module of the MTL7700 range. Please confirm polarity and safety description when matching an installed barrier.

When you send an enquiry for the MTL7728+, please quote the full part number exactly as printed on the nameplate, the quantity, and the intended application. If you are replacing an installed unit, a photograph of the nameplate helps us confirm the MTL7728+ you need. Our team can arrange a quotation with delivery to Oman and across the GCC.

Frequently asked questions about MTL7728+

The MTL7728+ is a passive single-channel positive zener barrier with a 28 V, 300 ohm, 93 mA safety description, a 50 mA fuse and 333 ohm end-to-end resistance. It suits controller outputs and solenoids, needs a good intrinsic safety earth, and is mounted on 35 mm DIN rail.

Documents and quotation

A copy of the MTL7700 range datasheet that covers the barrier for the MTL7728+ is available on this page for your engineering review. To request a quotation, send the RFQ with the part number MTL7728+, the quantity, the delivery location and any certification or documentation requirements, and we will respond with availability and lead time. Please review the specification against your loop or system requirements before ordering.

Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with MTL. Product names and part numbers are used only to identify the item you ask for.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.

Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.

MTL (Eaton) company profile

Founded 1971, Luton, England, as Measurement Technology Ltd
Origin Spin-off from Kent Instrumentation
Headquarters Luton, England
Ownership Eaton (Crouse-Hinds), via Cooper Industries from 2008
Product families MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points

Milestones

  • 1971: Measurement Technology Ltd is founded in Luton.
  • 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
  • 2008: Cooper Industries acquires MTL Instruments for £144 million.
  • 2012: Eaton acquires Cooper Industries.

MTL product families listed here

Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.

Where MTL barriers and isolators are used

These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.

MTL (Eaton) products we list

Family Examples
Isolator & Barrier Eaton MTL5541 Repeater Power Supply, MTL 5043, MTL 9370-FB2 Intrinsically Safe Fieldbus…, MTL CPM08-BN, MTL5576-THC Temperature Isolator Module
Automation Accessories MTL 9608 Process Junction Box
Automation Software MTL PCS45 Configuration Software and PCL…

Ordering MTL modules: what we need

Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.

Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.

FAQ

Questions about the MTL MTL7728+ Zener Safety Barrier, 28 V 300 ohm 93

Answers from our engineering team on installation, compatibility and integration.

01What is the MTL7728+ used for?
It is a single-channel positive-polarity zener barrier used for analogue controller outputs, solenoids, alarms and other digital outputs into a hazardous area.
02What is the safety description of the MTL7728+?
The datasheet lists 28 V, 300 ohm and 93 mA, with ia certification for IIC gases in all zones.
03Does the MTL7728+ need an earth connection?
Yes. As a shunt-diode barrier it relies on a high-integrity intrinsic safety earth, which is provided through the DIN rail connection.
04What is the voltage drop of the MTL7728+?
The range literature gives 6.66 V at 20 mA, with a maximum end-to-end resistance of 333 ohm.
05How do I request a quotation for the MTL7728+?
Send an RFQ with the part number MTL7728+, quantity and delivery location in Oman or the GCC, and we will reply with availability and lead time.