Phoenix Contact MACX MCR-SL-CAC-5-I AC Current Transducer

Description

MACX MCR-SL-CAC-5-I: AC current transducer with 4-20 mA output

The MACX MCR-SL-CAC-5-I measures alternating current up to 1 A or 5 A and converts it to a 0 to 20 mA or 4 to 20 mA signal for a PLC, recorder or DCS analogue input. The output range is chosen with a DIP switch, and an LED shows the operating state. It is a compact signal conditioner of the MACX MCR series for DIN rail mounting. Seven Star LLC supplies the MACX MCR-SL-CAC-5-I in Oman and the GCC as an independent supplier in Muscat.

In the name, MACX MCR is the signal conditioner series, SL marks the slim housing, CAC the AC current measurement, 5 the 5 A range and I the current output. The order number is 2810612.

Technical specifications of the MACX MCR-SL-CAC-5-I

Parameter Specification
Manufacturer / part number Phoenix Contact MACX MCR-SL-CAC-5-I (order no. 2810612)
Function Current measuring transducer for AC
Input current range 0 to 1 A AC or 0 to 5 A AC, configurable
Input impedance Below 50 mΩ
Output 0 to 20 mA or 4 to 20 mA, DIP-switch selectable
Supply voltage 24 V DC, -20 % to +25 % (19.2 to 30 V DC)
Current consumption Below 32 mA at 24 V DC and 20 mA output
Maximum transmission error Max. 0.5 % of the nominal range
Temperature coefficient Typ. below 0.015 %/K; max. below 0.02 %/K
Rated insulation voltage 300 V AC to earth
Power dissipation 1.2 W at nominal condition
Mounting DIN rail

How the MACX MCR-SL-CAC-5-I converts current to a signal

The transducer measures the AC current flowing in the monitored circuit through a low-impedance input of below 50 mΩ, which means the burden on the current transformer or circuit is very small. Inside, the AC value is converted to a proportional DC value and then to an analogue current output. Galvanic separation between input, output and supply prevents ground loops and protects the control system from surges on the measured circuit.

Output span and input range are set by DIP switches, so one device can cover both 1 A and 5 A secondary current transformer outputs and the common 0 to 20 or 4 to 20 mA standards. The live-zero 4 to 20 mA output lets the control system detect a wire break, which is not possible with 0 to 20 mA.

Where the MACX MCR-SL-CAC-5-I fits in a monitoring system

Typical use is behind a standard 1 A or 5 A current transformer in a motor or feeder circuit. The signal can then be shown on a panel meter or evaluated by a PLC for load monitoring, overload alarms or energy management. Related MACX MCR devices such as the MACX MCR-T-UIREL-UP temperature transducer cover other measured quantities with the same slim housing.

Because accuracy is 0.5 % of the nominal range, it is intended for monitoring and control, not for revenue metering.

Selection and ordering checklist for the MACX MCR-SL-CAC-5-I

  • Secondary current of the current transformer: 1 A or 5 A.
  • Output signal needed: 0 to 20 mA or 4 to 20 mA.
  • 24 V DC supply with 19.2 to 30 V DC window.
  • Accuracy needed: 0.5 % of nominal range.
  • Load circuit frequency and waveform (AC measurement).
  • Insulation requirement: 300 V AC to earth.

Installation, commissioning and maintenance of the MACX MCR-SL-CAC-5-I

Snap the module onto the rail, connect the current transformer secondary to the input terminals, never leaving a current transformer open-circuit, and connect the 24 V supply and the analogue output. Set the DIP switches before powering up and check the status LED.

Calibrate by injecting a known current and reading the output at the PLC. Include the device in the instrument loop checks; no regular adjustment is normally required.

Typical applications in Oman and the GCC

In Oman and the GCC, the MACX MCR-SL-CAC-5-I is used for motor load monitoring on pumps and fans, heater current supervision and feeder monitoring in substations and plants. Hot conditions are covered by the low temperature coefficient of the device.

The 4 to 20 mA output is compatible with almost every PLC and DCS, which simplifies spares and standardisation.

For loop checks, inject 1 A or 5 A through a test set and confirm that the output follows the expected linear scale. Record the scaling in the PLC, for example 20 mA equal to 5 A secondary, and then apply the transformer ratio in the control system so that operators see actual primary current. Remember that the measuring range is a signal range, not a protection function: overload protection of the motor should stay with a dedicated protection relay.

Comparison with related devices

Device Distinguishing data
MACX MCR-SL-CAC-5-I (this part) AC current 1 A / 5 A to 4-20 mA
MACX MCR-T-UIREL-UP Temperature transducer with relays
MACX MCR-UI-UI-NC Analogue signal conditioner
MACX MCR-VDC DC voltage transducer

Information to send with an RFQ for the MACX MCR-SL-CAC-5-I

  • Part number MACX MCR-SL-CAC-5-I and quantity.
  • Current transformer ratio and secondary current.
  • Output standard.
  • Supply voltage.
  • Mounting space.

Site conditions in Oman for the MACX MCR-SL-CAC-5-I

Control cabinets in Gulf plants often run hot, because many sit in outdoor kiosks or in rooms where air conditioning is not always reliable. Before you finalise the MACX MCR-SL-CAC-5-I, check the permitted ambient range and any derating stated by the manufacturer against the real temperature inside your panel, and leave the recommended spacing around the device so that heat can escape. Long cable runs between the field and the marshalling cabinet are common on large sites, so confirm the signal types, wiring limits and earthing arrangement early in the design.

It also helps to standardise on a small number of part numbers across a project. Keeping a few spare MACX MCR-SL-CAC-5-I units on site in Oman shortens recovery time after a fault, and documenting configuration settings makes replacement faster for the maintenance team.

Documents and quotation

Send us the part number MACX MCR-SL-CAC-5-I and the quantity you need, and we will confirm which official documents are available for this item. Seven Star LLC is an independent supplier in Muscat and quotes for projects across Oman and the GCC; we do not act on behalf of the manufacturer.

Please also tell us the delivery location and the project timeline so that availability can be checked before you commit to a schedule.

Datasheets & Documents
  • PDF Datasheet Phoenix Contact MACX MCR-SL-CAC-5-I Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Phoenix Contact is a German, family-owned manufacturer of electrical connection technology and industrial automation, founded in 1923 in Essen by Hugo Knümann. It began as a sales company, and in 1928 Knümann developed the modular terminal block mounted on a rail, the product the company is still best known for. Phoenix Contact is headquartered in Blomberg, North Rhine-Westphalia.

Seven Star LLC lists Phoenix Contact surge protection, power supplies and safety relays, and sources these components by order number for panel builders and maintenance teams in Oman.

Phoenix Contact company profile

Founded 1923, Essen, Germany, by Hugo Knümann, as Phönix Elektro- und Industrie-Bedarfsgesellschaft
Headquarters Blomberg, Germany
Ownership Family-owned (Eisert and Stührenberg families)
Key invention The modular terminal block on a DIN rail, 1928
Product families CLIPLINE terminal blocks, PCB terminals and connectors, QUINT and TRIO power supplies, relay modules, surge protection, signal conditioners, Ethernet switches and PLCnext controllers

Milestones

  • 1923: Hugo Knümann founds the company in Essen.
  • 1928: The first modular terminal block is developed.
  • Later: Headquarters move to Blomberg, Ostwestfalen-Lippe.

Phoenix Contact parts listed on this page

The TTC-6-2X1-24DC-UT (order number 2906799) is a surge protection device with screw connection for two 24 V DC signal wires that share a common reference potential. The QUINT-PS/1AC/24DC/10 is a single-phase DIN rail power supply delivering 24 V DC at 10 A. The PSR-SCP-24DC/ESP4/2X1/1X2 (order number 2981020) is a single-channel PSR safety relay for emergency stop and safety door monitoring, with two enabling current paths and plug-in screw terminals.

Phoenix Contact products we list

Family Examples
Isolator & Barrier 2906799 TTC-6-2X1-24DC-UT Surge Protector, MACX MCR-EX-SL-RPSSI-I Signal Isolator, MINI MCR-2-UI-UI 3-Way Signal Conditione…, PLT-SEC-T3-230-FM Type 3 Surge Protectio…
Power Modules QUINT-PS/1AC/24DC/10 QUINT Power Supply, QUINT4-PS/1AC/24DC/10 Power Supply, TRIO-PS-2G/1AC/24DC/10 Power Supply, UNO-PS/1AC/24DC/100W Power Supply
Automation Accessories PLC-RSC-24DC/21 Relay Module, PSR-SCP-24DC/ESP4/2X1/1X2 Safety Relay (…

Ordering Phoenix Contact components: what we need

Phoenix Contact items are ordered by a seven-digit order number together with the type designation, both printed on the side of the module. Send both, plus the quantity. If the number is unreadable, send the type text and a photo. For power supplies, state input voltage, output current and whether the unit runs in parallel or with a redundancy module. For buyers in the GCC replacing an older unit, we check the manufacturer's documentation for the listed successor type.

Facts checked against Phoenix Contact's own company history (phoenixcontact.com), October 2026.

FAQ

Questions about the Phoenix Contact MACX MCR-SL-CAC-5-I AC Current

Answers from our engineering team on installation, compatibility and integration.

01What does the MACX MCR-SL-CAC-5-I measure?
Alternating current up to 1 A or 5 A.
02What output signals are available?
0 to 20 mA or 4 to 20 mA, set by DIP switch.
03What is the accuracy?
Maximum transmission error of 0.5 % of the nominal range.
04What supply voltage is needed?
24 V DC, 19.2 to 30 V DC.
05What is the insulation rating?
Rated insulation voltage 300 V AC to earth.