Pepperl+Fuchs KCD2-SOT-2 2-Channel Transistor Switch Amplifier
Description
KCD2-SOT-2 two-channel transistor output switch amplifier
The KCD2-SOT-2 is a two-channel switch amplifier with passive transistor outputs. It takes NAMUR sensor or dry contact signals, isolates them and passes them to a control system input as fast electronic switching signals of up to 5 kHz. Compared with the relay version KCD2-SR-2, it has no moving parts and switches faster, which suits pulse and counting duty and PLC digital inputs that are sensitive to contact bounce.
Seven Star LLC supplies the KCD2-SOT-2 in Oman and the GCC as an independent supplier in Muscat.
KCD2-SOT-2 designation
The KCD2-SOT-2 belongs to the narrow 12.5 mm K-System housing family, and the datasheet names it a switch amplifier, a 2-channel signal conditioner with 24 V DC supply through the Power Rail and two passive transistor outputs. Its sibling KCD2-SR-2 has relay outputs. The datasheet gives SIL 2 with systematic capability SC 3 under IEC/EN 61508.
The transistor outputs are passive: they need an external supply from the control side. Rated voltage is 30 V DC and rated current 50 mA, and the 1-signal is the external voltage minus a maximum of 3 V.
Technical specifications of the KCD2-SOT-2
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Pepperl+Fuchs / KCD2-SOT-2 |
| Function | Switch amplifier, 2 channels, passive transistor outputs |
| Input | NAMUR (EN 60947-5-6) or dry contacts |
| Open circuit voltage / current | approx. 10 V DC / approx. 8 mA |
| Switching point / hysteresis | 1.2 … 2.1 mA / approx. 0.2 mA |
| Line fault detection | Breakage I ≤ 0.1 mA; short-circuit I ≥ 6.5 mA |
| Pulse / pause | min. 100 µs / 100 µs |
| Output rating | 30 V DC, 50 mA per output |
| Signal levels | 1-signal: external voltage minus 3 V max. at 50 mA; 0-signal: blocked, leakage ≤ 10 µA |
| Response time | ≤ 200 µs |
| Switching frequency | ≤ 5 kHz |
| Supply | 19 … 30 V DC; dissipation ≤ 800 mW |
| Functional safety | SIL 2, SC 3 |
| Ambient temperature | -20 … 60 °C; up to 70 °C with mounting conditions in the manual |
| Housing | Type A2, 12.5 x 119 x 114 mm, approx. 100 g, 35 mm DIN rail, IP20 |
How the KCD2-SOT-2 differs from a relay amplifier
The input stage and the line fault monitoring are the same as in the relay version: NAMUR current thresholds around 1.2 to 2.1 mA, cable break detection at 0.1 mA or below and short-circuit detection at 6.5 mA or more. What changes is the output stage. A solid-state transistor follows the input within 200 µs and can pulse up to 5 kHz, so rapidly changing signals from, for instance, a rotating toothed wheel are reproduced faithfully.
DIP switches reverse the operating mode and switch the fault detection off. A fault is shown by LEDs per NAMUR NE 44 and signalled on the collective error line of the Power Rail.
Because the output is a passive transistor, the load circuit must be powered by an external source of up to 30 V DC, which is normally the digital input module of the PLC.
The off-state leakage current of 10 µA or less is low enough not to hold a typical 24 V digital input in the on state, while the saturation drop of up to 3 V at 50 mA should be subtracted from the input threshold calculation. A PLC input that needs more than 50 mA, or inputs that sink large inrush currents, should be driven through the relay version or an interposing element instead.
Where to use the KCD2-SOT-2
Use it for PLC inputs that count pulses or that must avoid contact wear. For mains-voltage loads or inputs that need potential-free relay contacts, select the KCD2-SR-2 or, for load switching, the KFD2-RSH-1.2E.L3.
The module sits on the same Power Rail as the other KCD2 modules and can be powered through the KFD2-EB2 power feed.
Selection and ordering checklist for the KCD2-SOT-2
- Output type: transistor for high speed or relay for contacts
- PLC input compatibility, including external supply voltage and 50 mA limit
- Maximum pulse rate
- Fault detection settings
- Ambient temperature and extended-range mounting conditions
- Quantity of channels
Installation notes
Wire the NAMUR sensors to terminals 1 to 4 and the PLC inputs to terminals 5 to 8, observing polarity of the passive transistor outputs. Set DIP switches before power up.
To commission, check each channel with the sensor in the active and inactive state and test the cable fault function. Where the extended 70 °C range is needed, follow the mounting conditions in the manual.
Typical applications in Oman and the GCC
Speed and rotation pickups, limit switch signals feeding PLC inputs, and high-cycle counting in packaging, bottling and cement handling are good uses. In the Gulf, solid-state outputs also avoid contact corrosion in dusty or humid cabinets.
Power dissipation of the module is limited to 800 mW including the output stage, so full rows of these narrow modules remain a modest heat load even in cabinets with limited ventilation. Planning a spare module per major panel is advisable because the 12.5 mm family is normally replaced as a unit, without field repair.
Transistor and relay versions
Datasheet values.
| Part number | Output | Max. switching frequency | Life |
|---|---|---|---|
| KCD2-SOT-2 | Transistor | 5 kHz | Solid state |
| KCD2-SR-2 | Relay | 10 Hz | 107 cycles |
Information to send with an RFQ for the KCD2-SOT-2
Please supply the following.
- PLC input type and voltage
- Pulse rate
- Number of channels
- Quantity and delivery date
Documents and quotation
The manufacturer datasheet for the KCD2-SOT-2 is attached on this page, so the electrical data, terminal assignment and ambient limits quoted above can be checked against the original document before an order is placed.
Seven Star LLC supplies Pepperl+Fuchs products in Oman and the GCC as an independent supplier in Muscat. Send the quantity, the signal types and the project delivery date, and we will confirm availability and lead time in a written quotation.
Other Models in the Pf Kcd2 Range
Seven Star LLC supplies models from the Pf Kcd2 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Pepperl+Fuchs KCD2-STC-1 SMART Transmitter Power Supply 12.5 mm | Isolator & Barrier | View details |
| Pepperl+Fuchs KCD2-UT2-1 Universal Temperature Converter | Isolator & Barrier | View details |
| Pepperl+Fuchs KCD2-SR-2 2-Channel Relay Switch Amplifier | Isolator & Barrier | View details |
| Pepperl+Fuchs KCD2-SOT-2 2-Channel Transistor Switch Amplifier | Isolator & Barrier | You are viewing this model |
Datasheets & Documents
- Datasheet Pepperl+Fuchs KCD2-SOT-2 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.
Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.
Pepperl+Fuchs company profile
| Founded | 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs |
|---|---|
| Headquarters | Mannheim, Germany |
| Ownership | Privately owned (Pepperl+Fuchs SE) |
| Origins | Radio repair workshop that began making replacement transformers |
| Product families | Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures |
Milestones
- 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
- 1958: The first proximity switch is developed (some company sources say 1959).
Pepperl+Fuchs product families on this page
On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.
Where Pepperl+Fuchs equipment is used
Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.
Pepperl+Fuchs products we list
Ordering Pepperl+Fuchs parts: what we need
Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.
Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.
Browse Pepperl+Fuchs products by category: Sensors & Transmitters, Industrial Computer, Isolator & Barrier, Power Modules.
FAQ
Questions about the Pepperl+Fuchs KCD2-SOT-2 2-Channel Transistor
Answers from our engineering team on installation, compatibility and integration.
01What type of output does the KCD2-SOT-2 have?
Two passive transistor outputs rated 30 V DC and 50 mA.
02How fast can it switch?
Up to 5 kHz with a response time of 200 microseconds or less.
03Which inputs does it support?
NAMUR sensors and dry contacts with line fault detection.
04What is the temperature range?
-20 to 60 degrees C, and up to 70 degrees C when the mounting conditions in the manual are followed.
05What SIL level is stated?
SIL 2 with systematic capability SC 3.