E2S BExS110 Explosion Proof Alarm Horn Sounder
Description
A flameproof alarm horn for Zone 1, 2, 21 and 22 plant areas
The E2S BExS110 is an Ex d explosion proof alarm horn sounder with a flare re-entrant horn in a corrosion-proof, marine-grade, copper-free LM6 aluminium enclosure. It gives sound output of up to 117 dB(A) at 1 metre, with a choice of 32 alarm tones and 3 remotely selectable stages, and is approved to IECEx, ATEX, Ex EAC and INMETRO standards. SIL 1 and SIL 2 versions are available. For fire applications, the BExS110D 24 V dc siren is stated to be MED compliant and EN54-3 tested.
Typical uses are process plant, tank farms, offshore and onshore platforms, loading terminals and pump stations where the general alarm, toxic gas alarm or abandon-platform tone must be audible over machinery noise.
Technical specifications
| Parameter | Specification |
|---|---|
| Product type | BExS110 explosion proof alarm horn sounder (DF: Ex d, flare re-entrant horn) |
| Hazardous area use | Zone 1, 2, 21 and 22 |
| ATEX / IECEx coding | II 2G Ex db IIB T4 Ta -50 to +70 degC; II 2G Ex db IIC T4 Ta -50 to +55 degC; II 2D Ex tb IIIC T100 degC Db Ta -50 to +55 degC; II 2D Ex tb IIIC T115 degC Db Ta -50 to +70 degC |
| Certificates | IECEx KEM 10.0003X; ATEX KEMA 99ATEX6312X; Ex EAC RU C-GB.HA65.B.01252_21; INMETRO 10-IEx-0009; UKCA UL22UKEX2638X; VdS G206011; CPD 0786-CPD-20225; MED MEDB00001BU; CCOE PESO |
| Maximum output | 117 dB(A) at 1 m (108 dB(A) at 3 m) |
| Nominal output | 110 dB(A) at 1 m +/-3 dB, tone 2 |
| Volume control | Max. 110 dB(A), min. 72 dB(A), tone 2 |
| Tones and stages | 32 tones (UKOOA / PFEER compliant), 3 stages; stage programmable version has 45 tones and 4 stages |
| Effective range | 100 m at 1 kHz |
| Supply voltages | 12, 24, 48 V dc; 115, 230 V ac (50/60 Hz) |
| Current consumption | 12 V dc 195 mA; 24 V dc 265 mA; 48 V dc 130 mA; 115 V ac 110 mA; 230 V ac 56 mA |
| Ingress protection | IP66/67 |
| Cable entries | Dual M20 x 1.5 (one stopping plug included); NPT and M25 adaptors available |
| Terminals | 0.5 to 2.5 mm2 (20 to 14 AWG) |
| Temperature range | -50 to +70 degC |
| Weight | DC 3.00 kg; AC 3.20 kg |
| Safety integrity | SIL 1 and SIL 2 Route 2H to IEC 61508 (2010); S1 version SIL 2 Route 1H with diagnostics, SFF above 99 percent |
Ordering code and versions
The part code is built from the product type, horn type (DF), supply voltage (DC012, DC024, DC048, AC115, AC230), cable entry (A to G), stopping plug and adaptor material (brass, nickel-plated or stainless steel), bracket material (A2 304 or A4 316, with or without equipment tag), product version and enclosure colour. Versions are A1 default (SIL 1 and SIL 2 Route 2H), M1 MED (24 V dc only), P1 stage programmable, S1 SIL 2 Route 1H with diagnostics and T1 tropicalised. Accessories listed are the SP65-0001-A4 pole mount bracket kit and the SP65-0003-A4 sunshade, both in 316 stainless steel.
What to confirm before ordering
Confirm the gas group (IIB or IIC) and ambient temperature, which set the allowed T4 rating, the supply voltage, the cable gland thread, the tone and stage plan agreed with the plant alarm philosophy, and whether a SIL claim is needed. E2S advises additional tropicalisation where high humidity and high ambient temperature occur together. Combined horn and beacon units are also available, for example the E2S BExCS110-05, and further units are listed under fire and gas detection.
How the E2S BExS110 works
An electronic oscillator drives a horn driver inside the flameproof enclosure. The sound leaves through a flare re-entrant horn that boosts the output. A switch selects the tone, and the stage inputs let the control system change the alarm remotely. A wide range of supplies is available.
Where the BExS110 is used
- Process plant
- Tank farms
- Offshore and onshore platforms
- Loading terminals
- Pump stations
Selection checklist for the BExS110
- Supply voltage, dc or ac
- Tone and stage needs
- Sound level at the listener
- Cable entry type
- Ambient temperature
- Safety integrity version
- Fixing position
- Ordering code
Installation, commissioning and maintenance notes for the BExS110
Fix the horn with the bell pointing down or across. Fit a suitable gland to one M20 entry and close the second with the plug. Wire the supply to the terminals. Set the tone with the selector and test the sound level at the listener.
Requesting a quotation for the E2S BExS110
Please send the supply voltage, the tones, the entries and the version needed. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.
BExS110 sound output
The maximum output is 117 dB(A) at 1 metre.
BExS110 volume control
The volume can be set between 72 and 110 dB(A) on tone 2.
BExS110 tones
There are 32 tones and 3 stages.
BExS110 effective range
The effective range is 100 m at 1 kHz.
BExS110 supply voltages
The supplies are 12, 24 and 48 V dc and 115 and 230 V ac.
BExS110 current draw
The current is 265 mA at 24 V dc and 56 mA at 230 V ac.
BExS110 ingress protection
The enclosure is rated IP66/67.
BExS110 cable entries
It has two M20 x 1.5 entries, with NPT and M25 adaptors available.
BExS110 weight
The weight is 3.00 kg for dc and 3.20 kg for ac versions.
Sounder records for the BExS110
Record the tone setting, the supply and the date of each alarm test.
Choosing the right BExS110 tone
Choose the tone that the site alarm plan assigns to each event, and keep general and gas alarms distinct.
BExS110 horn type
The horn is a flare re-entrant type in a marine-grade LM6 aluminium enclosure.
BExS110 terminals
The terminals take wires of 0.5 to 2.5 mm2.
BExS110 temperature range
The operating range is minus 50 to plus 70 degrees C.
BExS110 safety integrity
SIL 1 and SIL 2 versions are available.
Documents and quotation
The attached E2S datasheet (revision of 4 Feb 2026) includes the tone table, the full part code and the approvals. Send the complete part code, the quantity and the project area classification with your enquiry.
See also: E2S GNExCP7-BG Explosion-Proof Break Glass Manual Call Point.
Datasheets & Documents
- Datasheet E2S BExS110 alarm horn sounder datasheet (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
E2S, European Safety Systems Ltd, is a British manufacturer of audible and visual signalling devices for hazardous and industrial locations, formed in 1992 and headquartered in London, with its design and production in West London. Its range includes explosion-proof and intrinsically safe sounders, beacons, combined units and manual call points. Halma plc acquired E2S for £230 million in December 2025.
Seven Star LLC sources and supplies E2S explosion-protected alarm sounders and xenon beacons for fire and gas systems in Oman, including the GNEx and BEx models shown on this page.
E2S company profile
| Founded | 1992, London, United Kingdom |
|---|---|
| Headquarters | London; manufacturing in West London |
| Other operations | USA and France |
| Ownership | Halma plc, since December 2025 |
| Product families | GNEx and D1x explosion-proof sounders, beacons and call points, BExS and BExCS sounders and combined units, IS-range intrinsically safe sounders and beacons, industrial alarm horns and strobes |
Milestones
- 1992: European Safety Systems is formed.
- 2025: Halma acquires E2S for £230 million.
E2S hazardous-area families
E2S groups its Ex signals by family. GNEx and BEx are both for Zone 1 and Zone 21, and the STEx family covers the same zones. D1x and D2x are the lines for Class/Division sites, and the IS family is intrinsically safe for Zone 0. The listed items show the pattern: GNExS1F is an alarm horn sounder, GNExB2X10 a xenon strobe beacon and BExCS110-05 a combined sounder and beacon.
E2S products we list
Ordering E2S signals: what we need
An E2S part number is completed by suffixes for supply voltage, lens color, cable entries and options, so send the whole code from the label. For a new requirement give the area classification, gas group and temperature class, voltage, lens color, entry thread, and the approval your project needs. Many GCC projects name IECEx or ATEX in the specification.
Facts checked against Halma's December 2025 acquisition announcement and E2S company profiles, October 2026.
Browse E2S products by category: Fire & Gas Detector.
FAQ
Questions about the E2S BExS110 Explosion Proof Alarm Horn Sounder
Answers from our engineering team on installation, compatibility and integration.
01What area classification is the BExS110 approved for?
Zone 1, 2, 21 and 22, with Ex db IIB/IIC and Ex tb IIIC coding as printed in the datasheet.
02How loud is the BExS110?
Up to 117 dB(A) at 1 m, with a nominal 110 dB(A) at 1 m +/-3 dB for tone 2.
03How many tones does it have?
32 tones and 3 remotely selectable stages; the stage programmable version has 45 tones and 4 stages.
04Which supply voltages are available?
12, 24 and 48 V dc and 115 and 230 V ac.
05What is the ingress protection?
IP66/67.