Brand:

ABB XT3N 250 TMD 200-2000 3p F F 50C 1SDA070162R1

Description

XT3N 250 TMD 200-2000: a 200 A breaker from the 250 A Tmax XT3 frame

XT3N 250 TMD 200-2000 3p F F 50C (order code 1SDA070162R1) is a fixed three-pole breaker from the Tmax XT3 frame, which is sized for 250 A. This unit is the 200 A step, with the performance level N (36 kA at 415 V AC) and a thermomagnetic TMD trip unit calibrated at 50 C.

At this rating the breaker is usually applied as the incomer or feeder protection of a sub-distribution board. The XT3 uses TMD trip units with a fixed instantaneous threshold.

Technical specifications

Parameter Specification
Order code 1SDA070162R1
Type designation XT3N 250 TMD 200-2000 3p F F 50C
Frame / breaking class Tmax XT3, size 250 A, performance level N: Icu 36 kA at 415 V AC
Rated current In 200 A (I1 adjustable 140 to 200 A)
Short-circuit trip I3 2000 A, fixed at 10 x In (TMD)
Poles 3 poles under this code; 4-pole version 1SDA070169R1 (neutral 100 %)
XT3 TMD range in the catalogue In 63 to 250 A; 50 % neutral available for In 125 A and above (125 A neutral at the 200 A rating)
Standard / protection IEC 60947-2; moulded-case circuit-breaker, fixed version with front terminals (F F)
Calibration Thermomagnetic trip unit calibrated at 50 C (this is the 50 C code, not the standard 40 C code)
Overload protection (L) Adjustable I1 = 0.7 to 1 x In, inverse long-time curve

Trip behaviour and neutral options

The overload threshold is adjustable from 0.7 to 1 x In, which gives 140 to 200 A for this breaker. The instantaneous threshold is fixed at 10 x In, that is 2000 A. Because the magnetic trip is not adjustable, the downstream cables and the upstream selectivity have to be checked with this fixed value in mind.

For the four-pole breaker (1SDA070169R1), the neutral can be 100 percent. The catalogue also lists a 50 percent neutral for In of 125 A and above; for the 200 A rating the 50 percent neutral values are 125 A thermal and 1250 A magnetic.

Disconnector and range context

The XT3 range runs from 63 A to 250 A. The matching XT3D 250 switch-disconnector (1SDA068210R1, three poles) is rated Icw 3 kA and complies with the AC21A, AC22A and AC23A utilisation categories, with 200 A in AC23.

For the performance level S (50 kA at 415 V), the catalogue lists the XT3S 250 TMD 200-2000 under 1SDA070176R1, which is a different order code; choose according to the available fault level.

Documents and quotation

The linked file is the ABB SACE Tmax XT 50 C technical catalogue – ordering codes 1SDC210064D0201. Seven Star LLC supplies the 1SDA070162R1 on request from Muscat as an independent supplier; availability and lead time are given in the quotation. More products of this kind are in the Circuit Breakers category, and a related item is the ABB SACE Tmax XT moulded case circuit breaker family page.

Confirm before ordering: the calibration temperature (this code is the 50 C version), number of poles and neutral rating, the prospective short-circuit current at the installation, the trip setting needed and any accessories such as shunt or undervoltage releases.

Datasheets & Documents
  • PDF Catalogue ABB SACE Tmax XT 50 C technical catalogue - ordering codes 1SDC210064D0201 Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB XT3N 250 TMD 200-2000 3p F F 50C 1SDA070162R1

Answers from our engineering team on installation, compatibility and integration.

01What is the order code of the XT3N 250 TMD 200-2000 3p F F 50C?
1SDA070162R1; the four-pole version is 1SDA070169R1.
02What is the instantaneous trip setting?
Fixed at 10 x In, which is 2000 A for the 200 A unit.
03What is the breaking capacity?
Icu 36 kA at 415 V AC for performance level N.
04Is there a higher-breaking version?
Yes, the XT3S version (50 kA at 415 V) under 1SDA070176R1.
05What is the thermal setting range?
140 to 200 A, adjustable 0.7 to 1 x In.