ABB S801S-C16 S800S High Performance MCB, 16 A Curve C
Description
S801S-C16 1-pole 16 A curve C breaker explained
The ABB S801S-C16 is a single-pole miniature circuit breaker from the S800S High Performance range, with a rated current of 16 A and tripping characteristic C. It breaks up to 50 kA at 240/415 V AC under IEC/EN 60947-2 and is suitable for isolation. The ABB order code is 2CCS861001R0164. In the type name, S801 is the pole count (1), the letter S the version (standard high-performance), C the curve and 16 the rated current in amperes.
The instantaneous release picks up between 5 and 10 times the rated current on AC, the usual compromise between sensitivity and immunity to switching peaks. Typical duties are mixed circuits with moderate inrush: lighting panels with discharge lamps, small motors, socket circuits and general distribution feeders. At 16 A the magnetic release operates at 80 to 160 A (5 to 10 × In), and the thermal release starts to act at 1.13 to 1.3 × In of the rated current.
S801S-C16 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | ABB / S801S-C16 |
| Order code | 2CCS861001R0164 |
| EAN | 7612271200503 |
| Series | S800S High Performance MCB |
| Poles | 1 |
| Tripping characteristic | C |
| Rated current In | 16 A |
| Rated frequency | 50/60 Hz |
| Rated insulation voltage Ui | AC 690 V |
| Rated impulse withstand voltage Uimp | 8 kV (1.2/50 µs) |
| Rated ultimate short-circuit capacity Icu (IEC/EN 60947-2) | 50 kA at AC 240/415 V; see table below for other voltages |
| Rated short-circuit capacity Icn (IEC/EN 60898-1) | 25 kA at 230/400 V AC |
| Thermal release | 1.13 to 1.3 × In (reference temperature 30 °C) |
| Magnetic release (AC) | 80 to 160 A (5 to 10 × In) |
| Terminals | Failsafe cage terminal, 1 to 50 mm² stranded, 1 to 70 mm² flexible, Cu only, 3.5 Nm |
| Pole dimensions (H × L × W) | 82.5 × 95 × 26.5 mm per pole |
| Weight | 0.24 kg |
| Ambient / storage temperature | −25 to +60 °C / −40 to +70 °C |
| Protection degree | IP20; IP40 at the actuating end |
| Mounting | 35 mm DIN rail to EN 60715, any position, any supply direction |
| Internal resistance / power loss per pole at 25 °C | 12.1 mΩ / 3.1 W |
| Maximum Zs for 0.1 s disconnection (Uo 230 V) | 1.5 Ω |
How the S801S-C16 protects the circuit
Two releases work together. A bimetal thermal element heats with the load current and opens the contacts on sustained overload; the delay shortens as the overload grows. An electromagnetic release reacts to short-circuit current without delay. For the S801S-C16 the thermal element is calibrated at 30 °C, so at higher cabinet temperatures it trips earlier and the usable current falls. Panel builders in hot sites should check the loading with the manufacturer derating information before fixing the final rating.
The contact system is built for high breaking capacity in a housing of 26.5 mm per pole; the complete 1-pole breaker is about 26.5 mm wide. Rated service short-circuit capacity (Ics) is 40 kA at 240/415 V AC for the S800S ratings.
Breaking capacity of the S801S-C16 at different voltages
| Voltage | Icu (IEC/EN 60947-2) |
|---|---|
| 240/415 V AC | 50 kA |
| 254/440 V AC | 30 kA |
| 289/500 V AC | 15 kA |
| 400/690 V AC | 6 kA |
For direct current, the S800S single-pole-pole version is rated 30 kA at DC 125 V (series total as listed by the manufacturer: 30 kA at DC 125 V (1-pole), 250 V (2-pole), 375 V (3-pole) and 500 V (4-pole)). Always check the voltage of the supply system against this table; the same breaker offers very different capacity at 415 V and at 690 V.
Where the S801S-C16 fits and which parts go with it
The breaker is part of the S800 system. Accessories snap on to the side: the S800-AUX auxiliary contact, the S800-AUX/ALT auxiliary/signal contact, the S800-SOR shunt trip, the S800-UVR undervoltage release and the S800-NT disconnectable neutral. DDA800 residual-current blocks can be added to build an RCBO assembly, and the S800-RSU remote operating unit is available for remote switching. Siblings that you may need in the same panel: S802S-C16, S803S-C16, S804S-C16.
S801S-C16 and neighbouring single-pole curve C ratings
| Type | Rated current | Order code | Weight |
|---|---|---|---|
| S801S-C10 | 10 A | 2CCS861001R0104 | 0.24 kg |
| S801S-C13 | 13 A | 2CCS861001R0134 | 0.24 kg |
| S801S-C16 | 16 A | 2CCS861001R0164 | 0.24 kg |
| S801S-C20 | 20 A | 2CCS861001R0204 | 0.24 kg |
| S801S-C25 | 25 A | 2CCS861001R0254 | 0.24 kg |
The rated current can be stepped up or down one size without changing the enclosure layout, but the cable cross-section, the upstream protection and the selectivity study must be checked again whenever the rating changes.
Selection checklist for the S801S-C16
- Rated current 16 A against the real load, cable ampacity and the ambient temperature in the enclosure
- Curve C against the inrush of the connected load; moving to another curve changes the magnetic threshold from 80 to 160 A (5 to 10 × In)
- Pole count (1) against the system: single-phase or DC feeder up to 125 V DC, or one phase of a three-phase system
- Prospective short-circuit current at the installation point against Icu of 50 kA at 240/415 V AC and the lower values at higher voltage
- Required accessories: auxiliary contacts, shunt trip, undervoltage release or RCD block
Installing and maintaining the S801S-C16
Mount the breaker on a 35 mm DIN rail to EN 60715; any mounting position and either supply direction are permitted. Strip the conductors to the length marked on the terminal, torque the cage terminals to 3.5 Nm with a Pozidriv 2 driver, and use copper conductors only. After energising, operate the toggle a few times and check the contact position. At the next service interval re-torque the terminals, check for discolouration from hot connections, and use the breaker’s test operation rather than a live short circuit to confirm function. Electrical endurance is 10,000 electrical and mechanical operations.
Using the S801S-C16 in Oman and the GCC
High ambient temperatures in switchrooms, dust-laden desert air and humid coastal sites all affect miniature breakers. The S801S-C16 has an ambient rating of up to 60 °C and was tested under cyclic damp heat, which suits motor control centres, pump stations, desalination auxiliaries, oil and gas skids and power distribution boards. A single-pole breaker on curve C is typically chosen here for mixed circuits with moderate inrush: lighting panels with discharge lamps, small motors, socket circuits and general distribution feeders. Because the thermal element is calibrated at 30 °C, panels that run hot should be derated deliberately rather than by trial.
Information to send with an RFQ for the S801S-C16
- Full type name S801S-C16 and order code 2CCS861001R0164
- Quantity and whether loose breakers or a complete panel assembly is needed
- System voltage, AC or DC, and prospective short-circuit current
- Load description and any accessories (auxiliary contacts, trips, RCD block)
- Delivery location in Oman or elsewhere in the GCC
Documents and quotation
Send the part number S801S-C16 and the quantity and we will confirm available documents and the supply details. The type and order code above follow the manufacturer’s published ordering data.
Seven Star LLC supplies ABB low-voltage protection in Oman and the GCC from Muscat, together with contactors, overload relays and drives.
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB S801S-C16 S800S High Performance MCB, 16 A
Answers from our engineering team on installation, compatibility and integration.
01What is the ABB S801S-C16?
It is a single-pole MCB of the ABB S800S range with 16 A rated current and tripping characteristic C. It breaks 50 kA at 240/415 V AC and is suitable for isolation.
02At what current does the S801S-C16 trip magnetically?
With characteristic C the instantaneous release acts at 80 to 160 A (5 to 10 x In) on AC. The thermal release begins to act at 1.13 to 1.3 x In of the rated current at a reference temperature of 30 deg C.
03What is the breaking capacity of the S801S-C16?
The rated ultimate breaking capacity is 50 kA at AC 240/415 V, falling with voltage as listed in the table; at 400/690 V it is 6 kA.
04Can the S801S-C16 be used on DC?
Yes within limits: the 1-pole version is rated for DC 125 V, and the manufacturer lists a DC breaking capacity of 30 kA at that voltage. Polarity and time constant must be checked for the application.
05Which accessories fit the S801S-C16?
The S800 side-mounting accessories fit: auxiliary contact S800-AUX, auxiliary/signal contact S800-AUX/ALT, shunt trip S800-SOR, undervoltage release S800-UVR, neutral S800-NT and DDA800 RCD blocks.